how to use multiple UPS with timers
...is set to 1. Afaik NUT waits for OB and LB before shutting down the system. Is there a way to change this behavior to only wait for OB? Then I would use FINALDELAY in case the power outage doesn't last long. I already tried to change the battery.runtime.low setting over the webinterface of the CS121 (snmp is readonly) but with our AEG UPS, this didn't work as expected(seems like a firmware bug) and I need to work around this problem. I'm already in contact with AEG but I also have a bunch of UPS units from other manufacturers to cover with the same controller card and different (potent...
2016 May 20
1
ups.status don't switch to "OB LB"
...alpower: 1467.00 output.L3-N.voltage: 229.00 output.L3.current: 10.80 output.L3.power.percent: 19.00 output.L3.realpower: 2533.00 output.phases: 3.00 output.power.nominal: 0.00 output.realpower.nominal: 0.00 output.voltage.nominal: 0.00 ups.beeper.status: UNKNOWN ups.firmware: n/a ups.firmware.aux: CS121 v 5.41.8 ups.mfr: Legrand ups.model: KEOR T ups.start.auto: no ups.status: OL ups.test.result: no test initiated ups.timer.reboot: -1 ups.timer.shutdown: -1 ups.timer.start: -1
2018 May 08
4
how to use multiple UPS with timers
Hi, I need to shut down a VMWare host if both connected UPS are x minutes on battery. Both UPS are connected via SNMP. Because there are multiple vm running on that host, shutting every vm down takes some time. So most likely, waiting for low battery, the time left won't be enough. I tried overwriting the settings for low battery but that didn't work. Are timers the only possible