Hi All! I have a traoble whith my ups, - megatec driver can not calculating % of charging and voltage on battery: # uname -a FreeBSD backup.*.*.* 8.1-RELEASE FreeBSD 8.1-RELEASE #0: Wed Sep 22 12:25:01 EEST 2010 ups.conf [Powercom] driver = megatec port = /dev/cuau0 #battvolts=12:24 desc = "powercom sxl-1000A" # ./nut start Network UPS Tools - UPS driver controller 2.4.1 Network UPS Tools - Megatec protocol driver 1.6 (2.4.1) Megatec protocol UPS detected. Cannot calculate charge percentage for this UPS. <================================ !!! Starting nut. Network UPS Tools upsd 2.4.1 listening on 172.16.0.220 port 3493 listening on 127.0.0.1 port 3493 Connected to UPS [Powercom]: megatec-Powercom Broadcast Message from ********** (no tty) at 18:42 EET... Communications with UPS Powercom at localhost established # upsc Powercom at localhost battery.voltage: 2.30 <================================ !!! driver.name: megatec driver.parameter.pollinterval: 2 driver.parameter.port: /dev/cuau0 driver.version: 2.4.1 driver.version.internal: 1.6 input.frequency: 50.0 input.voltage: 231.0 input.voltage.fault: 231.0 input.voltage.maximum: 231.0 input.voltage.minimum: 228.0 output.voltage: 231.0 ups.beeper.status: disabled ups.delay.shutdown: 0 ups.delay.start: 2 ups.load: 74.0 ups.mfr: unknown ups.model: unknown ups.serial: unknown ups.status: OL ups.type: online Plise help! Sorry 4 my english! best regards!
Citeren ahouse-support <support op ahouse.mine.nu>:> I have a traoble whith my ups, - megatec driver can not calculating > % of charging and voltage on battery:You UPS doesn't report the battery charge, so that's not unusual. The megatec driver will guesstimate the battery charge based on the battery voltage, but this is very unreliable. [...]> # ./nut start > Network UPS Tools - UPS driver controller 2.4.1 > Network UPS Tools - Megatec protocol driver 1.6 (2.4.1) > Megatec protocol UPS detected. > Cannot calculate charge percentage for this UPS. > <================================ !!![...]> # upsc Powercom op localhost > battery.voltage: 2.30 <================================ !!!See 'man 8 megatec' for answers how to fix the above two problems. Better yet, change to the 'blazer_ser' driver instead, which uses a better way to determine state of charge (based on a couple of parameters you need to provide). Make sure to read 'man 8 blazer' before returning here for help. Best regards, Arjen -- Please keep list traffic on the list (off-list replies will be rejected)