Pratt Chris
2013-Jul-15 10:17 UTC
[Nut-upsuser] HP R12000/3 UPS reports status as OL DISCHRG OB
Hi. Back before Christmas Arnaud sent me a patch for the snmp-ups driver for my HP R12000/3 UPS. Unfortunately shortly after I had to take quite a lot of sick leave so wasn't able to progress it, but I'm working on it again now. I'm at the point where I can start the driver with upsdrvctl and start the daemon with upsd. When I check the UPS status though it shows as OL DISCHRG OB, which can't be right (it should just be OL). Any suggestions? Console output attached. Chris. Chris Pratt Development Infrastructure Manager Comptel Corporation 69 Suttons Business Park, Sutton Park Avenue, Reading, RG6 1AZ, UK T: +44 118 929 4176 | M: +44 7979 854 307 | F: +44 118 929 4001 Chris.Pratt at comptel.com<mailto:Chris.Pratt at comptel.com> www.comptel.com<http://www.comptel.com/> [cid:image001.gif at 01CE814C.81F3CFE0] ________________________________ Disclaimer: This message and any attachments thereto are intended solely for the addressed recipient(s) and may contain confidential information. If you are not the intended recipient, please notify the sender by reply e-mail and delete the e-mail (including any attachments thereto) without producing, distributing or retaining any copies thereof. Any review, dissemination or other use of, or taking of any action in reliance upon, this information by persons or entities other than the intended recipient(s) is prohibited. Thank you. -------------- next part -------------- An HTML attachment was scrubbed... URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20130715/0af8aaec/attachment.html> -------------- next part -------------- A non-text attachment was scrubbed... Name: image001.gif Type: image/gif Size: 4100 bytes Desc: image001.gif URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20130715/0af8aaec/attachment.gif> -------------- next part -------------- A non-text attachment was scrubbed... Name: ups_status.zip Type: application/x-zip-compressed Size: 884 bytes Desc: ups_status.zip URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20130715/0af8aaec/attachment.bin>
Charles Lepple
2013-Jul-15 12:21 UTC
[Nut-upsuser] HP R12000/3 UPS reports status as OL DISCHRG OB
On Jul 15, 2013, at 6:17 AM, Pratt Chris wrote:> Hi. > > Back before Christmas Arnaud sent me a patch for the snmp-ups driver for my HP R12000/3 UPS. Unfortunately shortly after I had to take quite a lot of sick leave so wasn?t able to progress it, but I?m working on it again now.Hi Chris, Is this the patch you are referring to? http://thread.gmane.org/gmane.comp.monitoring.nut.user/7514/focus=7546> I?m at the point where I can start the driver with upsdrvctl and start the daemon with upsd. When I check the UPS status though it shows as OL DISCHRG OB, which can?t be right (it should just be OL).Please send the debug output from starting the snmp-ups driver directly (rather than through upsdrvctl). That should explain why the driver is getting those particular status bits. Bonus points if you can show the output for both online as well as on-battery conditions, although I recognize that can be difficult if the UPS is in production use. -- Charles Lepple clepple at gmail
Pratt Chris
2013-Jul-15 13:35 UTC
[Nut-upsuser] HP R12000/3 UPS reports status as OL DISCHRG OB
Hi Charles. Debug output attached. As you suspected, this is a fairly large 3-phase UPS running a range of live kit, so removing the supply is not an option. Chris. Chris Pratt Development Infrastructure Manager T: +44 118 929 4176 | M: +44 7979 854 307 | F: +44 118 929 4001 -----Original Message----- From: Charles Lepple [mailto:clepple at gmail.com] Sent: 15 July 2013 13:21 To: Pratt Chris Cc: nut-upsuser at lists.alioth.debian.org Subject: Re: [Nut-upsuser] HP R12000/3 UPS reports status as OL DISCHRG OB On Jul 15, 2013, at 6:17 AM, Pratt Chris wrote:> Hi. > > Back before Christmas Arnaud sent me a patch for the snmp-ups driver for my HP R12000/3 UPS. Unfortunately shortly after I had to take quite a lot of sick leave so wasn't able to progress it, but I'm working on it again now.Hi Chris, Is this the patch you are referring to? http://thread.gmane.org/gmane.comp.monitoring.nut.user/7514/focus=7546> I'm at the point where I can start the driver with upsdrvctl and start the daemon with upsd. When I check the UPS status though it shows as OL DISCHRG OB, which can't be right (it should just be OL).Please send the debug output from starting the snmp-ups driver directly (rather than through upsdrvctl). That should explain why the driver is getting those particular status bits. Bonus points if you can show the output for both online as well as on-battery conditions, although I recognize that can be difficult if the UPS is in production use. -- Charles Lepple clepple at gmail Disclaimer: This message and any attachments thereto are intended solely for the addressed recipient(s) and may contain confidential information. If you are not the intended recipient, please notify the sender by reply e-mail and delete the e-mail (including any attachments thereto) without producing, distributing or retaining any copies thereof. Any review, dissemination or other use of, or taking of any action in reliance upon, this information by persons or entities other than the intended recipient(s) is prohibited. Thank you.
Pratt Chris
2013-Jul-16 08:42 UTC
[Nut-upsuser] HP R12000/3 UPS reports status as OL DISCHRG OB
Sorry about that! Chris. Chris Pratt Development Infrastructure Manager T: +44 118 929 4176 | M: +44 7979 854 307 | F: +44 118 929 4001 -----Original Message----- From: Charles Lepple [mailto:clepple at gmail.com] Sent: 16 July 2013 00:32 To: Pratt Chris Subject: Re: [Nut-upsuser] HP R12000/3 UPS reports status as OL DISCHRG OB On Jul 15, 2013, at 9:35 AM, Pratt Chris wrote:> Debug output attached.Sorry, didn't appear to be attached. -- Charles Lepple clepple at gmail Disclaimer: This message and any attachments thereto are intended solely for the addressed recipient(s) and may contain confidential information. If you are not the intended recipient, please notify the sender by reply e-mail and delete the e-mail (including any attachments thereto) without producing, distributing or retaining any copies thereof. Any review, dissemination or other use of, or taking of any action in reliance upon, this information by persons or entities other than the intended recipient(s) is prohibited. Thank you. -------------- next part -------------- A non-text attachment was scrubbed... Name: debug_output.zip Type: application/x-zip-compressed Size: 11530 bytes Desc: debug_output.zip URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20130716/47226292/attachment.bin>
Charles Lepple
2013-Jul-17 02:25 UTC
[Nut-upsuser] HP R12000/3 UPS reports status as OL DISCHRG OB
Here's the first update of ups.status: 0.102449 getting data: ups.status (.1.3.6.1.4.1.232.165.3.4.5.0) 0.102546 su_ups_get: ups.status .1.3.6.1.4.1.232.165.3.4.5.0 0.102646 nut_snmp_get(.1.3.6.1.4.1.232.165.3.4.5.0) 0.104539 SNMP UPS driver : entering su_status_set() 0.104641 su_find_infoval: found OL (value: 3) 0.104730 => value: 3 0.104823 getting data: ups.status (.1.3.6.1.4.1.232.165.3.2.5.0) 0.104919 su_ups_get: ups.status .1.3.6.1.4.1.232.165.3.2.5.0 0.105028 nut_snmp_get(.1.3.6.1.4.1.232.165.3.2.5.0) 0.107134 SNMP UPS driver : entering su_status_set() 0.107231 su_find_infoval: found DISCHRG (value: 2) 0.107319 => value: 2 0.107412 getting data: ups.status (.1.3.6.1.4.1.232.165.3.7.3.0) 0.107507 su_ups_get: ups.status .1.3.6.1.4.1.232.165.3.7.3.0 0.107616 nut_snmp_get(.1.3.6.1.4.1.232.165.3.7.3.0) 0.109529 SNMP UPS driver : entering su_status_set() 0.109630 su_find_infoval: found OB (value: 1) 0.109720 => value: 1 The first one (...3.4.5.0) is labeled in the driver as CPQPOWER_OID_POWER_STATUS. I checked around for this, and didn't find a good definition, but that seems to match the OL state. The second one seems specific to the battery: static info_lkp_t cpqpower_battery_abm_status[] = { { 1, "CHRG" }, { 2, "DISCHRG" }, /* { 3, "Floating" }, */ /* { 4, "Resting" }, */ /* { 5, "Unknown" }, */ { 0, "NULL" } } ; I could see the battery monitoring circuit discharging the battery occasionally for maintenance, but is there a separate front-panel indicator for this mode? The third one is CPQPOWER_OID_ALARM_OB. This definitely doesn't make sense, since things with "alarm" in the name are usually pretty direct. The big question in my mind is, where did the NUT definitions come from? Did your UPS come with a CD that might contain a SNMP MIB definition file? Or is there an area on the HP support site? (All I saw was a firmware update .EXE)
Possibly Parallel Threads
- HP R12000/3 UPS reports status as OL DISCHRG OB
- HP R12000/3 UPS reports status as OL DISCHRG OB
- HP R12000/3 UPS reports status as OL DISCHRG OB
- NUT v2.6.4 with HP AF401A won't start
- snmp-ups sends status "OL OB" on HP R3000 UPS with AF465A management card [UPDATE]