2020 Jan 27
3
System with MGE UPS shuts down too early
...up). With batteries charged up to 91% the UPS supported
> the server for just 07:10 minutes and forced shutdown with 69% battery
> charge and over 20 minutes of run time...
>
> 20200125 021123 70 0.0 16 [OB] NA 0.0
> 20200125 021128 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> 20200125 021133 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> 20200125 021138 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> 20200125 021143 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> 20200125 021148 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> 20200125 021150 69 0.0 16 [FSD ALARM OB LB] NA 0.0
>
> So, it seems to me that my UPS...
2020 Jan 24
2
System with MGE UPS shuts down too early
On January 24, 2020 6:13:31 PM GMT+02:00, "Georgi D. Sotirov" <gdsotirov at gmail.com> wrote:
>OK, my UPS turned out to be older that I thought. I apparently bought
>and installed it in September 2016 (not 2017 as I initially wrote).
>That
>makes for over 3 years of work, which is over the life expectancy of
>the
>batteries,
Good batteries can last 4-5 years.
2020 Jan 27
1
Nut-upsuser Digest, Vol 175, Issue 30
...the UPS supported the server
> for
> > just 07:10 minutes and forced shutdown with 69% battery charge and over
> 20
> > minutes of run time...
> >
> > 20200125 021123 70 0.0 16 [OB] NA 0.0
> > 20200125 021128 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> > 20200125 021133 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> > 20200125 021138 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> > 20200125 021143 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> > 20200125 021148 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> > 20200125 021150 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> >
> >...
2020 Jan 27
0
System with MGE UPS shuts down too early
...ld up). With batteries charged up to 91% the UPS supported the server for
> just 07:10 minutes and forced shutdown with 69% battery charge and over 20
> minutes of run time...
>
> 20200125 021123 70 0.0 16 [OB] NA 0.0
> 20200125 021128 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> 20200125 021133 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> 20200125 021138 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> 20200125 021143 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> 20200125 021148 69 0.0 16 [FSD ALARM OB LB] NA 0.0
> 20200125 021150 69 0.0 16 [FSD ALARM OB LB] NA 0.0
>
> So, it seems to me that my UPS...
2020 Jan 25
0
System with MGE UPS shuts down too early
...power from the UPS
did hold up). With batteries charged up to 91% the UPS supported the
server for just 07:10 minutes and forced shutdown with 69% battery
charge and over 20 minutes of run time...
20200125 021123 70 0.0 16 [OB] NA 0.0
20200125 021128 69 0.0 16 [FSD ALARM OB LB] NA 0.0
20200125 021133 69 0.0 16 [FSD ALARM OB LB] NA 0.0
20200125 021138 69 0.0 16 [FSD ALARM OB LB] NA 0.0
20200125 021143 69 0.0 16 [FSD ALARM OB LB] NA 0.0
20200125 021148 69 0.0 16 [FSD ALARM OB LB] NA 0.0
20200125 021150 69 0.0 16 [FSD ALARM OB LB] NA 0.0
So, it seems to me that my UPS forces shutdown pretty rando...