Displaying 20 results from an estimated 100 matches similar to: "Confusion on Primary and Secondary"
2025 Mar 30
1
Confusion on Primary and Secondary
Hello and welcome,
Can you please point to any online "PiNUT" docs, if that is a project
name? I did not find anything that looked specific to the key word.
In any case, the "primary" role of upsmon applies to any UPS that it is
connected to and can directly manage, so in case of a power outage it tells
everyone else (secondaries) to shut down first, and then runs the UPS
2015 Sep 14
2
stale/dead ups logic
hi:
when testing nut in our environment, we found something that nut
maybe tune for "stale/dead ups" situation. currently the "dead ups"
are assume alive(eg: host shutdown unnecessary), unless it is in the
"OB" state before going to stale.
our environment (ServerA + ServerB forms a cluster):
ServerA-> usb to UPSA -> two PS power by UPSA and UPSB
2012 Sep 11
1
Back UPS ES and data stale with disconnected device
Hello NUT Team!
I continue playing with NUT for Windows and USBHID-UPS driver I've got from Frederic to fix "Data Stale" problem.
It seems there is something wrong when Network UPS Tools service is starting with disconnected USB cable. UPSMON is writing "Data Stale" to output and continue do it infinitely, even the cable is connected back. Here is a short log:
Network
2012 Sep 13
2
Early shutdowns and 2.6.5-1 package for Windows
Hello NUT Team!
I am testing the early shutdowns in NUT 2.6.5-1 package for Windows (Windows
7 x64).
My configuration files:
upsmon.conf
RUN_AS_USER upsmon
MONITOR upsa at 192.168.10.200 1 upsmon pass master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
NOTIFYCMD "upssched.exe"
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG
2012 Aug 30
1
Data stale and Back UPS ES
Hello!
I tried NUT 2.6.5-1 (Windows port) with my APC Back UPS ES. It seems I have
configured NUT properly, nut-scanner found my UPS:
[nutdev1]
driver = "usbhid-ups"
port = "auto"
vendorid = "051D"
productid = "0002"
product = "Back-UPS ES 525 FW:851.t3.I USB FW:t3"
serial = "8B0745R23575
2020 Aug 16
1
UPS Reboots when Pi Reboots!
OS: Raspbian Lite 4.19 (Linux 5.4.51-v7l+ armv7l)
NUT version: 2.7.4
Install Method: Package (apt-get)
Device Name: CyberPower CP1500PFCLCD, connected via USB
Problem: This is a brand-new installation; the only step I've taken is my
initial edit of /etc/nut/ups.conf (which I'll post below). I started the
driver and after doing so issued a reboot command to my Raspberry Pi (sudo
reboot).
2012 Sep 19
1
New intermediate Windows binaries release - 2.6.5-3
?Hello,
There is a new intermediate Windows binaries release available at :
http://www.networkupstools.org/package/windows/NUT-Installer-2.6.5-3.msi
This fixes a regression about stopping the NUT service.
Feedback is highly appreciated.
Regards,
Fred
--
Eaton Opensource Team - http://opensource.eaton.com
-----------------------------
-----------------------------
2014 May 27
1
Masterguard UPS A3000
Hi,
I'm trying to talk to an old Masterguard UPS A3000 so I can determine
current load and status etc, to determine the best replacement options.
After a fair amount of google fu, and attempting different things, this
is where I have ended up.
First, environment:
OS: Linux (Debian Stable)
NUT Version: 2.7.2-1 (Debian unstable package)
UPS details (on the rear lable):
Manufacturer:
2014 Jan 21
2
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote:
> MONITOR UPS_251 at localhost 2 monmaster password master
> MONITOR UPS_252 at localhost 2 monmaster password master
I think the "2"s here should be "1".
"powervalue is an integer representing the number of power supplies that the UPS feeds *on this system*."
So if UPS_251 is connected to one power supply on
2014 Jan 21
0
Shutdown when both (all) UPS on battery / low battery
> What do your configuration files look like? Setting MINSUPPLIES to 2 should work. You can run upsmon with a debug level of 3 or greater, and it will print the current and minimum "power value", which is what determines when to shut down.
>
> Also, if you don't want to wait for both UPSes to drain to the low battery state, you can set up a pair of dummy-ups drivers. I'm
2024 Nov 19
1
New UPS ABB
Hi Team
While i;m searching on the internet about UPS SNMP monitoring , I found
this NUT server. Thank God, But sad news is that my UPS is not listed in
the compatibility list.
But I download NUT server on my ubuntu node and just discover it
sudo /lib/nut/snmp-ups -DD -a ups
unfortunately got the below error message.
228.253598 [D2] Testing ups.model using OID 1.3.6.1.2.1.33.1.1.2.0
2014 Jan 21
3
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 3:16 AM, Rafa? Oleszek wrote:
> I would like to mention that MINSUPPLIES manipulation doesn't work. My nut version is : 2.2.2-4 (RHEL 5)
What do your configuration files look like? Setting MINSUPPLIES to 2 should work. You can run upsmon with a debug level of 3 or greater, and it will print the current and minimum "power value", which is what determines
2016 Oct 25
2
setting up CYBERPOWER CP1500PFCLCD
Hi,
Another beginner question. I spend hours trying to find the solution for
how to configure winnut properly but I' struggling to make it work. I want
my QNAP NAS TS-231 to work as a master and send signal to the PC to shut it
down during power outage. I configured QNAP properly (like this:
http://geekbeat.tv/qnap-adding-external-devices-qnap), but I don't know
what to do next.
I work
2014 Jan 21
2
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote:
> It does not matter what value I'll put in MONITOR and MINSUPPLIES line. NUT not waiting for both UPS to start timer.
Correct. You can think of upssched as operating on raw UPS status, rather than the calculated powervalue that upsmon uses to decide when to shut down.
--
Charles Lepple
clepple at gmail
2006 Feb 07
1
MGE Pulsar STS
Hello,
I'm trying to communicate with a MGE Pulsar STS 16 using nut
under Linux, but I've had no luck so far. I haven't saw it
supported in the doc, so if there's anything I can try...
Thanks,
Arnaud.
--
Perso: http://launay.org/blog/
H?bergement: http://www.nocworld.com/
2016 May 18
1
Monitoring Only
Hi,
What shoud I do in order to configure NUT to perform only monitoring, I
mean to not shutdown anything at all?
Thanks in advance!
--
--
Sergio Belkin
LPIC-2 Certified - http://www.lpi.org
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20160518/23c72ff1/attachment.html>
2014 Jan 23
0
Shutdown when both (all) UPS on battery / low battery
> On Jan 21, 2014, at 9:24 AM, Rafal Oleszek wrote:
>
>> I tried all options:
>> 1,2
>> and in MINSUPPLIES: 1,2,3,4
>> still didn't work.
>
> My mistake - I gave you the wrong advice before. For MINSUPPLIES, I'm used
> to either a 1:1 UPS-to-server ratio, or 2:1 where the server can run with
> either power supply unpowered.
>
> I just tried
2008 May 01
1
NUT for laptop
HI all
How to setup nut to use and monitor laptop battery on linux?
(/proc/acpi/battery/BAT0/state)
Emard
2014 Jan 23
2
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 9:24 AM, Rafal Oleszek wrote:
> I tried all options:
> 1,2
> and in MINSUPPLIES: 1,2,3,4
> still didn't work.
My mistake - I gave you the wrong advice before. For MINSUPPLIES, I'm used to either a 1:1 UPS-to-server ratio, or 2:1 where the server can run with either power supply unpowered.
I just tried this in upsmon.conf:
MONITOR dummy1 1 monuser
2006 Nov 07
6
Sweex 1000VA UPS
Hi,
I'm trying to get a sweex ups working with nut on debian sarge.
This one:
http://www.sweex.com/producten.php?lang=1&%20sectie=&item=59&artikel=95
It's shipped with UPSmart and according to the compatibility list it should
work with the
genericups upstype=7 driver. But it doesn't.
I get:
mybox:/etc/nut# /etc/init.d/nut start