search for: 0024c

Displaying 20 results from an estimated 23 matches for "0024c".

Did you mean: 0024
2009 Aug 03
1
SmartUPS-600 problem with 940-0024C cable
Hey guys, I built my own 940-0024C cable as described here: http://www.networkupstools.org/cables/940-0024C.jpg My problem is that I can't receive anything. Sending (e.g. through minicom or my own application) works fine. Nut itself is not able to detect My UPS or anything else. <snip> [myups] driver = apcsmart port =...
2007 Jul 31
1
Proposed apcsmart driver patch
G'day y'all, Here's a tiny patch set for drivers/apcsmart.c and drivers/apcsmart.h. Adds APC SmartUPS 1250 ("8QD" case) + 940-0024C recognition to apcsmart. (Unpatched apcsmart.c v1.99.8 misidentifies the SmartUPS 1250 as a "dumb" UPS.) For NUT 2.0.5+. NUT 2.0.5: Patches apply successfully. Builds successfully. Works as expected under Ubuntu 7.04. NUT 2.2: Patches apply successfully (with offset). Builds succes...
2009 Aug 14
1
Have an older Back-UPS Pro 1400(BP1400) can't get detailed info.
I just installed nut, and I it is detected but I don't get any usefull information. I have the serial cable that came with it which is a 940-0024C and I tried setting that in the driver, but no difference. What can I do to get stuff like battery voltage and such? Thanks, Brian upsc ups1 at localhost driver.name: apcsmart driver.parameter.cable: 940-0024C driver.parameter.pollinterval: 2 driver.parameter.port: /dev/ttyS0 driver.version: 2.2....
2006 Mar 02
1
Problem after reboot
...t): Success Driver failed to start (exit status=1) destiny:/usr/local/ups/bin# I see a "Success" and then a "Failed" notice. Which is which? And what has failed? And how? I tried running the driver on its own: destiny:/usr/local/ups/bin# ./apcsmart /dev/ttyS0 -x cable=940-0024C Network UPS Tools (version 2.0.2) - APC Smart protocol driver Driver version 1.99.7, command table version 2.0 getpwnam(nut): Success destiny:/usr/local/ups/bin# which points to me there's a problem with upsdrvctl somehow. Am running an APC Smart UPS V/S 1400 with a home made serial...
2006 Mar 02
1
Problem after reboot
...t): Success Driver failed to start (exit status=1) destiny:/usr/local/ups/bin# I see a "Success" and then a "Failed" notice. Which is which? And what has failed? And how? I tried running the driver on its own: destiny:/usr/local/ups/bin# ./apcsmart /dev/ttyS0 -x cable=940-0024C Network UPS Tools (version 2.0.2) - APC Smart protocol driver Driver version 1.99.7, command table version 2.0 getpwnam(nut): Success destiny:/usr/local/ups/bin# which points to me there's a problem with upsdrvctl somehow. Am running an APC Smart UPS V/S 1400 with a home made serial...
2007 Jan 30
5
initial configuration assistance
...search facility it's certainly possible I've missed what I'm looking for. Anyway, I wonder if someone can help me. I've very recently installed nut 2.0.4-r1 on a gentoo box and am in the initial stages of configuration and testing. Our APC Smart-UPS 3000 is connected with a 940-0024C serial cable, which seems to be a good one to use - I firstly removed the 940-1524C cable which happened to be dangling from the UPS. I've configured upsd.conf with [rack1ups] driver = apcsmart cable = 940-0024C port = auto desc = "Rack 1 UPS" an...
2006 Jun 19
2
Fw: Backups 300VA (BK-300C) Drivers
[BackUPS] driver = apcsmart port = /dev/ttyS0 desc "Back-UPS BK-300 @ Cap a l'orignal" > ----- Original Message ----- > From: "Charles Lepple" <clepple@gmail.com> > To: "NUT-MList" <nut-upsdev@lists.alioth.debian.org> > Sent: Monday, June 19, 2006 2:38 PM > Subject: Re: [Nut-upsdev] Backups 300VA (BK-300C) Drivers >
2006 Aug 13
2
can't get UPSDRV to see serial port
...Core 2 (3?) system that I wiped and installed SUSE 10.1 on so I'm fairly confident of the hardware. I thought I'd saved the nut configuration details before I did the reinstall, but can't find them. (D'oh!) The UPS is an APC BackUPS Pro 420. The cable is a clone of the APC 940-0024C 'smart' cable and matches the pinout on the nut site. I've created a user and group of 'ups' and set ports and permissions as outlined in the install doc. I've configged for a user of 'ups' and all the makes were generally clean, though some warnings were given...
2005 Aug 08
1
Here are CORRECT APC cable diagrams
+-----------------------------------------------------------------+ | | | Black APC 940-0024C Smart Signalling UPS Cable Wiring Diagram | | This information is verified and tested to be 100% correct. | | | +-----------------------------------------------------------------+ |...
2009 May 25
1
APC Smart UPS 900i
...nymore, I've installed NUT (Gentoo Ebuilds), but version 2.0.5 and version 2.2.2 loose connection to the UPS while version 2.4.1 and SVN version don't show any settings and there are no instant commands. The only information I can get are: driver.name: apcsmart driver.parameter.cable: 940-0024C driver.parameter.pollinterval: 2 driver.parameter.port: /dev/ttyUSB0 driver.version: 2.4.1 driver.version.internal: 2.03 input.voltage: 226.9 ups.mfr: APC ups.model: Smart-UPS ups.serial: 00016325 ups.status: OL How can I use the UPS (battery test, configuration)? Best regards, Renne
2006 Jun 19
4
Backups 300VA (BK-300C) Drivers
Hi, What driver should i use with APC BK-300C ? Michale Plourde Digicom Technologies
2013 Jan 30
3
bug report: apcsmart (WIN) 940-0024C connect fail, problem with command 'E'
Dear Ladies and Gentlemen, I have several old, yet functioning APC Smart-UPS (Model 600LS, Part AP600I, Firmware 6JI, no EEPROM, from 1991). They are not supported by Powerchute any more. I run NUT 2.6.5-4 on Windows XP SP3. I use COM1 port with cable 940-0024C. The connection fails with APC Smart protocol driver 3.0 (2.6.3-3534:3540M), APC command table version 3.0 or higher - it works with APC Smart protocol driver 2.1 (2.6.1-3057:3116M), APC command table version 2.2 or lower. Please fix the driver. Thank you. These units neither support the capabilit...
2006 Sep 04
5
Smart-UPS with SuSE 9.0/Nut
I have a Dell PE 2850 connected via 940-0024C cable to serial port on the UPS mentioned above. I've used apt-get to install nut-2.0.2-3 and attempted to configure based on the documentation. So far I'm getting the following when I try to start ups daemon: server:/etc/ups # /etc/init.d/ups start Starting service NUT: -> Starting...
2009 May 27
2
New NUT user with HP R3000XR problem
...I've already seen from the list archives that the BCMXCP driver is the correct driver for this UPS. I have already verified that I have the correct serial port and that it's working properly (I am able to communicate with an APC SU1400 on this port, using apcupsd-3.14.6 and an APC 940-0024C cable, with no problems). I have set the port permissions as per the install instructions, I've set the baud rate on the port to 9600 as per existing threads in the archives, and I'm using the HP straight-through serial cable (or is it just a serial extension cable?) that came with the...
2005 Aug 08
0
Re: Some usefull UPS information
...30602&atid=411544 Would you (or somebody else) be kind enough to make a graphic version (like the online version [1]) as I'll only use these ones for the upcoming User Manual (html version, user friendly and so on...) Thanks, Arnaud Quette --- [1] http://eu1.networkupstools.org/cables/940-0024C.jpg --- Linux / Unix Expert - MGE UPS SYSTEMS - R&D Dpt OpenSource Developer - http://arnaud.quette.free.fr/ Debian Developer - http://people.debian.org/~aquette/ ... and much more ...
2005 Jul 12
0
Smart-UPS DP missing variable
Hi, I've got a apc Smart-UPS DP 8000 XL and a 940-0024c cable., and when I launch upsdrvctl, I've got the following message : Network UPS Tools - UPS driver controller 2.0.2 Network UPS Tools (version 2.0.2) - APC Smart protocol driver Driver version 1.99.7, command table version 2.0 dstate_setflags: base variable (input.transfer.high) do...
2005 Jan 28
1
Apcupsd UPS monitoring
Having some fun with the APC monitoring daemon (apcupsd) - I've installed the Whitebox rpm and it runs OK but I cannot communicate with the UPS on ttyS0 or ttyS1. I'm using a supported cable (according to the utility's Web site). I've followed the troubleshooting tips on the app's Web site with no luck - the only bit that I can't resolve is it recommends disabling logins
2018 Nov 29
0
Problem to connect to APC SC1500
Hello, I am not able to get NUT working with a APC SC1500. The ups has only a serial port and came with a 940-0272a serial to usb cable. The cable has a fake Prolific chip in it, so only works by downgrading the driver to version 3.2. I tested a 940-0024C cable without success as well. The ups works with powerchute and apcupsd with the 940-0272a cable. Have not tested it with the other one. OS: Windows Server 2012 R2 NUT-Version: Windows-v2.6.5-6 UPS: APC SC 1500VA Driver: apcsmart upsdrvctl.exe start outputs this errors: -------------------------...
2007 Jan 12
1
Trouble connecting to apc smart 1500 via serial cable
...chine connected to the ups via serial cable. The cable is not grey, it is black, which AFAIK is one of those smart cables. But it's not working for me: # cat ups.conf [apc_chute] driver = apcsmart port = /dev/ttyS0 desc = "matrix" #cable = 940-0024C # upsdrvctl start apc_chute Network UPS Tools - UPS driver controller 2.0.4 Network UPS Tools (version 2.0.4) - APC Smart protocol driver Driver version 1.99.8, command table version 2.0 Unable to detect an APC Smart protocol UPS on port /dev/ttyS0 Check the cabling, port name or model na...
2014 Dec 23
2
NUT - Driver looks well, but connection from from client is lost or unavailable
...mage, > > ATEN USB TO RS232 UC232A (Debian found it without aditional driver) - I also tryed with RS232 to TTL but it works worse than USB converter, > > APC Smart-UPS SC450 RM (apcsmart driver documentation tell that this is new driver with only serial port), > > Home made 940-0024C cable tested by Windows PowerCute (UPS was recognised well without losing connections) > > > Instalation: > > I'm have little NUT experiance. Because of that was read that blog at the begining. > I made same installation of nut but without usb drivers at the begining. >...