2018 Jan 17
0
Eaton 5PX after battery replacement still says "replace battery" in NUT [HCL]
...first time in our Eaton 5PX a couple of weeks ago, but we haven?t been able to clear the ?ups.alarm: replace battery!? status.
>
> Details of our installation are:
> OS: Debian 6
> NUT version: 2.7.4
> Installation method: from source tarball
> UPS device: Eaton 5PX2000IRT, 240V, 1800W, 2000VA, bought in October 2013
>
We don't have a complete dump for the 5PX, but I would assume that it has at least one or two battery test commands, and I would recommend trying the quick one first. (If you can also send the output of "upscmd -l" and "upsrw", we can ad...
2018 Jan 16
2
Eaton 5PX after battery replacement still says "replace battery" in NUT
...replaced the battery for the first time in our Eaton 5PX a couple of weeks ago, but we haven?t been able to clear the ?ups.alarm: replace battery!? status.
Details of our installation are:
OS: Debian 6
NUT version: 2.7.4
Installation method: from source tarball
UPS device: Eaton 5PX2000IRT, 240V, 1800W, 2000VA, bought in October 2013
Here?s the status as reported by upsc:
battery.capacity: 9.00
battery.charge: 100
battery.charge.low: 20
battery.charge.restart: 0
battery.charger.status: floating
battery.energysave: no
battery.protection: yes
battery.runtime: 1032
battery.type: PbAc
device.mfr: E...