Jan Phillip Greimann
2013-Aug-23 13:50 UTC
[Nut-upsuser] HP R1500 G3 UPS does not accept battery.charge.low value via upsrw
Hi there, my HP R1500 G3 UPS doesn't apply my battery.charge.low value i set via upsrw. Is this a common problem with this model in nut 2.6.4? Any ideas how to force the UPS to accept this value? Regards Jan % upsc hp1500 battery.charge: 100 battery.charge.low: 20 battery.charge.warning: 20 battery.runtime: 23917 battery.temperature: 49.0 battery.type: PbAc battery.voltage: 39.0 battery.voltage.nominal: 36.0 device.mfr: Hewlett-Packard device.model: HP R1500 G3 UPS device.part: AF471A device.serial: XXXXXXXXXX device.type: ups driver.name: usbhid-ups driver.parameter.pollfreq: 30 driver.parameter.pollinterval: 2 driver.parameter.port: auto driver.version: 2.6.4 driver.version.data: TrippLite HID 0.8 driver.version.internal: 0.37 input.frequency: 50.0 input.transfer.high: 266.0 input.transfer.low: 194.0 input.voltage: 232.0 input.voltage.nominal: 230 output.current: 0.00 output.frequency: 50.0 output.frequency.nominal: 50 output.voltage: 231.0 output.voltage.nominal: 230 ups.beeper.status: enabled ups.delay.shutdown: 20 ups.delay.start: 30 ups.firmware: 264 ups.load: 0 ups.load.nominal: 80 ups.mfr: Hewlett-Packard ups.model: HP R1500 G3 UPS ups.power: 0.0 ups.power.nominal: 1500 ups.productid: 1fe0 ups.serial: XXXXXXXXXX ups.status: OL CHRG ups.test.result: No test initiated ups.timer.reboot: -1 ups.timer.shutdown: -1 ups.timer.start: -1 ups.vendorid: 03f0 % upsc hp1500 server.version 2.6.4 % upsrw hp1500 [battery.charge.low] Remaining battery level when UPS switches to LB (percent) Type: STRING Value: 20 [input.transfer.high] High voltage transfer point (V) Type: STRING Value: 266.0 [input.transfer.low] Low voltage transfer point (V) Type: STRING Value: 194.0 [ups.delay.shutdown] Interval to wait after shutdown with delay command (seconds) Type: STRING Value: 20 [ups.delay.start] Interval to wait before (re)starting the load (seconds) Type: STRING Value: 30 % upsrw -s battery.charge.low=30 hp1500 Username (root): admin Password: OK % upsrw hp1500 [battery.charge.low] Remaining battery level when UPS switches to LB (percent) Type: STRING Value: 20 [...]
Jan Phillip Greimann
2013-Aug-23 14:36 UTC
[Nut-upsuser] HP R1500 G3 UPS does not accept battery.charge.low value via upsrw
Some more information: The variables ups.delay.shutdown and ups.delay.start do change when set via upsrw. The values of the variables battery.charge.low, input.transfer.high and input.transfer.low do not change with upsrw. Regards, Jan Am 23.08.2013 15:50, schrieb Jan Phillip Greimann:> Hi there, > > my HP R1500 G3 UPS doesn't apply my battery.charge.low value > i set via upsrw. > > Is this a common problem with this model in nut 2.6.4? > > Any ideas how to force the UPS to accept this value? > > Regards > Jan > > % upsc hp1500 > battery.charge: 100 > battery.charge.low: 20 > battery.charge.warning: 20 > battery.runtime: 23917 > battery.temperature: 49.0 > battery.type: PbAc > battery.voltage: 39.0 > battery.voltage.nominal: 36.0 > device.mfr: Hewlett-Packard > device.model: HP R1500 G3 UPS > device.part: AF471A > device.serial: XXXXXXXXXX > device.type: ups > driver.name: usbhid-ups > driver.parameter.pollfreq: 30 > driver.parameter.pollinterval: 2 > driver.parameter.port: auto > driver.version: 2.6.4 > driver.version.data: TrippLite HID 0.8 > driver.version.internal: 0.37 > input.frequency: 50.0 > input.transfer.high: 266.0 > input.transfer.low: 194.0 > input.voltage: 232.0 > input.voltage.nominal: 230 > output.current: 0.00 > output.frequency: 50.0 > output.frequency.nominal: 50 > output.voltage: 231.0 > output.voltage.nominal: 230 > ups.beeper.status: enabled > ups.delay.shutdown: 20 > ups.delay.start: 30 > ups.firmware: 264 > ups.load: 0 > ups.load.nominal: 80 > ups.mfr: Hewlett-Packard > ups.model: HP R1500 G3 UPS > ups.power: 0.0 > ups.power.nominal: 1500 > ups.productid: 1fe0 > ups.serial: XXXXXXXXXX > ups.status: OL CHRG > ups.test.result: No test initiated > ups.timer.reboot: -1 > ups.timer.shutdown: -1 > ups.timer.start: -1 > ups.vendorid: 03f0 > > % upsc hp1500 server.version > 2.6.4 > > % upsrw hp1500 > [battery.charge.low] > Remaining battery level when UPS switches to LB (percent) > Type: STRING > Value: 20 > > [input.transfer.high] > High voltage transfer point (V) > Type: STRING > Value: 266.0 > > [input.transfer.low] > Low voltage transfer point (V) > Type: STRING > Value: 194.0 > > [ups.delay.shutdown] > Interval to wait after shutdown with delay command (seconds) > Type: STRING > Value: 20 > > [ups.delay.start] > Interval to wait before (re)starting the load (seconds) > Type: STRING > Value: 30 > > > % upsrw -s battery.charge.low=30 hp1500 > Username (root): admin > Password: > OK > > % upsrw hp1500 > [battery.charge.low] > Remaining battery level when UPS switches to LB (percent) > Type: STRING > Value: 20 > > [...] > > > _______________________________________________ > Nut-upsuser mailing list > Nut-upsuser at lists.alioth.debian.org > http://lists.alioth.debian.org/cgi-bin/mailman/listinfo/nut-upsuser >