> I suspect you will want the newer version for production (there was some
> issue regarding the popups when certain events happen), but let's get
this
> version working first before changing another variable.
Appreciate that. Agreed.
> For reference, I think the source code to NUT.exe is here:
> https://github.com/networkupstools/nut/blob/Windows-v2.6.5-
> 5/scripts/Windows/wininit.c
OK, we're getting closer. That little tidbit helped a lot.
Yes, that's the source to NUT.exe. And yes, NUT.exe runs the other processes
as I'd earlier suspected:
run_drivers();
run_upsd();
run_upsmon();
A quick glance through the code reveals a startup switch -N (run in non-service
mode). I did that, having stopped the service first, and then ran 'upsd
-D' as requested. This time I got an error message dialog window: "The
program can't start because LIBEAY32.dll is missing from your
computer."
BINGO. With that my nose went to the ground.
(FYI the reason we didn't get that dialog before is because Windows services
can no longer interact with the Desktop. Pre-Win8 they could, but that
capability has been removed. Now that we ran NUT.exe at the command line, we
could see it. So thanks for that source code tip.)
I poked around StartPage a bit, finding that LIBEAY32 is a component of
OpenSSL-Win32. Further searching led me here:
http://docwiki.embarcadero.com/RADStudio/Berlin/en/OpenSSL
I tried Option 2, but that site is down. So I used this instead:
http://web.archive.org/web/20160826051001/http://indy.fulgan.com/SSL/
(Wonderful thing, that WayBack Machine.)
I decided on the latest x86 version available there,
openssl-1.0.2h-i386-win32.zip. I extracted the two files, LIBEAY32.dll and
SSLEAY32.dll, to .\NUT\bin and tried upsd again. Success!
C:\Users\Admin>upsd
Network UPS Tools upsd Windows-v2.6.5-5-7-g72f380c
listening on 127.0.0.1 port 3493
Connected to UPS [ups]: usbhid-ups-ups
...and this:
C:\Users\Admin>upsmon
Network UPS Tools upsmon Windows-v2.6.5-5-7-g72f380c
UPS: ups at localhost (master) (power value 1)
Using power down flag file C:\killpower
...and this:
C:\Users\Admin>upsc ups at localhost
battery.charge: 100
battery.charge.low: 10
battery.charge.warning: 50
battery.runtime: 3420
battery.runtime.low: 120
battery.type: PbAc
battery.voltage: 27.2
battery.voltage.nominal: 24.0
device.mfr: American Power Conversion
device.model: Smart-UPS C 1000
device.serial: 3S1520X04472
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.vendorid: 051d
driver.version: Windows-v2.6.5-5-7-g72f380c
driver.version.data: APC HID 0.95
driver.version.internal: 0.38
ups.beeper.status: disabled
ups.delay.shutdown: 20
ups.firmware: UPS 10.0 / ID=1005
ups.mfr: American Power Conversion
ups.mfr.date: 2015/05/14
ups.model: Smart-UPS C 1000
ups.productid: 0003
ups.serial: 3S1520X04472
ups.status: OL
ups.timer.reboot: -1
ups.timer.shutdown: -1
ups.vendorid: 051d
So this all represents significant progress. But we're not out of the woods
yet.
When I run 'upsdrvctl start' I still get the 45-second hang and then
only this:
C:\Users\Admin>upsdrvctl start
Network UPS Tools - UPS driver controller Windows-v2.6.5-5-7-g72f380c
Network UPS Tools - Generic HID driver 0.38 (Windows-v2.6.5-5-7-g72f380c)
USB communication driver 0.32
interrupt pipe disabled (add 'pollonly' flag to 'ups.conf' to
get rid of this message)
Using subdriver: APC HID 0.95
It doesn't display the UPS model as indicated on p.21 in the PDF
documentation:
e.g. Detected EATON - Ellipse MAX 1100 [ADKK22008]
I don't know whether that's significant. I'm guessing it is.
Now here's the real problem. When I run 'NUT.exe -N' I get this:
PS C:\Users\Admin> Get-Process *ups*
Handles NPM(K) PM(K) WS(K) VM(M) CPU(s) Id ProcessName
------- ------ ----- ----- ----- ------ -- -----------
60 8 908 3896 42 0.00 3280 upsd
84 9 1344 5328 49 0.09 3348 upsmon
58 7 1696 4600 47 0.00 4916 usbhid-ups
I know that sounds good, but when I run NUT.exe as a service upsd and upsmon
don't start:
PS C:\Users\Admin> Get-Process *ups*
Handles NPM(K) PM(K) WS(K) VM(M) CPU(s) Id ProcessName
------- ------ ----- ----- ----- ------ -- -----------
58 6 1612 4484 26 0.02 3380 usbhid-ups
This also explains the errors in the Event Log when stopping the service:
Error stopping upsd (2)
Error stopping upsmon (2)
They never started in the first place, so they couldn't be stopped.
Here's the full output of NUT.exe -N:
C:\Users\Admin>nut -N
Running in non-service mode
EventLog : Starting
EventLog : Starting drivers
EventLog : Starting upsd
Network UPS Tools - UPS driver controller Windows-v2.6.5-5-7-g72f380c
Network UPS Tools upsd Windows-v2.6.5-5-7-g72f380c
Network UPS lTiosotlesn i-n gG eonne r1i2c7 .H0I.D0 .d1r ipvoerrt 03.43983
(Windows-v2.6.5-5-7-g72f380c)
USB communication driver 0.32
interrupt pipe disabled (add 'pollonly' flag to 'ups.conf' to
get rid of this message)
Using subdriver: APC HID 0.95
EventLog : Starting upsmon
EventLog : upsd - Startup successful
Network UPS Tools upsmon Windows-v2.6.5-5-7-g72f380c
UPS: ups at localhost (master) (power value 1)
Using power down flag file C:\killpower
EventLog : upsd - User upsmon at 127.0.0.1 logged into UPS [ups]
Back to the problem. I certainly wouldn't mind skipping the service
altogether and just running 'NUT.exe -N' in production, but that
suspends input and halts processing as it drops into polling mode. I can't
have a script hanging like that. I'll look into making an async call, but I
shouldn't have to be doing such things. Same goes with running the
client/server components individually.
However when do I run NUT.exe as intended, as a service, the client/server
components don't start. With no indication as to why not.
See the dilemma?
And given the absence of the discovery/announcement of the UPS model under
'upsdrvctl start' as previously discussed, I'm still not 100%
confident it's working correctly.
In fact I'm sure it's not:
C:\Users\Admin>usbhid-ups.exe -a ups -DD
...
0.063421 libusb_get_report: libusb0-dll:err [control_msg] sending control
message failed, win error: A device attached to the system is not functioning.
0.063421 Can't retrieve Report 89: Input/output error [A device attached
to the system is not functioning. ]
0.063421 Path: UPS.ff8600fd, Type: Input, ReportID: 0x89, Offset: 0, Size: 8
0.063421 libusb_get_report: libusb0-dll:err [control_msg] sending control
message failed, win error: A device attached to the system is not functioning.
0.063421 Can't retrieve Report 90: Input/output error [A device attached
to the system is not functioning. ]
0.063421 Path: UPS.ff8600fc, Type: Output, ReportID: 0x90, Offset: 0, Size: 8