Displaying 20 results from an estimated 21 matches for "energysave".
2017 Feb 21
1
[HCL] Powerware PW5125 with driver bcmxcp
...u'd like
me to do with it.
Let me know if there is anything else you need...
-------------- next part --------------
via NUT 2.7.4, FreeBSD 11.0
# upsc
ambient.temperature: 42
ambient.temperature.high: 70
battery.charge: 95
battery.charge.restart: 76
battery.charger.status: resting
battery.energysave.delay: 0
battery.energysave.load: 0
battery.packs: 1
battery.runtime: 2760
battery.runtime.low: 2
battery.voltage: 52.26
device.mfr: Eaton
device.model: PW5125 1500i
device.part: 05146632-5501
device.serial: UX475A0xxxxx
device.type: ups
driver.name: bcmxcp
driver.parameter.baud_rate:...
2017 Feb 20
2
[HCL] Powerware PW5125 with driver bcmxcp
This UPS is already listed in the compatibility list. But I wanted to
add the instant commands supported by upscmd:
============================
Instant commands supported on UPS [PW5125]:
beeper.disable - Disable the UPS beeper
beeper.enable - Enable the UPS beeper
beeper.mute - Temporarily mute the UPS beeper
load.on - Turn on the load immediately
outlet.1.load.off - Turn off the load on
2015 Mar 16
0
Roadmap to 2.7.3
On Mar 4, 2015, at 9:04 AM, Charles Lepple wrote:
> We only have a few open items that I think should be resolved before releasing 2.7.3. The list grew a bit in the past week, but we'll cover that later. Here is the list:
>
> * #93: Devices Dumps Library improvements <https://github.com/networkupstools/nut/issues/93>
> * #158: Powerware BCMXCP advanced features
2020 Sep 11
1
UPS recommendation for NUT and power-on-delay support
...port it.
>
> Thank you,
> Bart
Can you tell from this output? If not, what should I be looking for to answer your question?
[dan at slocum:~] $ upsc ups02
battery.capacity: 9.00
battery.charge: 100
battery.charge.low: 20
battery.charge.restart: 0
battery.charger.status: resting
battery.energysave: no
battery.protection: yes
battery.runtime: 1941
battery.type: PbAc
device.mfr: EATON
device.model: Eaton 5PX 2200
device.serial: G091C30079
device.type: ups
driver.name: dummy-ups
driver.parameter.mode: repeater
driver.parameter.pollinterval: 2
driver.parameter.port: ups02 at bast.int.unixathome....
2015 Mar 19
4
Roadmap to 2.7.3
...> what needs to be agreed upon for the new names?
>
I pushed to the same branch and documented the new vars: input.*.load,
input.*.realpower and input.*.power
No much need for a hard agreement, more for info...
I've rebased and pushed this branch to master.
I've also fixed the eaton-energysave branch as per the names pushed in in
#158.
Note that I've proposed and made an addition for
battery.energysave.realpower
Just rebased and merged the branch few minutes ago.
The rest is good to me too.
So is everything good to go from your PoV Charles?
thanks for this update and all your work,...
2013 Nov 01
3
Merging blzr as blazer (and un-merging voltronic?)
Daniele,
Thanks again for your work on both the voltronic and blzr drivers. To get the most exposure to new drivers, what we have typically done in the past is to rename the existing driver as *-old, so that users get the new driver by default when they upgrade (but the old driver is still available if there are regressions). This is how we are incorporating Michal's apcsmart updates.
On
2010 Oct 06
1
Model list missing my UPS, here is info for inclusion on the list
...TS:
>
> EATON Powerware 5130 using UPS cable works.
>
> lsusb shows:
> ID 0463:ffff MGE UPS Systems UPS
>
>
> nkj at grisen:~$ sudo upsc PingvinUPS
> battery.capacity: 9.00
> battery.charge: 71
> battery.charge.low: 20
> battery.charge.restart: 0
> battery.energysave: no
> battery.protection: yes
> battery.runtime: 2449
> battery.type: PbAc
> device.mfr: EATON
> device.model: 5130 RT 3000
> device.serial: NC302C5031
> device.type: ups
> driver.name: usbhid-ups
> driver.parameter.pollfreq: 30
> driver.parameter.pollinterval: 2
>...
2014 May 26
2
Resetting replace battery status on Pulsar 1500
...I can't find out how to reset the flag in NUT.
I've looked in upsc, upsrw and upscmd but none seem to have a suitable option.
The UPS is connected via RS232 and upsc output is as follows..
battery.capacity: 9.00
battery.charge: 100
battery.charge.low: 50
battery.charge.restart: 0
battery.energysave: no
battery.protection: yes
battery.runtime: 3000
battery.type: PbAc
device.mfr: MGE UPS SYSTEMS
device.model: Pulsar 1500
device.serial: 1Y3G41223
device.type: ups
driver.name: mge-shut
driver.parameter.offdelay: 120
driver.parameter.ondelay: 190
driver.parameter.pollfreq: 30
driver.parameter.poll...
2015 Mar 04
5
Roadmap to 2.7.3
We only have a few open items that I think should be resolved before releasing 2.7.3. The list grew a bit in the past week, but we'll cover that later. Here is the list:
* #93: Devices Dumps Library improvements <https://github.com/networkupstools/nut/issues/93>
* #158: Powerware BCMXCP advanced features <https://github.com/networkupstools/nut/pull/158>
* #185: insecure storage
2010 Mar 01
3
NUT with Eaton 9135 6000
Hi Dag
2010/2/28 Dag Atle Nettum <dagatle at innit.no>
> Hello
>
>
>
> I understand you are the project leader of Nut.
>
>
>
> In my company we have a Eaton 9135 6000 UPS, we are running NUT 2.4.1
> (Debian squeeze)
>
>
>
> The ups is connected with a USB cable but it reports a temperature of 300
> degredes.
>
>
>
> Can I send you
2020 Sep 30
2
reset "replace battery" flag
...hid-ups driver with what nut believes it
> sees. I have a feeling that some flag is misinterpreted
Sure. Attached.
Lionel
-------------- next part --------------
battery.capacity: 12.00
battery.charge: 100
battery.charge.low: 20
battery.charge.restart: 0
battery.charger.status: resting
battery.energysave: no
battery.protection: yes
battery.runtime: 4734
battery.type: PbAc
device.mfr: EATON
device.model: Eaton 5PX UPS LI R 3000
device.serial: 3C86090469
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter...
2023 Jan 17
1
PR to test for users of Qx devices (blazer and nutdrv_qx)
...0
min_bypass_freq, settable range: 50.0..59.0
No values for battery high/low voltages
Using 'guesstimation' (low: 62.400000, high: 90.000000)!
setvar(ups.delay.start, 60)
setvar: SUCCEED
setvar(ups.delay.shutdown, 30)
setvar: nothing to do... [ups.delay.shutdown]
battery.charge: 100
battery.energysave: no
battery.packs: 1
battery.protection: yes
battery.runtime: 2820
battery.voltage: 082.0
battery.voltage.high: 90.00
battery.voltage.low: 62.40
battery.voltage.nominal: 72.0
device.model: 3K
device.type: ups
driver.name: nutdrv_qx
driver.parameter.bypass_when_off: disabled
driver.parameter.offdela...
2023 Jan 17
1
PR to test for users of Qx devices (blazer and nutdrv_qx)
...0
min_bypass_freq, settable range: 50.0..59.0
No values for battery high/low voltages
Using 'guesstimation' (low: 62.400000, high: 90.000000)!
setvar(ups.delay.start, 60)
setvar: SUCCEED
setvar(ups.delay.shutdown, 30)
setvar: nothing to do... [ups.delay.shutdown]
battery.charge: 100
battery.energysave: no
battery.packs: 1
battery.protection: yes
battery.runtime: 2820
battery.voltage: 082.0
battery.voltage.high: 90.00
battery.voltage.low: 62.40
battery.voltage.nominal: 72.0
device.model: 3K
device.type: ups
driver.name: nutdrv_qx
driver.parameter.bypass_when_off: disabled
driver.parameter.offdela...
2020 Sep 25
2
reset "replace battery" flag
On Thu, Sep 24, 2020 at 06:51:23PM +0300, Manuel Wolfshant wrote:
> On 9/21/20 9:47 PM, Lionel Élie Mamane wrote:
>> We have a HP R/T 3000 G4 UPS; according to the data returned by the
>> usbhid-ups driver, it seems to be a "badge engineered" Eaton 5PX
>> UPS LI R 3000.
>> We have a stubborn "Replace Battery" alarm that stays (...):
>> The
2014 Dec 17
2
EATON 9SX not display battery.charge
...cp uucp 4604 Dec 15 17:19 upsd.conf
-rw-r----- 1 uucp uucp 15273 Dec 15 17:14 upsmon.conf
# cat /etc/devfs.conf
perm ugen1.3 0660
own ugen1.3 root:uucp
# cat /etc/devfs.rules
[nutusb=10]
add path 'usb/1.3.0' group uucp mode 0660
upsc eaton9sx
battery.capacity: 5.00
battery.energysave: no
battery.protection:
battery.type: PbAc
device.mfr: EATON
device.model: Eaton 9SX 5000i
device.serial: G200E36025
device.type: ups
driver.flag.maxreport: enabled
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.version: 2.7...
2023 Jan 15
1
PR to test for users of Qx devices (blazer and nutdrv_qx)
Cheers,
One PR waiting to get into 2.8.1 release timeframe is
https://github.com/networkupstools/nut/pull/1652 stemming from issue
https://github.com/networkupstools/nut/issues/1279
The gist of it is that "battery.voltage" and "battery.charge" were not
always reported correctly with nutdrv-qx driver (might be handled better by
blazer drivers though), and the overrides
2011 Oct 06
1
Differences between USB and serial on an MGE Pulsar Evolution 3000
...voltage.nominal "72"
12.389358 entering hid_get_value(UPS.PowerSummary.Output.Current)
12.389363 entering lookup_path(UPS.PowerSummary.Output.Current)
USB (using usbhid-ups)
----------------------
battery.charge: 100
battery.charge.low: 20
battery.charge.restart: 0
battery.energysave: no
battery.protection: yes
battery.runtime: 5400
battery.type: PbAc
device.mfr: MGE UPS SYSTEMS
device.model: Pulsar Evolution 3000
device.serial: AF3Ennnnn
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.pa...
2017 Mar 23
5
Fatal EEPROM fault!
Hello,
Sorry if any of this is obvious - I'm new to NUT.
NUT via upsc is displaying (edited for length):
device.model: Eaton 5P 2200
device.type: ups
driver.name: usbhid-ups
ups.alarm: Fatal EEPROM fault!
ups.status: ALARM OL CHRG
ups.test.interval: 604800
ups.test.result: Done and passed
driver.version: 2.7.2
driver.version.data: MGE HID 1.33
driver.version.internal: 0.38
Is this possibly
2018 Jan 16
2
Eaton 5PX after battery replacement still says "replace battery" in NUT
...ion: 2.7.4
Installation method: from source tarball
UPS device: Eaton 5PX2000IRT, 240V, 1800W, 2000VA, bought in October 2013
Here?s the status as reported by upsc:
battery.capacity: 9.00
battery.charge: 100
battery.charge.low: 20
battery.charge.restart: 0
battery.charger.status: floating
battery.energysave: no
battery.protection: yes
battery.runtime: 1032
battery.type: PbAc
device.mfr: EATON
device.model: Eaton 5PX 2000
device.serial: G098D27047
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.synchron...
2020 Sep 05
9
ups not being started sat reboot
But runs normally if started. On a rpi4 running an uptodate raspbian
buster, how do I set it to auto start at boot time?
Thanks.