2018 Dec 03
2
MGE EllipseMAX 1500 shuts down after a few hours
I have taken out the batteries and measured them with a multimeter.
They put out 13V (they are rated 12V 9Ah).
Putting them back again and disconnecting the UPS from the mains it is
kept on, powering all the connected devices.
The shutdowns only occur when the UPS is being monitored. Are you sure
it's a battery problem? Do UPS perform further tests when they are
being polled...
2024 Nov 13
1
Eaton 5PX 3rd party batteries
...useful.
>
> I have replaced a fair number (probably around a hundred) batteries in
> other UPSes and devices (like a Fuji X-Ray machine that takes 16
> 12VDC at 22AH batteries). That's over 200VDC at a Significant current (the
> batteries claim 12V, but they are charged to over 13V).
>
> I like batteries from RaionGroup.com or batterywholesale.com.
>
> There are some other companies out there that I will never buy from again.
>
> I try to get high-rate batteries, and they are harder to find. As I
> recall, one should avoid "deep discharge" batt...
2015 Dec 28
3
Server not shutting down before power loss
Hi I hope someone can please help.
I have an Ubuntu Server running 14.04.3 LTS and using an APC ES550 UPS
connected via USB.
I've installed Nut and can see it does monitor the UPS correctly and give
the correct stats with battery percentage etc.
But on doing a "real" test and unplugging the UPS from the power supply,
after watching the battery drop slowly suddenly the server just
2024 Nov 13
5
Eaton 5PX 3rd party batteries
...g is both correct and useful.
I have replaced a fair number (probably around a hundred) batteries in
other UPSes and devices (like a Fuji X-Ray machine that takes 16
12VDC at 22AH batteries). That's over 200VDC at a Significant current (the
batteries claim 12V, but they are charged to over 13V).
I like batteries from RaionGroup.com or batterywholesale.com.
There are some other companies out there that I will never buy from again.
I try to get high-rate batteries, and they are harder to find. As I
recall, one should avoid "deep discharge" batteries for UPSes. A deep
disch...
2015 Dec 29
0
Server not shutting down before power loss
...ry, - dead easy,
Then much more important: calculate internal resistance of each battery.
Batteries go bad after some years, even on trickle charge.
Measure voltage drop when driving a load such as 1 or a few car
headlamp bulbs in parallel. Then its simply Ohms law V=IR,
If voltage drops from say 13V to 11V & if you use 1 headlamp that
uses maybe 4 amps, then 13-11 / 4 = 2/4 = 0.5 which is on high side,
you dont want higher, better 0.3 or less.
Your UPS for PC's will prob. want a lot more than 4 amps, so low
internal resistance is critical to good UPS performance.
If you decide to us...
2018 Dec 03
0
MGE EllipseMAX 1500 shuts down after a few hours
On Dec 2, 2018, at 7:55 PM, raul <raulvior.bcn at gmail.com> wrote:
>
> I have taken out the batteries and measured them with a multimeter. They put out 13V (they are rated 12V 9Ah).
What sort of load did you have in parallel with the multimeter? (This is why Wolfy mentioned the light bulb: if the battery has developed excessive internal resistance, it will show proper voltages when tested open-circuit, but will read lower with a load.)
> Putting...
2001 Jul 04
0
Question about anova/ancova
...odel is
aov(Vol~apoe*hta*Age)
where ope and hta are 2 levels factor, and Age is quantitativ data.
We observed same results concerning :
Residual
interaction apoe:hta:Age
and other outputs are different.
Does anyone have an idea ?
--
Delcroix Nicolas - GIN - CNRS UMR 6095 - CEA LRC 13V
GIP CYCERON BP.5229 14074 CAEN Cedex
tel: 02 31 47 02 79 fax: 02 31 47 02 22
Email: delcroix at cyceron.fr
-------------- next part --------------
An HTML attachment was scrubbed...
URL: https://stat.ethz.ch/pipermail/r-help/attachments/20010704/f90d325d/attachment.html
2024 Nov 27
1
Eaton 5PX 3rd party batteries
...eful.
>
> I have replaced a fair number (probably around a hundred) batteries in
> other UPSes and devices (like a Fuji X-Ray machine that takes 16
> 12VDC at 22AH batteries). That's over 200VDC at a Significant current (the
> batteries claim 12V, but they are charged to over 13V).
>
> I like batteries from RaionGroup.com or batterywholesale.com.
>
> There are some other companies out there that I will never buy from again.
>
> I try to get high-rate batteries, and they are harder to find. As I
> recall, one should avoid "deep discharge" bat...
2013 Sep 22
1
Smart-UPS staying in OB after power return
Hi Kris,
On 09/21/2013 05:11 PM, Kris Jordan wrote:
> John Morris wrote, On 9/21/2013 11:28 AM:
>> The most distressing problem is the UPS stays OB after removing and
>> reapplying utility power. When power is removed, the UPS goes OB and
>> upsmon detects the power failure no problem, reporting
>> 's0-ups0 at localhost is on battery'. But when power is
2018 Jul 31
0
Adding drivers to NUT?
...the string voltage and not the single Cell voltage (Megatec 0.06).
- About battery low and high guesstimation the formula uses these values:
batt.volt.low = 104 * batt.volt.nom / 120 (for a 12V VRLA --> 10.4V batt.volt.low)
batt.volt.high = 130 * batt.volt.nom / 120 (for a 12V VRLA --> 13V batt.volt.high).
In my opinion these values are not correct (a 12V lead acid battery can be charged up to 13.8V while discharged to 9.6V)
Instead I would suggest:
batt.volt.low = 100 * batt.volt.nom / 120 (for a 12V VRLA --> 10V batt.volt.low)
batt.volt.high = 135 * batt.volt.nom / 120 (for...
2024 Nov 12
3
Eaton 5PX 3rd party batteries
Hello,
nut recently told me that the batteries need replacing in my Eaton 5PX2200RT (ups) and 5PXEBM48RT (external battery pack). According to my notes, it has been just over 4 years since I installed them. Looking at on-line sales, these seem to use batteries in a pre-packaged plastic shell. I don't recall if that's what's in my units or not.
Do you have any experience with
2018 Aug 28
1
Fwd: Forward of moderated message
...on the list against it?
>
> > - About battery low and high guesstimation the formula uses these values:
> >
> > batt.volt.low = 104 * batt.volt.nom / 120 (for a 12V VRLA --> 10.4V batt.volt.low)
> > batt.volt.high = 130 * batt.volt.nom / 120 (for a 12V VRLA --> 13V batt.volt.high).
> > In my opinion these values are not correct (a 12V lead acid battery can be charged up to 13.8V while discharged to 9.6V)
> >
> > Instead I would suggest:
> > batt.volt.low = 100 * batt.volt.nom / 120 (for a 12V VRLA --> 10V batt.volt.low)
> >...
2015 Dec 29
2
Server not shutting down before power loss
...uch more important: calculate internal resistance of each battery.
> Batteries go bad after some years, even on trickle charge.
> Measure voltage drop when driving a load such as 1 or a few car
> headlamp bulbs in parallel. Then its simply Ohms law V=IR,
>
> If voltage drops from say 13V to 11V & if you use 1 headlamp that
> uses maybe 4 amps, then 13-11 / 4 = 2/4 = 0.5 which is on high side,
> you dont want higher, better 0.3 or less.
>
> Your UPS for PC's will prob. want a lot more than 4 amps, so low
> internal resistance is critical to good UPS performanc...
2018 Jul 26
5
Adding drivers to NUT?
Dear Daniele,
nice to meet you, I'm a collegue of Gabriele.
The problem with "blazer_usb" driver ("blazer_ser" works correctly) is related to the following commands:
- "F" and "I": when the KRAULER subdriver check these UPS answers it uses wrong constants to check the lenght of the received packets, so these commands are considered as "not
2018 Dec 02
4
MGE EllipseMAX 1500 shuts down after a few hours
> If there is no message to NUT, I would consider opening a trouble
> ticket with Eaton. It is possible that there is a known issue and/or
> a firmware upgrade.
What kind of message to NUT? In the log (syslog) there is no other
message registered. In nut.log only this appears:
> Dec 1 08:10:54 openmediavault upsd[5284]: Data for UPS [ellipsemax]
> is stale - check driver
>