2013 Jun 29
2
upsrw doesn't set variable
NUT 2.6.5 on FreeBSD 9.1
Why isn't the variable outlet.1.delay.shutdown set with the following
command?
# upsc PW5125 at localhost | grep "outlet.1.delay.shutdown"
outlet.1.delay.shutdown: -1
# upsrw -u au -p ap -s outlet.1.delay.shutdown PW5125 at localhost
Enter new value for outlet.1.delay.shutdown: 10
OK
# upsc PW5125 at localhost | grep "outlet.1.delay.shutdown"
outlet.1.delay.shutdown:...
2009 Jun 20
1
upsmon says ONBATT when status: TRIM
Hi,
I've been getting emails from upsmon saying:
Subject: UPS PW5125 at localhost notification: ONBATT
UPS PW5125 at localhost on battery
But then the machines on the UPS stay on for hours; we haven't got
that kind of runtime, more like 10-20 minutes.
After a few occurrences, it now happened at a time where I could log
in to see in real time what is happenin...
2013 Jun 29
0
upsrw doesn't set variable
On 6/29/2013 at 9:14 AM Mike. wrote:
|NUT 2.6.5 on FreeBSD 9.1
|
|
|Why isn't the variable outlet.1.delay.shutdown set with the following
|command?
|
|
|
|# upsc PW5125 at localhost | grep "outlet.1.delay.shutdown"
|outlet.1.delay.shutdown: -1
|
|# upsrw -u au -p ap -s outlet.1.delay.shutdown PW5125 at localhost
|Enter new value for outlet.1.delay.shutdown: 10
|OK
|
|# upsc PW5125 at localhost | grep "outlet.1.delay.shutdown"
|outlet.1.delay.sh...
2013 Jun 29
3
upsrw doesn't set variable
On Jun 29, 2013, at 9:45 AM, Mike. wrote:
> On 6/29/2013 at 9:14 AM Mike. wrote:
>
> |NUT 2.6.5 on FreeBSD 9.1
> |
> |
> |Why isn't the variable outlet.1.delay.shutdown set with the following
> |command?
> |
> |
> |
> |# upsc PW5125 at localhost | grep "outlet.1.delay.shutdown"
> |outlet.1.delay.shutdown: -1
> |
> |# upsrw -u au -p ap -s outlet.1.delay.shutdown PW5125 at localhost
> |Enter new value for outlet.1.delay.shutdown: 10
> |OK
> |
> |# upsc PW5125 at localhost | grep "outlet.1.dela...
2017 Feb 20
2
[HCL] Powerware PW5125 with driver bcmxcp
This UPS is already listed in the compatibility list. But I wanted to
add the instant commands supported by upscmd:
============================
Instant commands supported on UPS [PW5125]:
beeper.disable - Disable the UPS beeper
beeper.enable - Enable the UPS beeper
beeper.mute - Temporarily mute the UPS beeper
load.on - Turn on the load immediately
outlet.1.load.off - Turn off the load on outlet 1 immediately
outlet.1.load.on - Turn on the load on outlet 1 immediately
outlet.1.sh...
2017 Feb 21
1
[HCL] Powerware PW5125 with driver bcmxcp
...upscmd output here:
>
> http://networkupstools.org/stable-hcl.html#footnotes
>
> Let us know if there is another place we should update.
>
> To get an idea of the age of the unit, is this a pre-merger Powerware, or is it also labeled Eaton?
>
> Given the age of the other PW5125 entries, can you please send upsc (and upsrw) output as well? Feel free to mask portions of the serial number, but at least for other vendors, the first few characters can be useful for identifying differences in the underlying implementation. Hopefully the ups.firmware value is sufficient.
>
&...
2017 Feb 21
0
[HCL] Powerware PW5125 with driver bcmxcp
...reed, and we do ask for upsc, upsrw and upscmd output here:
http://networkupstools.org/stable-hcl.html#footnotes
Let us know if there is another place we should update.
To get an idea of the age of the unit, is this a pre-merger Powerware, or is it also labeled Eaton?
Given the age of the other PW5125 entries, can you please send upsc (and upsrw) output as well? Feel free to mask portions of the serial number, but at least for other vendors, the first few characters can be useful for identifying differences in the underlying implementation. Hopefully the ups.firmware value is sufficient.
Thanks...
2008 Dec 21
1
upsd segfault.
Hi all,
Have a strange behaviour that I don't know how to debug.
This is when I use the Eaton PW5125 ups. I have it connected
And running in standby.
Starting up the drivers (pw3105 and pw5125) and they run.
Start up the upsd and can read info from both of them. The 3105 is
supplying the computer and the 5125 have a dummy load.
The 5125 is showing that it is off line. Now when I hit the on line...
2013 Jun 29
0
upsrw doesn't set variable
...harles Lepple wrote:
|On Jun 29, 2013, at 9:45 AM, Mike. wrote:
|
|> On 6/29/2013 at 9:14 AM Mike. wrote:
|>
|> |NUT 2.6.5 on FreeBSD 9.1
|> |
|> |
|> |Why isn't the variable outlet.1.delay.shutdown set with the
following
|> |command?
|> |
|> |
|> |
|> |# upsc PW5125 at localhost | grep "outlet.1.delay.shutdown"
|> |outlet.1.delay.shutdown: -1
|> |
|> |# upsrw -u au -p ap -s outlet.1.delay.shutdown PW5125 at localhost
|> |Enter new value for outlet.1.delay.shutdown: 10
|> |OK
|> |
|> |# upsc PW5125 at localhost | grep "outlet...
2013 Jun 29
1
upsrw doesn't set variable
...utlets: 2
>
> 16.658358 Number of bytes: 6
>
> 16.658369 Outlet number: 1
>
8<---------------snip------------
The problem is that I had a crash on my backup ;-( so I lost the
paper on the specific commands for 5125.
So if someone have the command specifications on pw5125, can you check
if this is the case for the 5125 that it is impossible to set auto off delay.
Regards
Kjell Claesson
Co author of the bcmxcp driver.
2013 Jun 29
2
upsrw doesn't set variable
...i Mike,
>
> Thanks for the quick reply.
>
> I checked the log file (which, admittedly, I should have done before I
> posted about the problem :) ).
>
> Here's the command and the corresponding log message:
>
> # upsrw -u au -p ap -s outlet.1.delay.shutdown=12 PW5125 at localhost
> OK
>
> bcmxcp[90004]: Set [outlet.1.delay.shutdown 12] failed due to invalid
> parameter
>
Yep the ups is telling that the command has an invalid parameter.
Have to check if there is any difference between the 5125 and others.
>
> Curious that the comman...
2013 Feb 21
1
NUT with Powerware 5125.
Hi,
Does anyone know how to make NUT works with Powerware 5125?
I already tried serial communication (genericups and bcmxcp) and USB
(usbhid-ups and bcmxcp_usb), but without success.
I'm using the latest version of NUT (2.6.5) under Debian amd64.
Can anyone help me?
Thanks.
Daniel
-------------- next part --------------
An HTML attachment was scrubbed...
URL:
2007 Apr 06
3
questions re. patching bcmxcp.c and choosing variable names
I've patched bcmxcp.c such that it can power cycle the outlet load
segments independently on a Powerware PW5125 UPS. I presume that it will
work for any XCP protocol UPS with 2 load segments.
Should these instant commands be called
outlet.1.shutdown.return
outlet.2.shutdown.return
?
Where do the descriptions displayed by upscmd -l come from? Presently it
shows
outlet.1.shutdown.return - Unavailable
out...
2007 Sep 19
1
Programming problem.
...PS_TOP_DATA_REQ
8a <-- PW_LOAD_OFF_RESTART
8b <-- PW_UPS_OFF
a0 <-- PW_SET_REQ_ONLY_MODE
cf <-- Autorisation command
So this ups does not need to list unused functions like: batt_test sys_test
set_config set_outlet e.t.c when you ask for possible commands.
But if you connect a PW5125 it have all the commands listed in
bcmxcp.h.
It should be some more listed in the bcmxcp.h, like
0x32 (event history block).
My plan was to use a struct and load it with the commands. Then
loop it and set a bool in the struct if it is present or not.
That could be done, but..........?
Then it is...
2013 Jun 29
0
upsrw doesn't set variable
...|>
|> Thanks for the quick reply.
|>
|> I checked the log file (which, admittedly, I should have done before
I
|> posted about the problem :) ).
|>
|> Here's the command and the corresponding log message:
|>
|> # upsrw -u au -p ap -s outlet.1.delay.shutdown=12
PW5125 at localhost
|> OK
|>
|> bcmxcp[90004]: Set [outlet.1.delay.shutdown 12] failed due to
invalid
|> parameter
|>
|Yep the ups is telling that the command has an invalid parameter.
|Have to check if there is any difference between the 5125 and others.
|>
|> Curious that t...
2009 Aug 27
2
Serial comm errors with bcmxcp on HP R3000 XR
I have setup nut-2.4.1 with the bcmxcp driver for my HP R3000 XR unit
and although it appears to work, I receive the following sorts of errors
in syslog:
Aug 27 10:33:05 sv18 bcmxcp[6373]: Communications with UPS lost: Receive
error (data): got 0 bytes instead of 64!!!
Aug 27 10:33:15 sv18 bcmxcp[6373]: Communications with UPS lost: Receive
error (data): got 0 bytes instead of 64!!!
Aug 27
2007 Nov 30
0
which driver for Powerware 5125
Hello,
I have a Powerware 5125 UPS and I don't know which driver I should use.
In the compatibility list for the stable branch I see 2 sections for
this model:
5119, 5125 - genericups upstype=15
PW5125 - bcmxcp
Why are there 2 and which should I use?
Thank you.
2007 Jul 10
1
[nut-commits] svn commit r1019 - in trunk: . drivers
.....
2007/7/9, Kjell Claesson <keyson-guest at alioth.debian.org>:
> Author: keyson-guest
> Date: Mon Jul 9 19:48:51 2007
> New Revision: 1019
>
> Log:
> Patch from Oliver Wilcock - bcmxcp.c modified to control individual load segments (outlet.2.shutdown.return) on Powerware PW5125.
>
> Modified:
> trunk/ChangeLog
> trunk/drivers/bcmxcp.c
> ...
thanks,
Arnaud
--
Free Software Developer - http://arnaud.quette.free.fr/
Debian Developer - http://people.debian.org/~aquette/
Network UPS Tools (NUT) Project Leader - http://www.networkupstools.org/
Ubuntu Medi...
2013 Jun 28
2
How to Simulate UPS on battery?
...ssched/upssched.lock
AT LOWBATT * START-TIMER lowbattwarn 1
AT ONBATT * START-TIMER onbattwarn 10
AT ONLINE * CANCEL-TIMER onbattwarn
And here is the upsmon.conf on S2:
$ cat /usr/local/etc/nut/upssched.conf
RUN_AS_USER _ups
MONITOR PW5125 at s1.EXAMPLE.COM 1 monuser tHEuNSPOKENpSWD slave
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -r now"
NOTIFYCMD /usr/local/sbin/upssched
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/killpower
NOTIFY...
2009 Jul 13
4
Accurate battery reports? (HP R3000 XR)
Hi
I have a HP R3000 XR UPS which NUT never says is at 100% battery.
It seems stuck in 98 or 99 . something percentage.
How accurate should i expect the reports to be? All my other UPSes has
been and is at 100%, even those i have retired.
My monitor system runs debian. The host that is physically connected
to this ups runs:
nut 2.2.2-6.4
The web script runs
nut-cgi 2.0.4-4
JonB