search for: notifyflags

Displaying 20 results from an estimated 189 matches for "notifyflags".

Did you mean: notifyflag
2014 Feb 25
3
NUT on Windows, Wall->message.exe
If there is a next Windows release, perhaps the default NOTIFYFLAG's should be adjusted? NOTIFYFLAG ONLINE SYSLOG NOTIFYFLAG ONBATT SYSLOG NOTIFYFLAG LOWBATT SYSLOG NOTIFYFLAG FSD SYSLOG NOTIFYFLAG COMMOK SYSLOG NOTIFYFLAG COMMBAD SYSLOG NOTIFYFLAG SHUTDOWN SYSLOG NOTIFYFLAG REPLBATT SYSLOG NOTIFYFLAG NOCOMM SYSLOG NOTIFYFLAG NOPARENT SYSLOG The 'wall'
2014 Feb 28
0
NUT on Windows, Wall->message.exe
On Feb 25, 2014, at 1:13 AM, Kris Jordan wrote: > If there is a next Windows release, perhaps the default NOTIFYFLAG's should be adjusted? > > NOTIFYFLAG ONLINE SYSLOG > NOTIFYFLAG ONBATT SYSLOG > NOTIFYFLAG LOWBATT SYSLOG > NOTIFYFLAG FSD SYSLOG > NOTIFYFLAG COMMOK SYSLOG > NOTIFYFLAG COMMBAD SYSLOG > NOTIFYFLAG SHUTDOWN SYSLOG > NOTIFYFLAG
2011 Sep 02
2
NUT 2.6.1+ Windows 2008 R2 - NOTIFYCMD not being called
Hi All, I'm using a recent post 2.6.1 build provided by Fred (executables have modified date of 9th August) I have configured upsmon.conf with :- NOTIFYCMD C:\NUT\etc\NotifyCmd.bat and :- NOTIFYFLAG ONLINE SYSLOG+EXEC NOTIFYFLAG ONBATT SYSLOG+EXEC NOTIFYFLAG LOWBATT SYSLOG+EXEC NOTIFYFLAG FSD SYSLOG+EXEC NOTIFYFLAG COMMOK SYSLOG+EXEC NOTIFYFLAG COMMBAD SYSLOG+EXEC
2017 Jun 09
2
Apple Mac slave
On Thu, 8 Jun 2017, Robbie van der Walle wrote: > After the first test and the NAS is restarted I had to change the > setting battery.charge.low again to 80? Does the NAS DSM reset battery.charge.low to 10 or is it internal to the UPS? You will have to experiment by disconnecting the UPS control lead from the NAS and connecting it (if possible) to the Mac. After setting to 80 and a
2006 Jul 11
2
notifycmd problem
hello, i've got a problem with the notifycmd here is a part of my upsmon.conf : NOTIFYCMD /usr/local/ups/bin/nut_notify NOTIFYMSG ONLINE "UPS %s is getting line power" NOTIFYMSG ONBATT "UPS %s is on battery" NOTIFYMSG REPLBATT "The UPS %s battery is bad and needs to be replaced" NOTIFYMSG LOWBATT "UPS %s is being shutdown by the master" NOTIFYMSG FSD
2006 Feb 14
3
Master privileges unavailable on UPS
Hello all, I'm having problems with what I'm told should be a straightforward issue. The message in /var/log/daemon is: <quote> Feb 13 10:37:57 lupin upsmon[31324]: Master privileges unavailable on UPS [lupin1500AVR@localhost]
2010 Jan 09
2
problem with mailing (nut 2.4.1 and a powermust650 -> megatec_usb)
Hello guys Yesterday i started do configure my Mustek Powermust650 with nut using the megatec_usb driver. Everything works fine except for the mailing when something happens. My upsmon looks like this: MONITOR powermust650 at localhost 1 local controller master MINSUPPLIES 1 SHUTDOWNCMD "/sbin/shutdown -h +0" NOTIFYCMD /root/upsmailer POLLFREQ 10 POLLFREQALERT 5 HOSTSYNC 15
2015 Feb 09
0
About your driver NUTDRV_ATCL_USB(8) for install
Dear Chales, Thanks for your quick reply. I have Raspberry with last Kernel [Linux pi1 3.18.6+ #753 PREEMPT Sun Feb 8 14:47:22 GMT 2015 armv6l GNU/Linux] If <upsdrvctl>, <upsd> and <upsmon> are stopped <nutdrv_atcl_usb> Works well without any error as "Device or resource busy". If I run <upsc> command never receive any value from my ups <upsc ups at
2015 Oct 29
2
The system doesn't shutdown
P.S.2 Today I experienced something weird. As I was working, the system started a shutdown and did shut down, then the UPS got powered off and then back on - an expected behavior for a power fail situation. However there was no power failure! I ran nut-journal to check what happened: Previous complete boot through shutdown Oct 29 10:09:33 i7 upsdrvctl[1966]: Using subdriver: MGE HID
2015 Feb 09
2
About your driver NUTDRV_ATCL_USB(8) for install
On Feb 9, 2015, at 6:48 AM, PERE (yahoo.es) <pererivers at yahoo.es> wrote: > 0.028188 Can't set USB configuration: could not set config 1: Device or resource busy > 0.029246 detached kernel driver from USB device... > 0.030559 USB device [0001:0000] opened > 0.866216 read: (8 bytes) => 03 00 00 00 00 00 00 00 > 0.866413 reply[0] = 0x03
2012 Jan 06
1
upsmon+snmp-ups does not shut down system
I've googled and RTFM'ed, but still can't solve this one. I hope you folks can. This affects my entire computer cluster, but let's start simple: I've got a computer running NUT; OS is Scientific Linux 5.5; kernel 2.6.18-274.12.1.el5xen. It connects to an APC SMART-UPS via an APC SmartCard using the snmp-ups driver. It generally works: upsmon will detect if the battery is low
2012 Jan 28
2
No shutdown on empty battery
Hello, I set up a FreeBSD 8.2 system with nut 2.6.1 and a Powerware 5115 connected by RS-232. I expected this setup to shut down before running out of battery power, but I either missed some important configuration or something else went wrong: The syslog says: Jan 9 05:03:42 b1 upsmon[67752]: UPS upsb1 at localhost on battery Jan 9 05:04:42 b1 upsmon[67752]: UPS upsb1 at localhost on line
2006 Jan 09
2
Master privileges unavailable
Hi, I'm using debian sarge on my server and connected a MGE-ups ellipse via the serial port. I searched the internet for the answer, but can't find it. My config files: <upsd.users> [admin] password = pwd allowfrom = 127.0.0.1/32 actions = set instcmds = all [upsmon] password = pwd allowfrom = 127.0.0.1/32 10.0.0.224/32 upsmon master [upsslave] password
2015 Oct 27
0
The system doesn't shutdown
On Tue, 27 Oct 2015, George Anchev wrote: > Yes, that was the power off test. However the upssched-cmd script gave > absolutely no signs of activity. Even it's logger lines don't show up in > journalctl. No any permission error messages - nothing. Only the 2 > messages from upsmon - on battery and then on line power. > > Here is the nut-report: >
2015 Oct 29
0
The system doesn't shutdown
...ly the same thing two days ago with an MGE Ellipse 1500 in which I had changed the batteries. Its clear that the script upssched-cmd should check the real battery charge before shutting anything down. I'll look at this, but it will be next week at the earliest. Meantime your change to the NOTIFYFLAGs is a good fix. > Also - what would be the proper config to *execute* a shutdown if there > is a low battery but *only* when there is an actual power failure > situation (i.e. the UPS is running on battery power)? [I suppose that > might work for the "optimistic" setup] At...
2012 Nov 09
1
181 message.exe processes
Windows Server 2000 R2 Standard edition x64 I found a bunch of message.exe processes running on this system (181 of them in total). The UPS was going on-battery a lot! There is no attached screen and I don't see any message boxes when I RDP. Do I just set NOTIFYCMD to something nonsensical to stop it from running message.exe? It would be nice if the Windows defaults were shown in the
2006 Aug 25
2
suse linux and nut
hi i bought a ultra ULT31502 ups someone seem able to run this ups with nut just see Dean thread on: http://www.tigerdirect.com/applications/searchtools/item-details.asp?EdpNo=770423&Tab=11&NoMapp=0 i use suse 10.1, i installed nut the ups is connected directely to my computer with an usb cable lsusb return Bus 001 Device 004: ID 0d9f:0001 Powercom Co., Ltd with lsmod, i can see
2017 Oct 31
2
Email Alerts for Multiple UPSs with upssched
Ah! So I can detect the source UPS in the upssched.conf and pass it as a distinct event to the shell script. That sounds like an excellent approach. Thanks! GMH From: O'Shaughnessy, Mike [mailto:Mike.OShaughnessy at gd-ms.com] Sent: Tuesday, October 31, 2017 12:46 PM To: Garrett Michael Hayes <Garrett at VerbalImaging.com>; nut-upsuser at lists.alioth.debian.org Subject: RE: Email
2020 Mar 24
2
upsmon SHUTDOWNCMD not working
Bonjour Openbsd 6.6 - NUT 2.7.4 from source - Eaton Ellipse Pro Installation OK upsc OK upsmon -c fsd OK (shutdown effective) I suppose mistake in upsmon config : # upsmon.conf MONITOR ellipse at localhost 1 upsmon pass master MINSUPPLIES 1 SHUTDOWNCMD "/sbin/shutdown -p -h now 'Sylvebarbe killed'" POLLFREQ 60 POLLFREQALERT 60 HOSTSYNC 120 DEADTIME 180 POWERDOWNFLAG
2012 Aug 09
1
problem_connection_NUT_infosec
Hello everybody, I have an Infosec's UPS and would like to shutdown my computer when he's on battery. My Infosec's UPS is not in the list of supported UPS but the driver is the same than megatec's driver (This is the same factory with some differences...) So, here are my configurations : -- Ubuntu Desktop -- apt-get install nut OK UPS connected to ubuntu via USB cable After