similar to: Request to Document obscure SERIAL flowcontrol setting

Displaying 20 results from an estimated 2000 matches similar to: "Request to Document obscure SERIAL flowcontrol setting"

2008 Mar 14
0
Sola 305 with INT-0051 cable
Hello again, I have a Sola 305 (aka Powerware 3110) here connected via a serial INT-0051 cable which I am trying to get working with nut. The driver.list file indicates that nut supports the Sola 305 when connected via the INT-0025C cable using the genericups driver with upstype set to 7 but it does not mention the INT-0051. I was able to use the "Basic CheckUPS II" utility provided
2005 Aug 08
1
Here are CORRECT APC cable diagrams
+-----------------------------------------------------------------+ | | | Black APC 940-0024C Smart Signalling UPS Cable Wiring Diagram | | This information is verified and tested to be 100% correct. | | |
2015 Nov 21
2
Contact-closure UPS
>> On Nov 21, 2015, at 2:43 AM, R?bert SZAKSZ <robert at szaksz.eu> wrote: >> >> I mesured it and on DC and it shows 0 V (zero V). >> May be the information (pls. see attachment) that UPS PIN1 should bee keept HI is mandatory. Should I connect it to PC PIN4 DTR? > >Certainly possible. blazer_ser and nutdrv_qx should set DTR high and RTS low by default, but
2006 Jul 11
1
Re: [nut-commits] svn commit r446 - in branches/Testing: . drivers man
> +22 = Gamatronic UPSs with alarm interface > + [CP=RTS] [OL=CTS] [LB=\-DCD] [SD=DTR] > + > +22 = CyberPower SL seriess > + [CP=RTS] [OL=CTS] [LB=\-CAR] [SD=DTR] > + > + This part of the patch is no good. While TIOCM_CAR is equivalent to TIOCM_CD (at least in some implementations) CAR certainly isn't handled the same as DCD by genericups. It won't be
2005 Oct 03
1
CyberPower SL-series
This code, added to drivers/genericups.h, supports the CyberPower SL series UPSes. I've tested with my 725SL - the online/on battery transition, and low battery status, and finally the shutdown signal all work as expected. *** genericups.h.orig Sun Nov 2 16:54:24 2003 --- genericups.h Mon Oct 3 13:49:00 2005 *************** *** 220,225 **** --- 220,234 ---- TIOCM_ST
2005 Feb 20
0
Re: Asterisk-Users Digest, Vol 7, Issue 260
> From: "James Bean" <james@hdcs.com.au> > Has anyone every setup an external open/close relay, off say a serial > interface, and have an extension trigger the relay? The following will do the trick. Just add a 5vdc solid state relay ('cause you can't sink too much current out of the RS232C port). Substitute "2", "4" or "6" in the
2006 Feb 04
1
Old Contact UPS Info
I tried to find a search button for the mailing list but could not. So rtfm me with the link please. If not.. I have an old Deltec PowerRite Pro 2 UPS which has a 9 pin serial cable. By trial and error Im pretty sure I found LB = DCD, but can not get the combination for OB / OL. No matter what I do I get the results below. driver.name: genericups driver.parameter.CP: CTS driver.parameter.LB:
2010 Jun 15
0
mercury smart1200 pro serial powerdown problem
Hello * Trying to get above serial UPS to work gives my some troubles. With upstype=21 [CP=RTS] [OL=CTS] [LB=-DCD] [SD=RTS+DTR] and/or upstype=4 [CP=RTS] [OL=CTS] [LB=-DCD] [SD=-RTS] I do get OL OB LB ok, but shutting down the UPS does not work. Direct call w/ command genericups ... -k and from lowbatt/ initscripts doesnt do. The UPS claims to be capable of and the software shipped (RUPS2000)
2005 Nov 30
4
ups.conf configure
Hello, I got this information from the manufacturer of my ups Kobian/Mercury and were tested wtih powstatd on Linux (Works OK). Now i want to configure it with NUT and i didn't have any luck (it always says OB) Initiliasation for monitoring: RTS = 1 (High) Main power fail: CTS = 0 (Low) Batter low: DCD = 0 (Low) Kill UPS: DTR = 0 (Low) How would the ups.conf look like? Reagards, Lep
2015 Nov 16
2
Contact-closure UPS
Hello, I have one UPS Infosec XP Pro 2500 RM and it works with windows sw RUPS2000. Now I want to install this UPS as virtual server on vmware ESXi vMA - (SUSE SLES 11SP2 linux). On this linux I have NUT 2.6.0 and I stopped now with configuration of genericups driver. Working cable (direct cable pin1-pin1 ... pin9-pin9) connection on Windows: PIN | PC | UPS
2015 Nov 16
0
Contact-closure UPS
[please use reply-all when responding - the list does not modify the reply-to header.] > On Nov 16, 2015, at 8:24 AM, R?bert SZAKSZ <robert at szaksz.eu> wrote: > > Hello, > > I have one UPS Infosec XP Pro 2500 RM and it works with windows sw RUPS2000. > Now I want to install this UPS as virtual server on vmware ESXi vMA - (SUSE SLES 11SP2 linux). > On this linux I
2015 Nov 21
0
Contact-closure UPS
> On Nov 21, 2015, at 2:43 AM, R?bert SZAKSZ <robert at szaksz.eu> wrote: > > I mesured it and on DC and it shows 0 V (zero V). > May be the information (pls. see attachment) that UPS PIN1 should bee keept HI is mandatory. Should I connect it to PC PIN4 DTR? Certainly possible. blazer_ser and nutdrv_qx should set DTR high and RTS low by default, but that can be adjusted. >
2005 Nov 03
1
Tripplite smart1500 ups
Hello, Does anyone know the settings to get this UPS talking to nut? I'm trying to get it working over the serial port, and I've tried using genericups type 5. When I do this, the driver seems to initialize, but then upsc shows the status to be OB LB. When I unplugged the UPS, there was no change in the status. I noticed on the Tripp Lite web site that this uses a different cable. It is
2007 Sep 03
0
Tr : adding Jageson Technology JASUNY UPS support to NUT
Hi Shanan, Since I'm lagging too much on this point, I've forwarded your mail to the NUT development list, in the hope that another developer will have a bit of time to merge your patch. thanks for your contribution, Arnaud Quette -- Free Software Developer - http://arnaud.quette.free.fr/ Debian Developer - http://people.debian.org/~aquette/ Network UPS Tools (NUT) Project Leader -
2006 Aug 18
0
(no subject)
Dear Mr Claesson, prepare for quite a long letter from me. I hope you will have time to read it. I bestowed a whole morning on trying to identify the correct upstype. Here are the results: root@marto:/home/marto# /usr/local/ups/bin/powercom -DD -u root -a Inform -x type=KP625AP Network UPS Tools - PowerCom and similars protocol UPS driver $ Revision: 0.5 $ (2.0.4) debug level is '2'
2006 Aug 08
1
GSM back door to shell with Centos and Palm handhelds
Hi folks, Don't know if it could be interesting or not, even useful, but past days i was spending my time trying to use an old gsm motorola v150 mobile phone to get access to my host from my palm device with pssh (http://www.sealiesoftware.com/pssh/), these are the steps i did to accomplish it, feel free to suggest or improve it, anyway i found it usefull. First, this motorolla has an usb
2011 Feb 16
3
Ippon Smart Winner 750/1000/1500/2000/3000
Have anybody expirience with Ippon Smart Winner 750/1000/1500/2000/3000 with serial interface ? I have tryed megatec and blazer_ser drivers with no success: [IPPON] driver = megatec port = /dev/ttyd0 desc = "IPPON smart winner 1500VA" model = "Smart Winner 750/1000/1500/2000/3000" # ./megatec -a IPPON -DDD Network UPS Tools - Megatec
2009 Oct 27
1
Protocol for Ritmo AS-800VA
Hi, I just acquired a Ritmo AS-800VA. Unfortunately, it doesn't work out of the box with nut - so I had to do a bit of reverse engineering on the protocol to get it working. Am now posting my findings here in the hope it will get this added to the next release. There are also 1000VA and 12000VA versions that this should work with. The protocol is very similar to the megatec protocol -
2012 Sep 06
2
Communications with UPS lost: No status from UPS
Hello, i've a problem, this is my configuration: - Atlantis Land UPS with serial port - a generic RS232 to USB cable adapter (QinHeng Electronics HL-340 USB-Serial adapter for linux). The problem is in the syslog file where i find: [...] Aug 19 09:07:25 ProLiant megatec[1126]: Communications with UPS lost: No status from UPS. Aug 19 09:07:26 ProLiant megatec[1126]: Communications with UPS
2002 Feb 26
0
syslinux timeout
Hi. I've ever wondered how nuch timeis left to timeout while waiting at the boot prompt, so I've writen this small patch to show it. This add a configuration command 'showtimeout'. If you like the patch I could improve it (for example to show the timeout in decimal because now it uses the writehex functions) Regards. -- ______ ________ / / \/ /___ ) I N T E G