Hello, My APC Ups uses nut to manage all systems connected to it. But if online power failed until it shutdown, it not restart automatically after the power returned. It stay down until i restart it. When i execute the command: # upsc siUps1 it output me this: battery.alarm.threshold: L battery.charge: 018.0 battery.charge.restart: 15 battery.date: 03/31/07 battery.runtime: 120 battery.runtime.low: 120 battery.voltage: 26.77 battery.voltage.nominal: 024 driver.name: apcsmart driver.parameter.pollinterval: 2 driver.parameter.port: /dev/ttyS0 driver.parameter.sdtype: 0 driver.version: 2.2.0- driver.version.internal: 1.99.8 input.frequency: 51.00 input.quality: FF input.sensitivity: H input.transfer.high: 253 input.transfer.low: 208 input.transfer.reason: S input.voltage: 226.0 input.voltage.maximum: 226.0 input.voltage.minimum: 222.0 output.voltage: 224.0 output.voltage.nominal: 230 ups.delay.shutdown: 300 ups.delay.start: 000 ups.firmware: 738.2.I ups.id: UPS_IDEN ups.load: 033.1 ups.mfr: APC ups.mfr.date: 03/31/07 ups.model: Smart-UPS SC1500 ups.serial: 5S0713T66466 ups.status: OL ups.test.interval: 1209600 ups.test.result: NO What can be my problem? Battery is concerned? Please Help. -------------- next part -------------- An HTML attachment was scrubbed... URL: http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20080418/cafcd3ee/attachment.htm
Hi, Edj? wrote:> Hello, > My APC Ups uses nut to manage all systems connected to it. But if > online power failed until it shutdown, it not restart automatically > after the power returned. It stay down until i restart it.Can you clarify this please? Do you mean that the UPS is shut down as a result of power failure and the UPS does not restart automatically after the power has returned? Or are you referring to a server? Thanks, Jon> When i execute the command: # upsc siUps1 > it output me this: > battery.alarm.threshold: L > battery.charge: 018.0 > battery.charge.restart: 15 > battery.date: 03/31/07 > battery.runtime: 120 > battery.runtime.low: 120 > battery.voltage: 26.77 > battery.voltage.nominal: 024 > driver.name: apcsmart > driver.parameter.pollinterval: 2 > driver.parameter.port: /dev/ttyS0 > driver.parameter.sdtype: 0 > driver.version: 2.2.0- > driver.version.internal: 1.99.8 > input.frequency: 51.00 > input.quality: FF > input.sensitivity: H > input.transfer.high: 253 > input.transfer.low: 208 > input.transfer.reason: S > input.voltage: 226.0 > input.voltage.maximum: 226.0 > input.voltage.minimum: 222.0 > output.voltage: 224.0 > output.voltage.nominal: 230 > ups.delay.shutdown: 300 > ups.delay.start: 000 > ups.firmware: 738.2.I > ups.id: UPS_IDEN > ups.load: 033.1 > ups.mfr: APC > ups.mfr.date: 03/31/07 > ups.model: Smart-UPS SC1500 > ups.serial: 5S0713T66466 > ups.status: OL > ups.test.interval: 1209600 > ups.test.result: NO > What can be my problem? Battery is concerned? Please Help. > > ------------------------------------------------------------------------ > > _______________________________________________ > Nut-upsuser mailing list > Nut-upsuser at lists.alioth.debian.org > http://lists.alioth.debian.org/mailman/listinfo/nut-upsuser-- ---------------------------- Jon Clark Scientific Officer Dept. of Applied Mathematics University of Sheffield Sheffield, S3 7RH, UK ----------------------------
Arjen de Korte
2008-Apr-18 11:52 UTC
[Nut-upsuser] My APC ups shutdown but doesn't start again
> My APC Ups uses nut to manage all systems connected to it. But if online > power failed until it shutdown, it not restart automatically after the > power returned. It stay down until i restart it.The shutdown command for the 'newhidups' and 'usbhid-ups' drivers up to (and including) nut-2.2.0 is broken for all vendors except MGE. You'll need to upgrade to nut-2.2.1 or newer if you need your systems to return after a power failure automatically. There is no workaround for this. We're sorry for the inconvenience. Best regards, Arjen -- Eindhoven - The Netherlands Key fingerprint - 66 4E 03 2C 9D B5 CB 9B 7A FE 7E C1 EE 88 BC 57