Displaying 5 results from an estimated 5 matches for "ap9620".
Did you mean:
19620
2014 Dec 17
2
interrupt pipe disabled [APC SMT3000RMI2U]
On Dec 17, 2014, at 3:46 AM, Frantz de Germain <frantz at info.univ-angers.fr> wrote:
> This seems to me a little bit complicated :-( Instead, can I use the
> apcsmart driver with the provided 940-0625a c?ble (RJ45/DB9 connectors) ? Or
> do I need to acquire an AP9620 SmartSlot expansion card, as I've seen in the
> Hardware compatibility list page ?
It sounds like you might need the AP9620:
http://news.gmane.org/find-root.php?message_id=512C533A.8010706%40sagebrushnetworks.com
Otherwise, I imagine that the DB9 just provides serial Microlink, instead...
2013 Feb 26
1
APC SMX3000RMLV2UNC with AP9631 NUT compatibility via network
.../resource/include/techspec_index.cfm?base_sku=SMX3000RMLV2UNC
http://www.apc.com/resource/include/techspec_index.cfm?base_sku=AP9631
I planned to use network connectivity with this unit and apcupsd, but have not
this far. The UPS is shared by multiple servers, so a USB or Serial connection
via the AP9620 is not feasible:
http://www.apc.com/resource/include/techspec_index.cfm?base_sku=AP9620
I found and started researching NUT, and would prefer using NUT with this APC
and future purchases of NUT-compatible hardware from OEMs other than APC,
e.g. Eaton.
I see a prior thread discussing the unfortun...
2014 Dec 18
0
interrupt pipe disabled [APC SMT3000RMI2U]
> Also, I don't think we have any confirmation of the variables that the AP9620 provides. Here is the list of full 'upsc' output for various APC models:
>
> http://buildbot.networkupstools.org/~buildbot/cayman/docs/latest/ddl/APC/index.html
Frantz,
Actually, it would be useful if you could send a copy of the output of 'upsc', 'upscmd -l' and...
2014 Dec 17
0
interrupt pipe disabled [APC SMT3000RMI2U]
...and if you need connectivity with an existing NUT setup:
>
> http://www.networkupstools.org/docs/man/apcupsd-ups.html
This seems to me a little bit complicated :-( Instead, can I use the
apcsmart driver with the provided 940-0625a c?ble (RJ45/DB9 connectors) ? Or
do I need to acquire an AP9620 SmartSlot expansion card, as I've seen in the
Hardware compatibility list page ?
--
Frantz de Germain
D?partement Informatique UFR Sciences / DDN
Universit? d'Angers
2014 Dec 17
2
interrupt pipe disabled [APC SMT3000RMI2U]
On Dec 16, 2014, at 9:45 AM, Frantz de Germain <frantz at info.univ-angers.fr> wrote:
> Bye the way I just realize that I can't retrieve the ups.load, among other
> thing :-(
To the best of my knowledge, Microlink is not supported by any third-party tools (including NUT), but some variables are exposed via standard USB HID. Apparently, ups.load is not one of them.
Your UPS might