Issue with On Line Status (APC MGE Galaxy 5500 + AP9635CH)
...) hit in the table wins, IIRC, so if an actual device exposes some
> data in several OIDs (e.g. with different-precision data types, like in
> vendor-extended vs. IETF-standard MIBs), the preference ordering may matter.
>
> Jim
>
>
> On Mon, Mar 27, 2023 at 2:01?PM mateuszx <jasmati09 at gmail.com> wrote:
>
>> So what would it take me to edit NUT's code for my case to work? My
>> Network Management Card sends its output state using unfortunately only (I
>> guess so) this OID: 1.3.6.1.4.1.318.1.1.1.11.1.1.0
>> Weirdly the standard way of obtainin...
2023 Mar 29
1
Issue with On Line Status (APC MGE Galaxy 5500 + AP9635CH)
...ices. The first (or was it
last?) hit in the table wins, IIRC, so if an actual device exposes some
data in several OIDs (e.g. with different-precision data types, like in
vendor-extended vs. IETF-standard MIBs), the preference ordering may matter.
Jim
On Mon, Mar 27, 2023 at 2:01?PM mateuszx <jasmati09 at gmail.com> wrote:
> So what would it take me to edit NUT's code for my case to work? My
> Network Management Card sends its output state using unfortunately only (I
> guess so) this OID: 1.3.6.1.4.1.318.1.1.1.11.1.1.0
> Weirdly the standard way of obtaining Battery Status (dr...
2023 Mar 27
1
Issue with On Line Status (APC MGE Galaxy 5500 + AP9635CH)
...problem but the question is:
How do I integrate my bit recognition with NUT's nut2mib struct and so on...
I am working on drivers/apc-mib.c UPS driver
Maybe is there something relatable already in the code so I can "make my
work easier"?
Matthew
czw., 9 mar 2023 o 16:00 mateuszx <jasmati09 at gmail.com> napisa?(a):
> I've got an update on this case
> Using tkmib I discovered that my UPS (NMC per say) sends its state by OID
> 1.3.6.1.4.1.318.1.1.1.11.1.1.0
> .iso.org.dod.internet.private.enterprises.apc.products.hardware.ups.upsState.upsBasicState.upsBasicStateOutp...
2023 Mar 09
1
Issue with On Line Status (APC MGE Galaxy 5500 + AP9635CH)
...s getting ups.status about changing "a few lines of code" in
let's say apc-mib.c file in the drivers folder of the repo or I should make
a commit and code ups.status depending on bits received using this OID?
I am running NUT 2.8.0 at the moment.
czw., 9 mar 2023 o 14:14 mateuszx <jasmati09 at gmail.com> napisa?(a):
> I've got an update on this case
> Using tkmib I discovered that my UPS (NMC per say) sends its state by OID
> 1.3.6.1.4.1.318.1.1.1.11.1.1.0
> .iso.org.dod.internet.private.enterprises.apc.products.hardware.ups.upsState.upsBasicState.upsBasicStateOutp...
2023 Feb 27
1
Issue with On Line Status (APC MGE Galaxy 5500 + AP9635CH)
Hello,
At my workplace I have exact UPS config as stated in the subject (APC MGE
Galaxy 5500 + AP9635CH).
I have it set up to work with snmp-ups NUT driver.
Despite many readings from *upsc* command I am not receiving "On Line
Status" (ups.status OL) nor "On Battery Status" (ups.status OB) and
therefore I can't get my systems to shutdown during a power outage event.
2023 Feb 27
1
Issue with On Line Status (APC MGE Galaxy 5500 + AP9635CH)
Hello,
At my workplace I have exact UPS config as stated in the subject (APC MGE
Galaxy 5500 + AP9635CH).
I have it set up to work with snmp-ups NUT driver.
Despite many readings from *upsc* command I am not receiving "On Line
Status" (ups.status OL) nor "On Battery Status" (ups.status OB) and
therefore I can't get my systems to shutdown during a power outage event.