search for: pcmup

Displaying 11 results from an estimated 11 matches for "pcmup".

Did you mean: pcmu
2017 May 17
2
Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
...r no load, since despite being in state OB DISCHRG the battery.charge is still 100. It's best to perform such tests with a dummy load such as a table lamp and an old fashioned incandescent 100 watt bulb. ==> Yes. I got it and try to ascend load as below results dinow-All-Series:~# upsc pcmups Init SSL without certificate database battery.charge: 32 battery.charge.low: 10 battery.charge.warning: 30 battery.date: 2010/12/20 battery.runtime: 256 battery.type: PbAc device.mfr: POWERCOM Co.,LTD device.model: HID UPS Battery device.serial: 004-0D9F-000 device.type: ups driver.name: usbhid-up...
2017 May 16
2
Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
...s. ==> I got it. I tried to command "upsdrvctl shutdown" on both line-mode and battery-mode ==> But ups do not disconnect its outlets power ----------------------------------------------------------------------------------- BB. Could you show us the output of command "upsc pcmups"? ==> Yes. Below 2 mode were the outputs of command "upsc pcmups" B1. Battery Mode dinow-All-Series:/etc/nut$ upsc pcmups Init SSL without certificate database battery.charge: 100 battery.charge.low: 10 battery.charge.warning: 30 battery.date: 2010/12/20 battery.runtime: 784 ba...
2017 May 17
1
Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
...r no load, since despite being in state OB DISCHRG the battery.charge is still 100. It's best to perform such tests with a dummy load such as a table lamp and an old fashioned incandescent 100 watt bulb. ==> Yes. I got it and try to ascend load as below results dinow-All-Series:~# upsc pcmups Init SSL without certificate database battery.charge: 32 battery.charge.low: 10 battery.charge.warning: 30 battery.date: 2010/12/20 battery.runtime: 256 battery.type: PbAc device.mfr: POWERCOM Co.,LTD device.model: HID UPS Battery device.serial: 004-0D9F-000 device.type: ups driver.name: usbhid-up...
2017 May 15
1
Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
...1) > ??? USB communication driver 0.32 > ??? Using subdriver : PowerCOM HID 0.4 > ??? Initiating UPS shutdown Hi, Normally one would expect the UPS to disconnect it's power outlets after the default ups.delay.shutdown = 20 seconds. Could you show us the output of command "upsc pcmups"? > CC. Do you have a script in a systemd system-shutdown directory which calls > "upsdrvctl shutdown" ? > > ==> No Once the command "upsdrvctl shutdown" works, you will need to incorporate it in your shutdown process. NUT 2.7.4 includes file .../scrip...
2017 May 11
2
Good Day NUT
Good Day nut Many thanks for your reading ==> AA. I confront an issue that can't shutdown the ups With the nut, I can get the ups status(upsc) and shutdown the linux-ubuntu when power failure occurs(upsmon) But don't know which configuration I ignore to setup for ups shutdown ==> BB. I want to check that with the command "upsdrvctl shutdown" and
2007 Jan 18
1
Nut with Powercom iCute ICT-530U (USB)
Hi! Is there any user of nut having this type of UPS? ( http://www.pcmups.com.tw/product/iCute.html) It works nice under windows and also is detected under Linux and installed as USB HID device. There is problem however, as the software provided by its manufacturer (http://www.pcmups.com.tw/download/Download/UPSMON_USBV091.zip) doesn't seem to comunicate with the UP...
2017 May 16
0
Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
On Tue, 16 May 2017, Dinow Hsieh wrote: > BB. Could you show us the output of command "upsc pcmups"? > > ==> Yes. Below 2 mode were the outputs of command "upsc pcmups" > > battery.charge: 100 > battery.charge.low: 10 > battery.charge.warning: 30 > battery.date: 2010/12/20 ... > ups.date: 2010/12/20 > ups.load: 4 ... > ups.status: OB DISCHRG Is...
2017 May 17
0
[Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
On May 17, 2017, at 4:53 AM, Dinow Hsieh <dinow at upspowercom.com.tw> wrote: > > ==> I tried below set-command but it react fail > > dinow-All-Series:~# upsrw -s "ups.delay.shutdown"="30" -u pcmups pcmups at localhost > Password: > Unexpected response from upsd: ERR ACCESS-DENIED > This error is not from the driver. Be sure to specify a NUT user and password that is allowed to send instcmds: http://networkupstools.org/docs/man/upsd.users.html If you need to modify upsd.users,...
2007 Jul 20
1
PowerCOM UPS management protocol specification
Hello All. I have PowerCOM ( http://pcmups.com.tw/ ) UPS management protocol specification at http://www.sovico.org/pcm.txt Current version of NUT contains any drivers include driver for Powercom, but not fully funcionality. This specification describe protocol for next series UPS: BLACK KNIGHT: All UPS AP series WARRIOR: WAR-1000AP WOW...
2013 Jun 05
2
several problems with Powercom BNT-500AP
...t; uname -a Linux raspberrypi 3.6.11+ #393 PREEMPT Fri Mar 8 16:36:28 GMT 2013 armv6l GNU/Linux exact NUT version pi at raspberrypi ~ $ dpkg -s nut Package: nut ... Version: 2.6.4-2.3 NUT installation method: package exact device name and related information: BNT-500AP http://pcmups.com.tw/eA/html/product/show.php?num=229 <http://pcmups.com.tw/eA/html/product/show.php?num=229&root=13&kind=113&page =1&keyword> &root=13&kind=113&page=1&keyword= I have several problems with my UPS: 1. Wrong battery and UPS date reported. According to s...
2010 Mar 24
2
Powercom RS232 driver improvement/rewrite
...some leds of my units are only available in the 650VA version, but mine looks like a 500VA. The manual refered to some "UPSMON" software, which I tracked to Powercom, just to find out that the KIN or BNT [456]25AP also have the same chasis design as my unit, but according to this (http://pcmups.com.tw/download/Download/PCM-King325A-625AP.pdf), mi ups is nearer the KIN (due to the drawing of the european power connector). The manuals also match, but not the serial port "details". As NUT supports both the SOLA and Powercom, I tested both drivers to finally find that the UPS answe...