Displaying 11 results from an estimated 11 matches for "pcmup".
Did you mean:
pcmu
2017 May 17
2
Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
...r no load, since despite
being in state OB
DISCHRG the battery.charge is still 100. It's best to perform such tests
with a dummy load
such as a table lamp and an old fashioned incandescent 100 watt bulb.
==> Yes. I got it and try to ascend load as below results
dinow-All-Series:~# upsc pcmups
Init SSL without certificate database
battery.charge: 32
battery.charge.low: 10
battery.charge.warning: 30
battery.date: 2010/12/20
battery.runtime: 256
battery.type: PbAc
device.mfr: POWERCOM Co.,LTD
device.model: HID UPS Battery
device.serial: 004-0D9F-000
device.type: ups
driver.name: usbhid-up...
2017 May 16
2
Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
...s.
==> I got it. I tried to command "upsdrvctl shutdown" on both line-mode and
battery-mode
==> But ups do not disconnect its outlets power
-----------------------------------------------------------------------------------
BB. Could you show us the output of command "upsc pcmups"?
==> Yes. Below 2 mode were the outputs of command "upsc pcmups"
B1. Battery Mode
dinow-All-Series:/etc/nut$ upsc pcmups
Init SSL without certificate database
battery.charge: 100
battery.charge.low: 10
battery.charge.warning: 30
battery.date: 2010/12/20
battery.runtime: 784
ba...
2017 May 17
1
Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
...r no load, since despite
being in state OB
DISCHRG the battery.charge is still 100. It's best to perform such tests
with a dummy load
such as a table lamp and an old fashioned incandescent 100 watt bulb.
==> Yes. I got it and try to ascend load as below results
dinow-All-Series:~# upsc pcmups
Init SSL without certificate database
battery.charge: 32
battery.charge.low: 10
battery.charge.warning: 30
battery.date: 2010/12/20
battery.runtime: 256
battery.type: PbAc
device.mfr: POWERCOM Co.,LTD
device.model: HID UPS Battery
device.serial: 004-0D9F-000
device.type: ups
driver.name: usbhid-up...
2017 May 15
1
Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
...1)
> ??? USB communication driver 0.32
> ??? Using subdriver : PowerCOM HID 0.4
> ??? Initiating UPS shutdown
Hi, Normally one would expect the UPS to disconnect it's power outlets
after the default ups.delay.shutdown = 20 seconds. Could you show us the
output of command "upsc pcmups"?
> CC. Do you have a script in a systemd system-shutdown directory which calls
> "upsdrvctl shutdown" ?
>
> ==> No
Once the command "upsdrvctl shutdown" works, you will need to incorporate
it in your shutdown process. NUT 2.7.4 includes file
.../scrip...
2017 May 11
2
Good Day NUT
Good Day nut
Many thanks for your reading
==> AA. I confront an issue that can't shutdown the ups
With the nut, I can get the ups status(upsc) and shutdown the linux-ubuntu when power failure occurs(upsmon)
But don't know which configuration I ignore to setup for ups shutdown
==> BB. I want to check that with the command "upsdrvctl shutdown" and
2007 Jan 18
1
Nut with Powercom iCute ICT-530U (USB)
Hi!
Is there any user of nut having this type of UPS? (
http://www.pcmups.com.tw/product/iCute.html)
It works nice under windows and also is detected under Linux and installed
as USB HID device. There is problem however, as the software provided by its
manufacturer (http://www.pcmups.com.tw/download/Download/UPSMON_USBV091.zip)
doesn't seem to comunicate with the UP...
2017 May 16
0
Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
On Tue, 16 May 2017, Dinow Hsieh wrote:
> BB. Could you show us the output of command "upsc pcmups"?
>
> ==> Yes. Below 2 mode were the outputs of command "upsc pcmups"
>
> battery.charge: 100
> battery.charge.low: 10
> battery.charge.warning: 30
> battery.date: 2010/12/20
...
> ups.date: 2010/12/20
> ups.load: 4
...
> ups.status: OB DISCHRG
Is...
2017 May 17
0
[Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
On May 17, 2017, at 4:53 AM, Dinow Hsieh <dinow at upspowercom.com.tw> wrote:
>
> ==> I tried below set-command but it react fail
>
> dinow-All-Series:~# upsrw -s "ups.delay.shutdown"="30" -u pcmups pcmups at localhost
> Password:
> Unexpected response from upsd: ERR ACCESS-DENIED
>
This error is not from the driver. Be sure to specify a NUT user and password that is allowed to send instcmds:
http://networkupstools.org/docs/man/upsd.users.html
If you need to modify upsd.users,...
2007 Jul 20
1
PowerCOM UPS management protocol specification
Hello All.
I have PowerCOM ( http://pcmups.com.tw/ ) UPS management protocol
specification at http://www.sovico.org/pcm.txt
Current version of NUT contains any drivers include driver for
Powercom, but not fully funcionality.
This specification describe protocol for next series UPS:
BLACK KNIGHT: All UPS AP series
WARRIOR: WAR-1000AP
WOW...
2013 Jun 05
2
several problems with Powercom BNT-500AP
...t;
uname -a
Linux raspberrypi 3.6.11+ #393 PREEMPT Fri Mar 8 16:36:28 GMT 2013 armv6l
GNU/Linux
exact NUT version
pi at raspberrypi ~ $ dpkg -s nut
Package: nut
...
Version: 2.6.4-2.3
NUT installation method: package
exact device name and related information:
BNT-500AP
http://pcmups.com.tw/eA/html/product/show.php?num=229
<http://pcmups.com.tw/eA/html/product/show.php?num=229&root=13&kind=113&page
=1&keyword> &root=13&kind=113&page=1&keyword=
I have several problems with my UPS:
1. Wrong battery and UPS date reported.
According to s...
2010 Mar 24
2
Powercom RS232 driver improvement/rewrite
...some leds of my units are
only available in the 650VA version, but mine looks like a 500VA. The
manual refered to some "UPSMON" software, which I tracked to Powercom,
just to find out that the KIN or BNT [456]25AP also have the same
chasis design as my unit, but according to this
(http://pcmups.com.tw/download/Download/PCM-King325A-625AP.pdf), mi
ups is nearer the KIN (due to the drawing of the european power
connector). The manuals also match, but not the serial port "details".
As NUT supports both the SOLA and Powercom, I tested both drivers to
finally find that the UPS answe...