search for: bnt500ap

Displaying 6 results from an estimated 6 matches for "bnt500ap".

2013 Jun 10
2
several problems with Powercom BNT-500AP
I took the log. Here's what happened. Broadcast Message from nut at rasp (somewhere) at 16:18 ... UPS BNT500AP at localhost battery needs to be replaced occurred when for the first time value "1" was read as "UPS.PowerSummary.PresentStatus.NeedReplacement", on this line: 6409.240690 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x0a, Offset: 6, Size: 1, Va...
2013 Jun 11
0
several problems with Powercom BNT-500AP
[I am CC'ing Alexey from Powercom in case he has seen any of these issues with the Raspberry Pi hardware.] On Jun 10, 2013, at 1:05 PM, M?rti?? Pu??tis wrote: > I took the log. Here's what happened. > Broadcast Message from nut at rasp > (somewhere) at 16:18 ... > UPS BNT500AP at localhost battery needs to be replaced > > occurred when for the first time value "1" was read as "UPS.PowerSummary.PresentStatus.NeedReplacement", on this line: > 6409.240690 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x0a, Offset:...
2013 Jun 05
2
several problems with Powercom BNT-500AP
...?t connected to UPS doesn?t reboot. 4. This is the most bothering. I have seen it only once. NUT reported ?on battery? (actually there was no brownout) followed by immediate ?battery is low?, that triggered shutdown of pi. Broadcast Message from nut at rasp (somewhere) at 20:45 ... UPS BNT500AP at localhost on battery Broadcast Message from nut at rasp (somewhere) at 20:45 ... UPS BNT500AP at localhost battery is low Broadcast Message from nut at rasp (somewhere) at 20:45 ... Immediately after shutdown I turned the Raspberry pi on and checked the status. It showed...
2013 Jun 08
0
several problems with Powercom BNT-500AP
On Jun 8, 2013, at 12:57 PM, M?rti?? Pu??tis wrote: > I'll take a longer driver log. This page (http://www.networkupstools.org/support.html) says that to take a driver log NUT should be stopped, so I won't be able to tell when these events occurred within a driver log. Hmm, I didn't realize it said that, but I think that's to prevent having two copies of the same driver
2013 Jun 08
2
several problems with Powercom BNT-500AP
Thanks for the support. Here's list of when transition to battery with return to utility power within a few seconds occurred in last few days: Wednesday 1:41 11:48 11:54 12:59 13:42 14:42 18:13 18:14 Thursday 5:23 Friday 5:12 7:39 7:43 Saturday 7:34 Here's list of when messages that battery needs replacement occurred: Wednesday 20:34 Thursday 9:07 23:09 Friday 18:25 Saturday 7:32 19:47
2013 Nov 27
0
several problems with Powercom BNT-500AP
...[I am CC'ing Alexey from Powercom in case he has seen any of these issues with the Raspberry Pi hardware.] On Jun 10, 2013, at 1:05 PM, M?rti?? Pu??tis wrote: > I took the log. Here's what happened. > Broadcast Message from nut at rasp > (somewhere) at 16:18 ... > UPS BNT500AP at localhost battery needs to be replaced > > occurred when for the first time value "1" was read as "UPS.PowerSummary.PresentStatus.NeedReplacement", on this line: > 6409.240690 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x0a, Offset:...