Displaying 20 results from an estimated 225 matches for "pbac".
Did you mean:
pac
2005 Oct 26
0
A minor nit to pick
Ladies and Gentlemen,
Running newhidups with -DD shows the following line that starts with
"-> String:" occasionally, with no contect that it is related to:
......
Can't find object UPS.Battery.Temperature
-> String: PbAc (len = 4/4)
Can't find object UPS.Output.PercentLoad
......
However, running newhidups with -DDD, shows the proper context:
......
hu_find_infoval: searching for value = 4
-> String: PbAc (len = 4/4)
hu_find_infoval: found PbAc (value: 4)
......
since the upsdebugx() statements there are a...
2016 May 14
2
Low Battery event not occurring
>
> battery.charge: 3
> battery.charge.low: 10
> battery.charge.warning: 30
> battery.runtime: 93
> battery.temperature: 32.9
> battery.type: PbAC
> battery.voltage: 46.4
> battery.voltage.nominal: 48.0
Is it possible that battery.charge is really 30% rather than 3%?
The 3016 protocol models have issues with scaling on some of the voltages and frequencies. You can see this by killing the driver, and restarting it with '-DDD'....
2017 Jun 05
2
Fwd: Emerson Liebert GXT4
...the driver and upsd, what does "upsc ups" return? If you can also include "upsrw ups" and "upscmd -l ups" output, we can update the DDL.
#upsc ups
Init SSL without certificate database
battery.charge: 100
battery.charge.low: 20
battery.charge.warning: 0
battery.type: PbAc
battery.voltage: 1.0
battery.voltage.nominal: 0.0
device.mfr: Emerson Network Power
device.model: Liebert GXT4
device.serial: 1607000058AFC23
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.producti...
2006 Dec 08
2
F6C1500-TW-RK
...r usb.
i was able to get hidups to work using the below settings, but it
provides limited information.
my ups.conf entry:
[belkin]
driver = hidups
port = /dev/usb/hiddev0
and the output of upsc:
gateway:/etc/nut# upsc belkin@localhost
battery.charge: 100
battery.chemistry: PbAc
battery.runtime: 120
battery.voltage: 12.5
driver.name: hidups
driver.parameter.port: /dev/usb/hiddev0
driver.version: 2.0.1
ups.mfr: Unknown
ups.model: Belkin UPS
ups.serial:
ups.status: OL
thanks!
Jamie Fiedler
IT Manager
Tippingpoint Labs
83 Chapel St
Newton, MA 02458
T 617.332.8261
F 617...
2020 Apr 23
3
Low battery unexpected shutdown
...root cause.
First, let me focus on my scenario and current setup:
In normal status (ONLINE, fully charged) my UPS runtime is about 20minutes,
this is some of the relevant info:
Charge 100%
Charge Low 20%
Runtime 20m37s
Type PbAc
Manufacturer EATON
Model Ellipse
ECO 1200
Serial 000000000
Power 25VA
Frequency Nominal 50Hz
Voltage 230.0V
Voltage Nominal 230V
Delay Shutdown 25s
Delay Star...
2020 Sep 22
4
UPS Losing Connection
Installed a new Tripplite Smart1500LCD on a CentOS 7 host using the usb
connector. Nut does connect:
$upsc ups
battery.charge: 100
battery.runtime: 1407
battery.type: PbAC
...
But after a half hour or so the connection is lost. Restarting nut
re-establishes the connection.
Any idea what might be causing the dissconnection?
2016 May 16
1
Low Battery event not occurring
...nge, and it still won't incite a poweroff:
==========================================================================
[root at localhost ~]# upsc myups at localhost
battery.charge: 76
battery.charge.low: 90
battery.charge.warning: 30
battery.runtime: 1811
battery.temperature: 31.9
battery.type: PbAC
battery.voltage: 49.2
battery.voltage.nominal: 48.0
device.mfr: Tripp Lite
device.model: TRIPP LITE SMART2200RM2UN
device.serial: 2608CY0SM8##########
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.version:...
2012 Sep 19
2
Unable to disable beeper on Powercom Imperial IMP-525AP
...{NUT_USER} -p {NUT_PASSWORD} powercom beeper.toggle
returns *OK*, however, ups.beeper.status=enabled
Thank you,
Sergey
==========
Additional info:
1)
$ upsc powercom
battery.charge: 100
battery.charge.low: 10
battery.charge.warning: 30
battery.date: 2010/01/01
battery.runtime: 2432
battery.type: PbAc
device.mfr: POWERCOM Co.,LTD
device.model: UPS IMP--525AP FW3.A2
device.serial: 3A2-0000-0001
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.version: 2.6.5
driver.version.data: PowerCOM HID 0.3
driver.ver...
2010 Apr 15
2
Patch for HP T1000 INTL
I got HP T1000 INTL UPS to work with NUT. Looks like it is more or
less equal to HP T750 INTL. I have only tested USB, not serial.
2013 Sep 10
1
[HCL] Eaton 5S1500LCD supported by usbhid-ups
Device Manufacturer: Eaton
Device Name: 5S1500LCD
----------------------------------------------------------
upsc output:
battery.charge: 100
battery.charge.low: 20
battery.runtime: 3515
battery.type: PbAc
device.mfr: EATON
device.model: Ellipse PRO 1500
device.serial: 0000000000
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.vendorid: 0463
driver.version: 2.6.4
driver.version.data: MGE HID 1.31
dri...
2013 Sep 10
1
[HCL] Eaton 5S1500LCD supported by usbhid-ups
Device Manufacturer: Eaton
Device Name: 5S1500LCD
----------------------------------------------------------
upsc output:
battery.charge: 100
battery.charge.low: 20
battery.runtime: 3515
battery.type: PbAc
device.mfr: EATON
device.model: Ellipse PRO 1500
device.serial: 0000000000
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.vendorid: 0463
driver.version: 2.6.4
driver.version.data: MGE HID 1.31
dri...
2016 May 16
0
Low Battery event not occurring
...re is what it currently looks like after charging over the weekend:
====================================================
[root at localhost ~]# upsc myups at localhost
battery.charge: 100
battery.charge.low: 10
battery.charge.warning: 30
battery.runtime: 2273
battery.temperature: 33.9
battery.type: PbAC
battery.voltage: 54.6
battery.voltage.nominal: 48.0
device.mfr: Tripp Lite
device.model: TRIPP LITE SMART2200RM2UN
device.serial: 2608CY0SM8###########
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.version:...
2007 May 31
2
RE hp r/t2200 and NUT
Hello Linas,
> Just wanted to inform You (for the compatibility list), that HP R/T2200
works perfectly with the hidups driver. Thank You very much for NUT! :)
>
> # upsc hp at localhost
> battery.charge: 100
> battery.chemistry: PbAC
> battery.voltage: 22.7
> driver.name: hidups
> driver.parameter.port: /dev/usb/hiddev0
> driver.version: 2.0.5
> ups.delay.shutdown: -1
> ups.delay.start: -1
> ups.load: 18
> ups.mfr: Hewlett Packard
> ups.model: R/T2200 INTL
> ups.status: OL
Thanks for this feedba...
2008 Jul 24
2
Tripplite Smart1500SLT configuration?
...ocal/ups/bin/upsc tripplite at localhost ups.status
OL
I'm starting to think this is looking good. Now for some details:
root at golum:# /usr/local/ups/bin/upsc tripplite at localhost
battery.charge: 100
battery.charge.low: 10
battery.charge.warning: 30
battery.temperature: 24.9
battery.type: PbAC
battery.voltage: 40.7
battery.voltage.nominal: 36.0
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.vendorid: 09ae
driver.version: 2.3.0-1515
driver.version.data: TrippLite HID 0.2 (experimental)
driver.version.inte...
2009 Nov 10
1
[PATCH] Add support for Liebert PowerSure PSA to liebert-hid.c
...s patch adds support for the following ups to liebert-hid.c:
$ lsusb | grep Liebert
Bus 007 Device 005: ID 10af:0001 Liebert Corp. PowerSure PSA UPS
Using this patch, I'm able to obtain information about the ups via
upsc:
$ upsc upsname
battery.charge: 100
battery.runtime: 1012
battery.type: PbAc
battery.voltage: 1172
battery.voltage.nominal: 12
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.version: 2.4.1
driver.version.data: Liebert HID 0.3
driver.version.internal: 0.34
ups.mfr: Liebert
ups.model: Liebert PSA 650 F...
2020 Apr 23
0
Low battery unexpected shutdown
...scenario and current setup:
>
> In normal status (ONLINE, fully charged) my UPS runtime is about
> 20minutes, this is some of the relevant info:
>
> Charge 100%
> Charge Low 20%
> Runtime 20m37s
> Type PbAc
> Manufacturer EATON
> Model Ellipse
> ECO 1200
> Serial 000000000
> Power 25VA
> Frequency Nominal 50Hz
> Voltage 230.0V
> Voltage Nominal 230V...
2014 Jun 05
2
Question about voltage threshold setting in NUT
...srw -s default.input.transfer.low=70 -u * -p * ups
Unexpected response from upsd: ERR VAR-NOT-SUPPORTED
$ sudo upsrw -s overwrite.input.transfer.low=70 -u * -p * ups
Unexpected response from upsd: ERR VAR-NOT-SUPPORTED
battery.charge: 100
battery.charge.low: 20
battery.runtime: 1087
battery.type: PbAc
device.mfr: EATON
device.model: Eaton 3S 550
device.serial: 000000000
device.type: ups
driver.name: usbhid-ups
driver.parameter.offdelay: 90
driver.parameter.ondelay: 120
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.vendorid: 0463
drive...
2017 Jun 13
2
Unable to use nut-2.7.4 with Eaton 5E1500I USB
...1.0
Don't hesitate if you need more guidance for trying this branch.
FYI, I've just made a test with the same unit, on a Debian jessie (kernel
3.16.43-2, libusb 0.1.12-25) both with 2.7.4 and the latest git master, and
it works fine:
battery.charge: 62
battery.runtime: 2725
battery.type: PbAc
device.mfr: EATON
device.model: 5E 1500i
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.synchronous: no
driver.version: 2.7.4.1
driver.version.data: MGE HID 1.42
driver.version.internal: 0.42
input...
2013 Aug 23
1
HP R1500 G3 UPS does not accept battery.charge.low value via upsrw
...e.low value
i set via upsrw.
Is this a common problem with this model in nut 2.6.4?
Any ideas how to force the UPS to accept this value?
Regards
Jan
% upsc hp1500
battery.charge: 100
battery.charge.low: 20
battery.charge.warning: 20
battery.runtime: 23917
battery.temperature: 49.0
battery.type: PbAc
battery.voltage: 39.0
battery.voltage.nominal: 36.0
device.mfr: Hewlett-Packard
device.model: HP R1500 G3 UPS
device.part: AF471A
device.serial: XXXXXXXXXX
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.vers...
2017 Apr 12
4
HP R1500 G2 USB on Ubuntu
...tc/udev/rules.d/
udevadm control --reload-rules
udevadm trigger
reboot server to be sure everything is OK
Nicolas
upsc HPR1500
Init SSL without certificate database
battery.charge: 100
battery.charge.low: 20
battery.charge.warning: 20
battery.runtime: 24171
battery.temperature: 46.0
battery.type: PbAc
battery.voltage: 41.0
battery.voltage.nominal: 36.0
device.mfr: Hewlett-Packard
device.model: HP R1500 G2 UPS
device.part: 416830-002
device.serial: 3Cxxxxxxxx (not usefull)
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port...