2006 Jul 24
2
fentonups driver patch for Effekta MHD3000 UPS
...- added an is_online member to the modeltabs, stating weather the
mode is an on-line UPS or not
- on an on-line UPS the b5 of the status is BYPASS instead of
BOOST/TRIM so set it in the status
- set SHUTDOWN and TEST flag is status according to b1 b2
- added id string to mtab2 for MHD3000
Note the I set the is_online flag for all the existing UPS to 0, so the
behavior will be the same as before the patch, although probably it is
wrong. Someone knowing which model are on-line later can set the flags
correctly.
Please also send the reply to my email, because I'm not on the li...