2014 Oct 02
2
Socomec ITYS 3000 + Netvision upsmon output
On 02.10.2014 03:42, Charles Lepple wrote:
> On Oct 1, 2014, at 5:07 AM, Tarvo.Tiits at automaatika.ee wrote:
>
>> Why is ups.status empty?
> If I understand the commit log for SVN r3590, then that revision was supposed to set the status to OL if the numeric state was 9 for ECO mode. It does not appear to do that:
>
> https://github.com/networkupstools/nut/commit/9cb2de3d9568aa382cc118b4385d97d5664c457b
>
> Is your UPS set to ECO mode? Can you do a snmpget on .1.3.6.1.4...
2014 Oct 02
0
Socomec ITYS 3000 + Netvision upsmon output
On Oct 1, 2014, at 5:07 AM, Tarvo.Tiits at automaatika.ee wrote:
> Why is ups.status empty?
If I understand the commit log for SVN r3590, then that revision was supposed to set the status to OL if the numeric state was 9 for ECO mode. It does not appear to do that:
https://github.com/networkupstools/nut/commit/9cb2de3d9568aa382cc118b4385d97d5664c457b
Is your UPS set to ECO mode? Can you do a snmpget on .1.3.6.1.4.1.4555.1.1.1.1.4....
2014 Oct 02
0
Socomec ITYS 3000 + Netvision upsmon output
...ct 2, 2014, at 1:53 AM, Tarvo Tiits <Tarvo.Tiits at automaatika.ee> wrote:
> On 02.10.2014 03:42, Charles Lepple wrote:
>> On Oct 1, 2014, at 5:07 AM, Tarvo.Tiits at automaatika.ee wrote:
>>
>>> Why is ups.status empty?
>> If I understand the commit log for SVN r3590, then that revision was supposed to set the status to OL if the numeric state was 9 for ECO mode. It does not appear to do that:
>>
>> https://github.com/networkupstools/nut/commit/9cb2de3d9568aa382cc118b4385d97d5664c457b
>>
>> Is your UPS set to ECO mode? Can you do a snm...
2014 Oct 01
2
Socomec ITYS 3000 + Netvision upsmon output
Hi,
I have UPS Socomec ITYS 3000 with Netvision card.
OS is Centos 6.5 64-bit.
NUT installed with yum,.
nut-2.6.5-2.el6.x86_64
nut-client-2.6.5-2.el6.x86_64
Why is ups.status empty?
Here is upsc output:
upsc myups at localhost
battery.charge: 97.00
battery.runtime: -60.00
battery.voltage: -0.10
device.mfr: Net Vision v6.01 (SN 0101414290)
device.model: ITYS 3 kVA
device.serial: 3I14450043