search for: cpqpower_oid_alarm_ob

Displaying 6 results from an estimated 6 matches for "cpqpower_oid_alarm_ob".

2013 Jul 17
2
HP R12000/3 UPS reports status as OL DISCHRG OB
...t; }, */ /* { 4, "Resting" }, */ /* { 5, "Unknown" }, */ { 0, "NULL" } } ; I could see the battery monitoring circuit discharging the battery occasionally for maintenance, but is there a separate front-panel indicator for this mode? The third one is CPQPOWER_OID_ALARM_OB. This definitely doesn't make sense, since things with "alarm" in the name are usually pretty direct. The big question in my mind is, where did the NUT definitions come from? Did your UPS come with a CD that might contain a SNMP MIB definition file? Or is there an area on the HP sup...
2014 Feb 27
0
snmp-ups sends status "OL OB" on HP R3000 UPS with AF465A management card [UPDATE]
...as "CPQPOWER_OID_POWER_STATUS"), the > value returned by both UPSes is 3, meaning "OL" as defined in > "cpqpower_pwr_info[]" (which is indeed the expected state for the UPS at > present. > > But if I inspect OID .1.3.6.1.4.1.232.165.3.7.3.0 > ("CPQPOWER_OID_ALARM_OB") as suggested by Arnaud, this one returns "1" > on both UPSes (i.e. "OB", as defined in "cpqpower_alarm_ob[]") -- an > information which is clearly inaccurate. Both UPSes are currently on > grid power, as reported by their Web management interface. >...
2013 Jul 16
0
HP R12000/3 UPS reports status as OL DISCHRG OB
Sorry about that! Chris. Chris Pratt Development Infrastructure Manager T: +44 118 929 4176 | M: +44 7979 854 307 | F: +44 118 929 4001 -----Original Message----- From: Charles Lepple [mailto:clepple at gmail.com] Sent: 16 July 2013 00:32 To: Pratt Chris Subject: Re: [Nut-upsuser] HP R12000/3 UPS reports status as OL DISCHRG OB On Jul 15, 2013, at 9:35 AM, Pratt Chris wrote: > Debug output
2014 Feb 27
2
snmp-ups sends status "OL OB" on HP R3000 UPS with AF465A management card
...ined in ./drivers/compaq-mib.c as "CPQPOWER_OID_POWER_STATUS"), the value returned by both UPSes is 3, meaning "OL" as defined in "cpqpower_pwr_info[]" (which is indeed the expected state for the UPS at present. But if I inspect OID .1.3.6.1.4.1.232.165.3.7.3.0 ("CPQPOWER_OID_ALARM_OB") as suggested by Arnaud, this one returns "1" on both UPSes (i.e. "OB", as defined in "cpqpower_alarm_ob[]") -- an information which is clearly inaccurate. Both UPSes are currently on grid power, as reported by their Web management interface. Both UPS management...
2013 Jul 15
4
HP R12000/3 UPS reports status as OL DISCHRG OB
Hi. Back before Christmas Arnaud sent me a patch for the snmp-ups driver for my HP R12000/3 UPS. Unfortunately shortly after I had to take quite a lot of sick leave so wasn't able to progress it, but I'm working on it again now. I'm at the point where I can start the driver with upsdrvctl and start the daemon with upsd. When I check the UPS status though it shows as OL DISCHRG OB,
2014 Mar 11
2
snmp-ups sends status "OL OB" on HP R3000 UPS with AF465A management card [UPDATE]
...POWER_STATUS"), the >> value returned by both UPSes is 3, meaning "OL" as defined in >> "cpqpower_pwr_info[]" (which is indeed the expected state for the UPS at >> present. >> >> But if I inspect OID .1.3.6.1.4.1.232.165.3.7.3.0 >> ("CPQPOWER_OID_ALARM_OB") as suggested by Arnaud, this one returns "1" >> on both UPSes (i.e. "OB", as defined in "cpqpower_alarm_ob[]") -- an >> information which is clearly inaccurate. Both UPSes are currently on >> grid power, as reported by their Web management inte...