[Nut-upsuser] What are some effective power status solutions?
Greetings NUT users, I am looking for a solution to monitor the power OUTSIDE my datacenter. (The on/blackout status of main building power). My small datacenter is covered by a UPS, an older Liebert 18Kva unit with no environmental or status monitoring outside of the LCD console and audible alarm. The Liebert UPS is backed by a 35KW diesel generator which usually kicks on within 10 seconds of a power outage. The generator has a ~36hour runtime. (Air conditioning of the datacenter is also generator backed). This solution is great for the needs of the datacenter for most conditions, but I still would like to know when power in my building goes out so I know if the outage is long enough for me to need to come on site shut non-critical systems down or monitor generator fuel levels. What I am looking to accomplish is setting up a cheap pollable UPS that can report online or no incoming power status. Which will then be used by Nagios to send off an alert. The only load on the UPS will be a clock or something very low power like an LED light. Yes, it is a hack... but it's a simple hack, and they have saved me more times than not. What would be the cheapest UPS unit that NUT, or other apps can poll to check good vs no power status? I was looking at the PowerWare 3105, though it's a beta driver. For $40, it seems like it would be a good starting point. If the solution becomes too expensive, Ill just end up putting a longlife lightbulb on building power and pointing a webcam at it. Anyone have any sample output of this or other UPS unit? Or any other ideas for this sort of monitoring? Thanks, Jarett Kulm eMail: jkulm@planalytics.com -------------- next part -------------- An HTML attachment was scrubbed... URL: http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20050912/09735fe5/attachment.html
Arjen de Korte
2005-Sep-12 14:46 UTC
[Nut-upsuser] What are some effective power status solutions?
> I am looking for a solution to monitor the power OUTSIDE my datacenter. > (The on/blackout status of main building power).[...]> Anyone have any sample output of this or other UPS unit? Or any other > ideas for this sort of monitoring?Since you only need a status signal and not a full UPS function, I would hook up to a relay with a 110VAC coil (or 230VAC, whatever you have in your place of the world) and use that to interface to a serial port. Wire the contacts such that it mimics one of the many 'dumb' serial interface UPSes and off you go. Regards, Arjen