similar to: battery.voltage Powercom Macan MRT-3000

Displaying 20 results from an estimated 1000 matches similar to: "battery.voltage Powercom Macan MRT-3000"

2023 Jan 13
1
battery.voltage Powercom Macan MRT-3000
I suppose, this approach may be apply to some other data from that UPS. I could check another values and ask powercom support for other data items to explain interpretation, if it will help. On 13.01.23 14:22, Greg Troxel wrote: > That makes sense to me. The field needs to be split into bytes. The > low byte is the integer part of voltags, and the high part is units of > 10 mV. And
2023 Jan 13
1
battery.voltage Powercom Macan MRT-3000
That makes sense to me. The field needs to be split into bytes. The low byte is the integer part of voltags, and the high part is units of 10 mV. And this is per cell. Probably the unit is measuring the total and then dividing by 36. But volts per cell will have the same interpretation for varying cell counts, so it's a nice representation.
2013 Apr 28
0
PowerCOM BNT-1000AP HID instant commands patch
Hello, Got PowerCOM BNT-1000AP, usb id 0d9f:00a6, firmware FW4.A6 nut 2.4.3 on debian stable shows only two instant commands: beeper.toggle - Toggle the UPS beeper -- not working test.battery.start.quick - Start a quick battery test -- works ok. No load and shutdown commands. Trying svn trunk version, with the same results. Debug output shows the problem: 0.035558
2008 Jan 22
1
Duncan's MRT: limitations to qtukey() function?
Dear all, I'm using R to perform multiple comparison testing on agriculture genotype trials. To perform the Duncan's MRT, I use the qtukey() function with the following syntax: qtukey(p = ((1 - 0.05) ^ (pos - 1)), nmeans = pos, df = ni) I experience a strange behaviour when the number of means in the trial and the number of residual degrees of freedom (ni) becomes high
2015 Mar 13
0
Problems with NUT 2.7.2 on CentOS 7 and using the Mini-Box OpenUPS
[please keep the list CC'd. thanks!] On Mar 13, 2015, at 10:53 AM, Philip Taylor <philip at kelsotowers.co.uk> wrote: > I?ve set up UPSMON to simply execute ?shutdown -h now? and my system shuts down when I type ?upsmon -c fsd?. The problem is that the OpenUPS doesn?t shut down as a result; and therefore when the power comes back on, unless the battery has totally run out, the
2017 May 12
0
APC Back-UPS XS 1500G says "No battery"
On May 11, 2017, at 1:51 PM, Jesse Molina <jmolina at swoncology.net> wrote: > > I suspect this is a driver problem because while NUT claims the battery isn't plugged in, it's giving me battery runtime/charge info. Both can't be valid at the same time. > > I am at a remote location from the computer and UPS, so I can't physically go over and check. I asked a
2006 Jan 27
0
[PATCH] fentonups patch to make it work with some powercom ups's
Hi list here is the patch to make fentonups recognize some PowerCOM's UPS's, and to setup terminal lines for them (at least for SMK-1500a) as powercom's original upsmon do. fentonups -x powercom works correctly with SMK-1500a (it screamed ''Communications with UPS lost - check cabling' or 'Short read during UPS id sequence' without this patch). Sorry for
2017 Apr 26
0
Powercom BNT-2000AP(USB)
Hello all! Some days ago we received new UPS?Powercom BNT-2000AP with USB interface to replace an old staff and I've spent three last days trying to connect it with NUT. I have a FreeBSD 8.4 box with NUT 2.7.2. # dmesg|grep -i powercom ugen0.3: <POWERCOM Co.,LTD> at usbus0 uhid0: <POWERCOM Co.,LTD HID UPS Battery, class 0/0, rev 1.10/0.01, addr 3> on usbus0 uhid0: <POWERCOM
2014 May 29
0
Resetting replace battery status on Pulsar 1500
On May 28, 2014, at 8:59 PM, Daniel O'Connor wrote: > On 28 May 2014, at 21:59, Charles Lepple <clepple at gmail.com> wrote: >>> What would log it? >> >> The driver. > > OK. > >>> I could try running the driver with debugging and see if that shows anything of interest. >> >> That should help. Unfortunately for non-debug
2013 May 01
1
Powercom BNT-1500AP serial config
Hey all, Finally got around to hooking up my Powercom BNT-1500AP to nut. It's the old serial interface. Connects okay and gets most information, but a couple of data are way off. Any config recommendations or upgrade recommended? I've played with config a little, but no hits yet. Details: NUT version 2.4.3 ups.conf: [ups] driver = powercom port = /dev/ttyS0
2009 Sep 19
1
Powercom 600AP USB support
Hi, I know it's been a topic many times here, but I've searched the archives, googled for days, and I simply don't believe, that there is still no solution to this. I'm using a PowerCom BNT-600AP ups with usb port. I've downloaded the latest version from svn, compiled it, and tried to use it: * megatec(_usb) - no luck, it did not find the UPS (I?ve read in this list, that
2017 Apr 30
0
Powercom BNT-2000AP(USB)
On April 28, 2017 9:11:59 AM GMT+03:00, "????????? ?????????" <vtk-alexb at mail.ru> wrote: >Hello all! > >Some days ago we received new UPS?Powercom BNT-2000AP with USB >interface to replace an old staff and I've spent four last days trying >to connect it with NUT. I have a FreeBSD 8.4 box with NUT 2.7.2. > ># dmesg|grep -i powercom >ugen0.3:
2007 Sep 04
1
powercom-usb drriver complie?
Hi, Arjen; I am new to linux and not sure how to create the PowerCom-usb driver. So could you please compile powercom-usb file for me. I am happy to test it out with the USB PowerCom Ups. Thanks, Paul MCSE/MCSA/MCP ------------------------------ Message: 2 Date: Mon, 03 Sep 2007 11:13:32 +0200 From: Arjen de Korte <nut+users at de-korte.org> Subject: Re: [Nut-upsuser] Powercom USB UPS is
2012 Sep 19
2
Unable to disable beeper on Powercom Imperial IMP-525AP
Hi ALL, Powercom Imperial IMP-525AP seems to be fully compatible with NUT. Unfortunately, I can not disable beeper. upscmd -u {NUT_USER} -p {NUT_PASSWORD} powercom beeper.toggle returns *OK*, however, ups.beeper.status=enabled Thank you, Sergey ========== Additional info: 1) $ upsc powercom battery.charge: 100 battery.charge.low: 10 battery.charge.warning: 30 battery.date: 2010/01/01
2010 Dec 02
1
Powercom SXL-1000A-LCD
Hi All! I have a traoble whith my ups, - megatec driver can not calculating % of charging and voltage on battery: # uname -a FreeBSD backup.*.*.* 8.1-RELEASE FreeBSD 8.1-RELEASE #0: Wed Sep 22 12:25:01 EEST 2010 ups.conf [Powercom] driver = megatec port = /dev/cuau0 #battvolts=12:24 desc = "powercom sxl-1000A" # ./nut start Network UPS Tools - UPS driver controller 2.4.1
2008 Oct 21
1
Powercom Imperial/Black Knight USB support for NUT
2008/10/18 Sergiy Yegorov <prapor at unixzone.org.ua>: > Dear Arnaud! Hi Sergiy and Alexey, > Please, check this patch. It adds USB-attached Powercom UPS Imperial & > Black Knight series. Originaly code is writed by Kirill Burdin > (burdin at post.ru) for Imperial UPS`es. > I`m just sysadmin without enought C programming > skills, so I adapted it to nut-2.2.2-6
2010 Jul 02
0
Powercom driver patch
Hello everybody! I'm trying to use nut-2.4.1 with brand new UPS Powercom Imperial IMD-825AP USB. I've faced a problem that the driver powercom despite specifying type=IMP automatically re-detects the UPS as "KIN" and then interprets raw data incorrectly. The same problem was reported by other Powercom users on the official support forum ( http://forum.pcm.ru ). I suppose the
2017 Aug 10
2
New powercom device?
In a separate discussion, on 6/26/17 4:04 AM, Arnaud Quette wrote: > Hi > > If you're sure it's a HID device, add an entry in drivers/powercom-hid.c > { USB_DEVICE(POWERCOM_VENDORID, 0x0002), NULL }, > > Then autogen.sh + configure... > Please also report back so that I can update the code > > Cheers > Arno Thanks! I don't *know* whether or not
2006 Apr 21
1
Powercom BNT-1200AP
Hello I have UPS Powercom Black Knight Pro 1200 (BNT-1200AP) I try to use nut, but powercom driver not understand my model Ok, i try to use type KIN1500AP and it's work But powercom driver can't set UPS's shutdown delay time Also i have powercom's original program (upsmon), and this program can do it What can i do for help to add this function to nut's powercom driver? For
2012 Jul 21
0
Re Powercom Vanguard driver for nut
Hi Have been trying to get nut and Powercom Vanguard 2000 ups communicating ? in the /lib/udev/rules.d/52-nut-usbups.rules file we have this entry #? PowerCOM VGD - Vanguard? - usbhid-ups ATTR{idVendor}=="0d9f", ATTR{idProduct}=="0004", MODE="664", GROUP="nut" ? In the /etc/ups/ups.conf [UPS] ??????? driver = usbhid-ups ??????? port =