2010 Sep 19
1
Final R3000XR tip
On the basis of continuing experience, one final piece of R3000XR battery pack advice: After swapping the R3000XR battery pack, power-cycle the UPS, wait until the battery pack is at least 50% charged, then disconnect the UPS from wall power for a minute or so before plugging it back in. Until I did this, my UPS would charge the battery pack fully, then let...
2010 Sep 09
2
HP R3000XR charge level
This is not a NUT question per se ... or at least, I don't think it is. I just replaced the battery pack in my HP R3000XR; the new batteries were shipped with 90% charge, were at about 87% when they went in, and were up to 98% charge the next day. Last weekend, the server that runs NUT went down for no apparent reason, wiping out its boot blocks, corrupting its boot archive beyond repair, and forcing an OS reinst...
2010 Sep 17
0
FYI: HP R3000XR
I posted earlier about a problem with a HP R3000XR that was showing abnormally low charge a couple of days after replacing the battery pack. For those with R3000XRs, the progblem seems to be: (1) while you CAN hot-swap the battery-pack on an R3000XR, the UPS automatically goes into bypass mode when you do so; (2) it doesn't necessarily...
2009 May 27
2
New NUT user with HP R3000XR problem
Greetings, I've just installed nut-2.4.1 on a Solaris 10 x86 machine to monitor a HP R3000XR UPS. SunOS babylon4 5.10 Generic_138889-08 i86pc i386 i86pc Solaris First of all, I encountered a single problem during the build. After configuring, drivers/Makefile ends up containing the following line: LIBNETSNMP_LDFLAGS = -R../lib -L/usr/sfw/lib -lnetsnmp -lgen [...] This is clearly wro...
2012 Jan 03
1
2 different APC UPS using USB get in power off recoverable state
...eb 8 03:49:55 PST 2010 armv5tel GNU/Linux I have hand installed Network UPS Tools upsstats 2.4.3 from source. ups.conf: [apc1500] driver = usbhid-ups port = auto serial=AS0535132782 # powers switches and routers [Smart-UPS_3000] driver = usbhid-ups port = auto serial=JS1030003421 [R3000XR] port = /dev/ttyUSB0 driver = bcmxcp The R3000XR did work, but neither apc1500 nor Smart-UPS_3000. I tried restarting nut, I tried in other linux servers (just plugging in and seeing dmesg). Nothing helped. So I scheduled downtime and powered off the UPses. That did help, and since that nut h...
2017 Apr 03
4
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...[ALARM OL] NA NA 20170403 154155 100 230.4 21.4 [ALARM OL] NA NA root at dkfitlet:/etc/nut# upsmon -DDD Network UPS Tools upsmon 2.7.2 kill: No such process 0.000000 UPS: apc1500 at localhost (monitoring only) 0.000214 UPS: Smart-UPS_3000 at localhost (monitoring only) 0.000328 UPS: R3000XR at localhost (monitoring only) 0.001278 Using power down flag file /etc/killpower 0.002126 debug level is '3' 0.005831 Init SSL without certificate database 0.011754 Trying to connect to UPS [apc1500 at localhost] 0.013150 Can not connect to localhost in SSL, continue un...
2010 Feb 08
2
question about multi ups monitoring and reactions with nut
-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA1 Hello everybody, I have a Debian network server doing monitoring for three UPS devices. > MONITOR r3000xr at localhost 1 monuser xxxxxxxxxx master > MONITOR apcups01 at localhost 1 monuser xxxxxxxxx monitor-only > MONITOR apcups02 at localhost 1 monuser xxxxxxxxx monitor-only I want nut to send an email to root for every changes nut detects to any of the UPS devices. The network server itself i...
2005 Nov 07
3
HP/Compaq Rackmount UPS Support?
Hi, I have an HP R5500XR and a Compaq R3000XR that I would like to use with nut. I searched the compatibility lists and the mail list archives but couldn't find anything. They both have 9 pin serial ports. Can anyone give me any information about them, and if they are supported by nut? Thanks, Denny Fox
2013 Aug 07
0
HP R1500 G3 problems
...at softjury.de> wrote: > Hi there, > > OS: (L)ubuntu 12.04 precise LTS > Nut: 2.6.3-1ubuntu1.1 > Installation Method: Package (apt-get install nut) > Hardware: HP R1500 G3 INT FYI: I have a different UPS, a HP R3000 XR and I monitor it using serial and the bcmxcp driver. [R3000XR] port = /dev/ttyUSB0 driver = bcmxcp
2009 May 28
1
NUT upsstats.cgi problem
I seem to have NUT all working with my R3000XR, except for the CGIs. The webserver's all properly configured and upsstats.cgi *runs*, but doesn't yield any useful output - no values are displayed, every value is replaced by [error: Invalid argument]. Apache is not logging any resulting errors, and there doesn't seem to be a lo...
2013 Aug 08
4
HP R1500 G3 problems
..., >> >> OS: (L)ubuntu 12.04 precise LTS >> Nut: 2.6.3-1ubuntu1.1 >> Installation Method: Package (apt-get install nut) >> Hardware: HP R1500 G3 INT > > FYI: > I have a different UPS, a HP R3000 XR and I monitor it using serial and the bcmxcp driver. > > [R3000XR] > port = /dev/ttyUSB0 > driver = bcmxcp > > > > > _______________________________________________ > Nut-upsuser mailing list > Nut-upsuser at lists.alioth.debian.org > http://lists.alioth.debian.org/cgi-bin/mailman/listinfo/nut-upsuser Hi I am working on improvi...
2013 Aug 08
0
HP R1500 G3 problems
...12.04 precise LTS >>> Nut: 2.6.3-1ubuntu1.1 >>> Installation Method: Package (apt-get install nut) >>> Hardware: HP R1500 G3 INT >> >> FYI: >> I have a different UPS, a HP R3000 XR and I monitor it using serial and the bcmxcp driver. >> >> [R3000XR] >> port = /dev/ttyUSB0 >> driver = bcmxcp >> >> >> >> >> _______________________________________________ >> Nut-upsuser mailing list >> Nut-upsuser at lists.alioth.debian.org >> http://lists.alioth.debian.org/cgi-bin/mailman/listi...
2009 Dec 17
2
multiple usb apc smart ups with nut?
Hello everybody, I got tree UPS devices connected to a Debian server, and i am searching for a way to configure them. The server power-cord is only connected to one of the ups devices, and should monitor the other ups systems to sent email status. I got a HP R3000XR UPS with has a RS232 communication port that I have working perfectly. Then I have two APC SmartUPS 750V devices that are connected with USB, but I don't know how to setup the nut configuration to deal with both the devices. This is my dmesg output: Dec 14 19:36:39 sammy kernel: [ 2.22152...
2017 Apr 03
4
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On 03/04/17 17.24, Roger Price wrote: > On Mon, 3 Apr 2017, Jon Bendtsen wrote: > >> On 03/04/17 17.10, Roger Price wrote: >>> On Mon, 3 Apr 2017, Jon Bendtsen wrote: >>> >>>> Power seem to be lost immediately. >>>> But my APC Smart-UPS 1500 always reported everything OK. >>>> battery.charge : 100 >>> ...
2006 Aug 23
0
bcmxcp: get right firmware version
at least for an HP R3000XR with the 6-cereal card, the first CPU is said 6-port card, not the inverter. so get the firmware version from the last CPU, not the first. I wonder wether it makes more sense to store them all, aka ups.firmware.cpu0 etc. $OpenBSD$ --- drivers/bcmxcp.c.orig Wed Aug 23 11:16:01 2006 +++ drivers/b...
2013 Aug 07
4
HP R1500 G3 problems
Hi there, OS: (L)ubuntu 12.04 precise LTS Nut: 2.6.3-1ubuntu1.1 Installation Method: Package (apt-get install nut) Hardware: HP R1500 G3 INT Hardware-Specs: http://h18004.www1.hp.com/products/quickspecs/14059_div/14059_div.pdf Problem: I tried to set up nut with our new arrived HP R1500 G3 UPS but there is a failure with the usb connection. After trying "/lib/nut/usbhid-ups -DD -a
2010 Feb 18
2
HP R1500 G2 UPS
Hi, I have a HP R1500 G2 UPS and want to get it working under Debian Lenny - as this OS is not supported by HP I'm trying to use nut for it - but I can't get it working. Do I have any chance to get the UPS running with nut. I also tried different drivers but had no luck either. Or does anyone has experience with HP UPS under debian ? Any help would be nice ! I tried /lib/nut/usbhid-ups
2010 Sep 19
0
A logging/graphing UPS client using rrdtool and UPS::Nut
...y voltage and current, and output voltage and current. It uses rrdtool to generate three sets of graphs charting these parameters in a 24-hour high-resolution view and a 7-day medium-resolution view. This is a proof-of-concept tool, and is written specifically for the operating parameters of a HP R3000XR UPS, which is a transformerless DSP design using a line-voltage battery pack. You may find you need to modify some graph parameters if you have a transformer-based UPS using a low-voltage battery pack. You B<MUST> must specify the name of the UPS to monitor, and should set up an unprivilege...