2008 Mar 20
1
NUT behaviour when master system fails
...on and what we are doing wrong.
By running a slave upsmon process with a debugging flag set it can be
seen that the 15 minute delay occurs as a result of the upsmon's poll of
the master's upsd process. Once the master has gone off line, the slave
upsmon reports:
polling ups: apcups at nutMaster.domain.uk
get_var: apcups at nutMaster.domain.uk / status
and then 'hangs'. A 15 minute delay follows before the polling process
returns that the master's upsd process is not reachable.
A brief examination of the NUT source code indicates that a system
"write" statement...
2015 Sep 11
3
"upsmon -c fsd" cause system shutdown
hi:
my testing server has two power supply and attach to two ups. one
of the ups is connect to the server with usb.
my upsmon.conf like below:
# for two ups
MONITOR ftups at localhost 1 monmaster nutmaster master
MONITOR ftups at 10.1.1.2 1 monslave nutslave slave
MINSUPPLIES 1
# for early shutdown
NOTIFYFLAG ONBATT EXEC+WALL+SYSLOG
NOTIFYFLAG ONLINE EXEC+WALL+SYSLOG
NOTIFYCMD /usr/sbin/upssched
the early shutdown script use "upsmon -c fsd" to set FSD to
master ups. but when testin...
2019 Mar 30
2
upssched Not Running
2019 Apr 03
2
upssched Not Running
...FYFLAG statements whether I was
> changing them or not. Previously, I had a mixture of commented and
> uncommented, assuming the commented ones used default values.
>
> $ grep -Ev "^(#|\s*$)" /etc/nut/upsmon.conf
> RUN_AS_USER nut
> MONITOR myups1 at localhost:3493 1 nutmaster pass master
> MINSUPPLIES 1
> SHUTDOWNCMD "/sbin/shutdown --poweroff +1"
> NOTIFYCMD /sbin/upssched
> POLLFREQ 10
> POLLFREQALERT 5
> HOSTSYNC 15
> DEADTIME 15
> POWERDOWNFLAG /etc/nut/killpower
> NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC
> NOTIFYFLAG ONBATT S...
2019 Apr 03
0
upssched Not Running
2019 May 25
2
Low Battery False Alarms