2010 Mar 26
2
apcupsd, APC UPSs, and batteries, resolved
...t; for some APC SmartUPS 3000 - rackmount UPSs. The "kit", costing about half of what APC is asking, is just the batteries, and you pull the tray out, open it up, and swap out the batteries. Except, I did this on one... and the replace battery light never went out. Not using apcupsd's apctest, not pushing the button. The five lights on the right that show power level went down to about one or two, and took an hour or two to come back up. apctest just said replace battery was the status. I put another set in. I swapped it with another UPS, and its lights went on, so it wasn't just t...
2014 Dec 04
0
Changing self test date
...ts on APC UPSes ? I'd > like to be able to choose the day and the hour so that it happens at office > hours, in case of any problem... > > I've tried to do this by launching a test at a convenient time, but the self > tests still occurs at the previous date and hour :-( The apctest program from apcupsd does not offer much more insight: http://sourceforge.net/p/apcupsd/svn/HEAD/tree/branches/Branch-3_14/src/apctest.c#l2202 This forum post from 2013 suggests that an easy way is to change the UPS setting to "test at power on", then use a script (with NUT, you woul...
2014 Dec 04
2
Changing self test date
Hello, does any one know how to change the date of the self tests on APC UPSes ? I'd like to be able to choose the day and the hour so that it happens at office hours, in case of any problem... I've tried to do this by launching a test at a convenient time, but the self tests still occurs at the previous date and hour :-( Regards. -- Frantz de Germain D?partement Informatique UFR
2010 Jan 08
3
USB problems on 8.0-STABLE
I am having problems with mouse, keyboard and APC UPS. When attempting to start apcupsd I get the following error: Jan 8 17:42:06 Ace apcupsd[1606]: apcupsd FATAL ERROR in generic-usb.c at line 636 Cannot find UPS device -- For a link to detailed USB trouble shooting information, please see <http://www.apcupsd.com/support.html>. Jan 8 17:42:06 Ace apcupsd[1606]: apcupsd error shutdown
2010 Jan 22
1
apcupsd
...PC batteries, which were dead, with new ones, non-APC. They're just dumb batteries, no chips or whatever on them. If I hook it up using a serial cable, I can get info. If I hook it up the way I had it, with APC's weird USB cable - and this is the way it was working before - it fails. I run apctest, and it gives me: Attached to driver: usb sharenet.type = DISABLE cable.type = USB_CABLE You are using a USB cable type, so I'm entering USB test mode mode.type = USB_UPS Setting up the port ... Hello, this is the apcupsd Cable Test program. This part of apctest is for testing USB UPSes. Get...
2013 Jan 13
0
APC UPS: replacement battery always triggers shutdown
...this they'd be greatly appreciated. > >I've been in the same situation after replacing the battery in SC620I model. > >Then I found http://old.nabble.com/SmartUPS-and-new-battery-td20678966.html >and followed the procedure: > >1. Shutdown the apcupsd daemon. >2. Run apctest >3. Choose option 6 to enter terminal mode >4. Enter Y (UPS should respond SM) >5. Enter 1 (one, not el; wait 4 seconds) >6. Enter 1 (one, not el; UPS should respond PROG) >7. Enter 0 (zero, not oh; UPS should respond with current constant) >8. Enter + (plus) or - (minus) to incre...
2014 Dec 05
2
Changing self test date
...like to be able to choose the day and the hour so that it happens at > > office hours, in case of any problem... > > > > I've tried to do this by launching a test at a convenient time, but the > > self tests still occurs at the previous date and hour :-( > > The apctest program from apcupsd does not offer much more insight: > > http://sourceforge.net/p/apcupsd/svn/HEAD/tree/branches/Branch-3_14/src/apctest.c#l2202 > > This forum post from 2013 suggests that an easy way is to change the UPS > setting to "test at power on", then use a s...
2012 Nov 11
1
APC UPS: replacement battery always triggers shutdown
?I've been using nut on an APC Back-UPS 750 for several years with no problem, seeing the walled "UPS on battery power" messages during short 1-2 minute outages. This is connected with the original USB cable that came with the unit. After replacing the battery recently, nut always triggers a shutdown when AC power is cut off, even if only for 1 minute. I see that the data fields
2014 May 03
0
NUT + OpenBSD + dc2500cc + APC Smart-UPS SC620 = problem
...ou probably only need to pass one "-D" flag to see at what point the detection fails. > I suspect there is something special with serial ports on d2500cc motherboard > as I also tried, out of curiousity, apcupsd from OpenBSD ports, and it failed > to detect the UPS either. Does apctest from apcupsd have any better diagnostics? > I wonder if anybody else has successfully run NUT on d2500cc motherboard with > serial UPS?
2014 May 02
2
NUT + OpenBSD + dc2500cc + APC Smart-UPS SC620 = problem
Hi, I am trying to set up NUT on a mini-ITX system running OpenBSD 5.5. I have an APC Smart-UPS SC620 which runs perfectly well on Ubuntu, with nut-2.2.1. Ubuntu system uses ASUS motherboard. On mini-ITX system, I have Intel d2500cc motherboard with 4 serial ports. I've tested ports by connecting them with a null-modem cable and running cu in 2 terminals. Type in one terminal, output shows
2023 Nov 27
1
APC Modbus support is finally here!
...orrect battery.date.maintenance. but I think that's not very important. there's not even that attribute at apcupsd.) 3. test.battery.stop works fine at SRT3000XL. but it is not working at SMT2200RM2U (same experience as the driver author). I think it is not important. BTW, at program "apctest" from apcupsd, the function "test.battery.start" is called "self test", and the physical ups panel also shows "self test". the function "test.panel.start" is called "alarm test" at apctest. what bothers me is when testing, the ups status will b...
2023 Nov 27
1
APC Modbus support is finally here!
...orrect battery.date.maintenance. but I think that's not very important. there's not even that attribute at apcupsd.) 3. test.battery.stop works fine at SRT3000XL. but it is not working at SMT2200RM2U (same experience as the driver author). I think it is not important. BTW, at program "apctest" from apcupsd, the function "test.battery.start" is called "self test", and the physical ups panel also shows "self test". the function "test.panel.start" is called "alarm test" at apctest. what bothers me is when testing, the ups status will b...
2017 Apr 12
0
PowerCom shutdown command
...WERCOM Co.,LTD" ??? bus = "002" ??? pollfreq = 10 ??? offdelay = 120 ??? ondelay = 180 Monitoring works fine, but: upscmd -u UPSUSER -p UPSPASSWD -a RPT-1000AP shutdown.return says "OK" and does nothing. Meanwhile apcusd is able to poweroff this UPS correctly. USB dump by apctest "Test kill UPS power" command: CTRL_IN(0.0): 00:00:0000:0000:1030303030 # 2.5421979427337646 CTRL_OUT(0.0):21:09:0310:0000:1040000000 # 0.0000979900360107 CTRL_IN(0.0): 00:00:0000:0000:1030303030 # 0.0175840854644775 CTRL_IN(0.0): 00:00:0000:0000:0f00 # 0.0109839439392090 CTRL_OUT(0.0):21...
2023 Nov 24
1
APC Modbus support is finally here!
I believe some fixes were applied to the branch since your report (most visibly, about battery time settings), are you in position to test how it behaves now? :) Thanks in advance, Jim Klimov On Wed, Nov 22, 2023 at 3:20?PM Jim Klimov <jimklimov+nut at gmail.com> wrote: > Great! Thanks for the info, and hope the driver author can address the > nits (forwarding now...) > > Jim
2023 Nov 24
1
APC Modbus support is finally here!
I believe some fixes were applied to the branch since your report (most visibly, about battery time settings), are you in position to test how it behaves now? :) Thanks in advance, Jim Klimov On Wed, Nov 22, 2023 at 3:20?PM Jim Klimov <jimklimov+nut at gmail.com> wrote: > Great! Thanks for the info, and hope the driver author can address the > nits (forwarding now...) > > Jim
2023 Nov 27
2
APC Modbus support is finally here!
...ce. but I > think that's not very important. there's not even that attribute at > apcupsd.) > > 3. test.battery.stop works fine at SRT3000XL. but it is not working at > SMT2200RM2U (same experience as the driver author). I think it is not > important. BTW, at program "apctest" from apcupsd, the function > "test.battery.start" is called "self test", and the physical ups panel > also shows "self test". the function "test.panel.start" is called > "alarm test" at apctest. what bothers me is when testing, the up...
2023 Nov 27
2
APC Modbus support is finally here!
...ce. but I > think that's not very important. there's not even that attribute at > apcupsd.) > > 3. test.battery.stop works fine at SRT3000XL. but it is not working at > SMT2200RM2U (same experience as the driver author). I think it is not > important. BTW, at program "apctest" from apcupsd, the function > "test.battery.start" is called "self test", and the physical ups panel > also shows "self test". the function "test.panel.start" is called > "alarm test" at apctest. what bothers me is when testing, the up...
2010 Mar 02
3
Back to apcupsd
Ok, so another apc UPS 3000 complained about bad batteries, and I changed them out from the same order that I'd gotten in a couple of months ago. The APC SmartUPS 3000 started connecting and disconnecting the USB connection. I brought down and up the service, no joy. Finally, after googling, I found a *completely* undocumented way to start apcupsd, that a few years ago someone was told to
2014 May 03
2
NUT + OpenBSD + dc2500cc + APC Smart-UPS SC620 = problem
...inting out 5 lines and then timing out and giving up in 15 seconds. > >> I suspect there is something special with serial ports on d2500cc motherboard >> as I also tried, out of curiousity, apcupsd from OpenBSD ports, and it failed >> to detect the UPS either. > > Does apctest from apcupsd have any better diagnostics? No, it timed out almost exactly the same as NUT apcsmart driver. > >> I wonder if anybody else has successfully run NUT on d2500cc motherboard with >> serial UPS? > Now the good news is that I tried connecting UPS through USB-serial...
2013 Feb 28
8
false low battery alarm
Hi, I have two types of UPS devices and one of them (APC) gave me a false "low battery" alert. I can't reproduce the problem... Also, there was nothing apparently wrong with the UPS at the time of the false alert. All I could do was grab the driver values within a minute after the "low battery" notification. These are the values: battery.runtime.low : 120