4
System with MGE UPS shuts down too early
Hello, I'm experiencing a strange early shutdown behavior with the following system: * */OS/*: Slackware Linux 14.2 x86_64 * */NUT/*: 2.7.4 (from my own package <https://sotirov-bg.net/slackpack/pack.cgi?id=4083>) * */UPS/*: MGE Ellipse PRO 1600 <powerquality.eaton.com/Products-services/Backup-Power-UPS/Ellipse-PRO.aspx> (bought in September 2017) */Problem description/*: An hour ago there was a power outage for about 3-4 minutes. However, the system w...
2020 Jan 11
0
System with MGE UPS shuts down too early
On January 11, 2020 1:18:27 PM GMT+02:00, "Georgi D. Sotirov" <gdsotirov at gmail.com> wrote: >Hello, > >I'm experiencing a strange early shutdown behavior with the following >system: > > * */OS/*: Slackware Linux 14.2 x86_64 > * */NUT/*: 2.7.4 (from my own package > <https://sotirov-bg.net/slackpack/pack.cgi?i...
2020 Jan 11
1
System with MGE UPS shuts down too early
On January 11, 2020 3:42:15 PM GMT+02:00, Roger Price <roger at rogerprice.org> wrote: >On Sat, 11 Jan 2020, Georgi D. Sotirov wrote: > >> Jan 11 11:49:15 sotirov-bg upsmon[2677]: UPS mgeups at localhost on >battery >> Jan 11 11:49:15 sotirov-bg upssched[29746]: Executing command: >ups-on-battery >> Jan 11 11:49:15 sotirov-bg upssched-cmd: Unrecognized command: >ups-on-battery > >These l...
2020 Jan 11
4
System with MGE UPS shuts down too early
OK. I'll try it, but it really puzzles me how the battery could have gone bad for just 15 months. The online power is pretty stable, so the battery hasn't gone through many charge/discharge cycles... Regards, -- Georgi On 11.1.2020 at 14:24, Manuel Wolfshant wrote: > > indicates that the UPS thought that battery was close to depleted and decided to shutdown. I suggest to fully
2020 Jan 11
0
System with MGE UPS shuts down too early
On Sat, 11 Jan 2020, Georgi D. Sotirov wrote: > Jan 11 11:49:15 sotirov-bg upsmon[2677]: UPS mgeups at localhost on battery > Jan 11 11:49:15 sotirov-bg upssched[29746]: Executing command: ups-on-battery > Jan 11 11:49:15 sotirov-bg upssched-cmd: Unrecognized command: ups-on-battery These lines say that you have something lik...
2020 Jan 24
0
System with MGE UPS shuts down too early
...sable SHUTDOWNCMD in upsmon.conf? Or is there any other way to ignore forced shutdown? I'd like to see how long it would go until the batteries actually drain. Regards, -- Georgi On 12.1.2020 at 12:43, Manuel Wolfshant wrote: > On January 12, 2020 12:27:38 PM GMT+02:00, "Georgi D. Sotirov" <gdsotirov at gmail.com> wrote: >> You have a point, but how to check the actual manufacturing date? > Some UPSes return this date whem intetogated with upsc > Otherwise... examine carefully the labels of the UPS > Regards > wolfy > >> >> Regards, >&g...
2020 Jan 27
1
Nut-upsuser Digest, Vol 175, Issue 30
...> than "Re: Contents of Nut-upsuser digest..." > > > Today's Topics: > > 1. Re: Timer doesn't appear to start (Roger Price) > 2. Re: System with MGE UPS shuts down too early (nicolae788) > 3. Re: System with MGE UPS shuts down too early (Georgi D. Sotirov) > > > ---------------------------------------------------------------------- > > Message: 1 > Date: Mon, 27 Jan 2020 09:31:49 +0100 (CET) > From: Roger Price <roger at rogerprice.org> > To: nut-upsuser Mailing List <nut-upsuser at lists.alioth.debian.org> > S...
2020 Jan 24
2
System with MGE UPS shuts down too early
On January 24, 2020 6:13:31 PM GMT+02:00, "Georgi D. Sotirov" <gdsotirov at gmail.com> wrote: >OK, my UPS turned out to be older that I thought. I apparently bought >and installed it in September 2016 (not 2017 as I initially wrote). >That >makes for over 3 years of work, which is over the life expectancy of >the >batteries,...
2020 Jan 27
3
System with MGE UPS shuts down too early
On 1/25/20 10:53 AM, Georgi D. Sotirov wrote: > OK, so yesterday evening I done a real test cutting of the power to > the UPS. And it went good... the UPS supported my server for 28:50 > minutes (i.e. the expected runtime with this load), before forcing > shutdown. The batteries could still hold as charge was 30 % with ab...
2012 Sep 02
1
CELT 0.11.3 tandem test fails
...#39;m upgrading to it); * Lower optimization level (i.e. -O2) makes not difference; * I wasn't able to find anything useful by Googling the error messages. Let me know if I could help you with more information and I hope you're resolve the problem soon. Best regards, -- *Georgi D. Sotirov* -------------- next part -------------- An HTML attachment was scrubbed... URL: http://lists.xiph.org/pipermail/opus/attachments/20120903/4ca010de/attachment-0001.htm -------------- next part -------------- A non-text attachment was scrubbed... Name: signature.asc Type: application/pgp-signature...
2020 Jan 11
0
System with MGE UPS shuts down too early
On January 11, 2020 3:02:59 PM GMT+02:00, "Georgi D. Sotirov" <gdsotirov at gmail.com> wrote: >OK. I'll try it, but it really puzzles me how the battery could have >gone bad for just 15 months. The online power is pretty stable, so the >battery hasn't gone through many charge/discharge cycles... It also depends on the actual ma...
2020 Jun 18
0
Please share experience with PowerWalker UPSes
...PowerWalker UPSes? Would you recommend them or rather not? What I should consider? One thing that concerns me is that I do not see variables battery.charge and battery.runtime to be supported and for me this is important information. Thanks in advance for your answers! Regards, -- Georgi D. Sotirov -------------- next part -------------- An HTML attachment was scrubbed... URL: <http://alioth-lists.debian.net/pipermail/nut-upsuser/attachments/20200618/19d7d564/attachment.html>
2020 Jan 27
0
System with MGE UPS shuts down too early
...running multiple tests with a load (car headlight bulb or similar) on the battery outside the ups. This is to eliminate the suspicion of a software or UPS unit fault. Alex. On Mon, 27 Jan 2020, 02:53 Manuel Wolfshant, <wolfy at nobugconsulting.ro> wrote: > On 1/25/20 10:53 AM, Georgi D. Sotirov wrote: > > OK, so yesterday evening I done a real test cutting of the power to the > UPS. And it went good... the UPS supported my server for 28:50 minutes > (i.e. the expected runtime with this load), before forcing shutdown. The > batteries could still hold as charge was 30 % with...
2020 Jan 25
0
System with MGE UPS shuts down too early
...UPS is not waiting for the preset low battery charge value of 15%? What is actually driving this FSD ALARM and LB signal when batteries for sure could hold up more? Regards, -- Georgi On 24.1.2020 at 18:28, Manuel Wolfshant wrote: > On January 24, 2020 6:13:31 PM GMT+02:00, "Georgi D. Sotirov" <gdsotirov at gmail.com> wrote: >> OK, my UPS turned out to be older that I thought. I apparently bought >> and installed it in September 2016 (not 2017 as I initially wrote). >> That >> makes for over 3 years of work, which is over the life expectancy of >&gt...