similar to: Nut-upsuser Digest, Vol 175, Issue 30

Displaying 20 results from an estimated 9000 matches similar to: "Nut-upsuser Digest, Vol 175, Issue 30"

2020 Jan 27
3
System with MGE UPS shuts down too early
On 1/25/20 10:53 AM, Georgi D. Sotirov wrote: > OK, so yesterday evening I done a real test cutting of the power to > the UPS. And it went good... the UPS supported my server for 28:50 > minutes (i.e. the expected runtime with this load), before forcing > shutdown. The batteries could still hold as charge was 30 % with about > 15 minutes run time. And the UPS did hold for
2020 Jan 27
0
System with MGE UPS shuts down too early
Hello. I sometimes encountered batteries that were ok, but at times one of the cells would develop a random short/open, therefore reducing the real capacity even if voltage reading was ok. In the absence of a battery load tester i would suggest running multiple tests with a load (car headlight bulb or similar) on the battery outside the ups. This is to eliminate the suspicion of a software or UPS
2020 Jan 25
0
System with MGE UPS shuts down too early
OK, so yesterday evening I done a real test cutting of the power to the UPS. And it went good... the UPS supported my server for 28:50 minutes (i.e. the expected runtime with this load), before forcing shutdown. The batteries could still hold as charge was 30 % with about 15 minutes run time. And the UPS did hold for another full 10 minutes before powering off. These are the relevant lines
2020 Jan 11
0
System with MGE UPS shuts down too early
On January 11, 2020 1:18:27 PM GMT+02:00, "Georgi D. Sotirov" <gdsotirov at gmail.com> wrote: >Hello, > >I'm experiencing a strange early shutdown behavior with the following >system: > > * */OS/*: Slackware Linux 14.2 x86_64 > * */NUT/*: 2.7.4 (from my own package > <https://sotirov-bg.net/slackpack/pack.cgi?id=4083>) > * */UPS/*: MGE
2020 Jan 11
4
System with MGE UPS shuts down too early
Hello, I'm experiencing a strange early shutdown behavior with the following system: * */OS/*: Slackware Linux 14.2 x86_64 * */NUT/*: 2.7.4 (from my own package <https://sotirov-bg.net/slackpack/pack.cgi?id=4083>) * */UPS/*: MGE Ellipse PRO 1600 <powerquality.eaton.com/Products-services/Backup-Power-UPS/Ellipse-PRO.aspx> (bought in September 2017) */Problem
2020 Jan 24
2
System with MGE UPS shuts down too early
On January 24, 2020 6:13:31 PM GMT+02:00, "Georgi D. Sotirov" <gdsotirov at gmail.com> wrote: >OK, my UPS turned out to be older that I thought. I apparently bought >and installed it in September 2016 (not 2017 as I initially wrote). >That >makes for over 3 years of work, which is over the life expectancy of >the >batteries, Good batteries can last 4-5 years.
2020 Sep 30
0
Question about hardware failures / FSD
On Tue, 29 Sep 2020, João Luis Meloni Assirati wrote: > The UPS I am developing a driver to is able to report several flags for > critical hardware conditions, like overheat, overload, inverter failure, > output short etc. What should be the correct policy of operation when such a > condition occurs? I think that the an UPS in such a condition is not reliable > and therefore a
2020 Aug 14
0
Synology NAS is shutting down Ubuntu servers after very brief power outage (fwd)
I found something interesting that I think may apply here. Check this out... https://forum.synology.com/enu/viewtopic.php?f=19&t=73960&hilit=ups+slave *I have the latest version of the Windows port of NUT (A UPS management package) installed on my Windows 7 machine. The UPS I am using is a very old APC BK650M which is controlled and sends its status via a special serial cable to the
2020 Aug 14
1
Synology NAS is shutting down Ubuntu servers after very brief power outage (fwd)
On Fri, 14 Aug 2020, Todd Benivegna wrote: > https://forum.synology.com/enu/viewtopic.php?f=19&t=73960&hilit=ups+slave  > > I have the latest version of the Windows port of NUT (A UPS management package) installed on my Windows 7 machine. The UPS I am using is a > very old APC BK650M which is controlled and sends its status via a special serial cable to the Windows
2020 Apr 23
3
Low battery unexpected shutdown
Hi, recently I observed that during a power outage, my NUT setup doesn't shutdown properly. Indeed it never reaches the LowBattery state to notify and initiate shutdown on clients. Reviewing my setup and logs I think I'm facing multiple problems and I'm unable to point to real root cause. First, let me focus on my scenario and current setup: In normal status (ONLINE, fully charged)
2020 Aug 14
0
Synology NAS is shutting down Ubuntu servers after very brief power outage (fwd)
Sorry, I guess it is */usr/syno/bin/synoups* On Fri, Aug 14, 2020 at 2:27 PM Todd Benivegna <todd at benivegna.com> wrote: > I found something interesting that I think may apply here. Check this > out... > > > > https://forum.synology.com/enu/viewtopic.php?f=19&t=73960&hilit=ups+slave > > *I have the latest version of the Windows port of NUT (A UPS
2020 Jan 11
1
System with MGE UPS shuts down too early
On January 11, 2020 3:42:15 PM GMT+02:00, Roger Price <roger at rogerprice.org> wrote: >On Sat, 11 Jan 2020, Georgi D. Sotirov wrote: > >> Jan 11 11:49:15 sotirov-bg upsmon[2677]: UPS mgeups at localhost on >battery >> Jan 11 11:49:15 sotirov-bg upssched[29746]: Executing command: >ups-on-battery >> Jan 11 11:49:15 sotirov-bg upssched-cmd: Unrecognized command:
2020 Apr 23
0
Low battery unexpected shutdown
Hello. Battery, battery, battery. I am only thinking at worn batteries. I recently had the same symptoms with an hp/eaton g3 1500va. One of the 3 batteries was reading a healthy 12.8v, but when put under load it would quickly drain. I would measure each battery and test them under load, like with a car headlight bulb switched on both fillaments. On Thu, 23 Apr 2020, 16:54 Marc Franquesa,
2019 Jun 10
0
How to shutdown macOS / mac OSX from Network UPS Tools client - NUT
> On 9 Jun 2019, at 21:19, Roger Price <roger at rogerprice.org> wrote: > Using upssched and a upssched-cmd script to shut down the system is an alternative to using the builtin upsmon SHUTDOWNCMD on status [OB LB]. A upssched-cmd script can provide a managed shutdown well before [OB LB] is reached, but should the UPS reach that status upsmon's SHUTDOWNCMD will take over and
2020 Jan 11
0
System with MGE UPS shuts down too early
On Sat, 11 Jan 2020, Georgi D. Sotirov wrote: > Jan 11 11:49:15 sotirov-bg upsmon[2677]: UPS mgeups at localhost on battery > Jan 11 11:49:15 sotirov-bg upssched[29746]: Executing command: ups-on-battery > Jan 11 11:49:15 sotirov-bg upssched-cmd: Unrecognized command: ups-on-battery These lines say that you have something like AT ONBATT mgeups at localhost EXECUTE ups-on-battery
2016 Jul 11
0
Proposal for technique to stop a timer at any moment
Here is patch 2 of 2. Roger diff -rup -x '*.html' -x '*.8' -x '*.5' nut-2.7.4.orig/docs/man/upsd.txt nut-2.7.4.dev/docs/man/upsd.txt --- nut-2.7.4.orig/docs/man/upsd.txt 2015-12-29 09:42:34.000000000 +0100 +++ nut-2.7.4.dev/docs/man/upsd.txt 2016-07-07 10:08:51.939354892 +0200 @@ -119,6 +119,16 @@ administrative functions like SET and IN controlled in
2024 Feb 21
1
System keeps going into FSD mode after power on
Hello, I am a new user of NUT and trying to wrap my ahead around a couple of things. I installed NUT 2.7.4-13 from package on RasPi 4, running Raspbian Linux 11 (bullseye). I have Cyberpower SL700U connected to it. For testing I set battery.charge.low to 90, so I wouldn't have to wait a long time. See all relevant config below. First of all, what seems to happen is that UPS gets to the low
2018 Sep 06
0
Poweroff USP on upsmon FSD
Hi! I'm trying to setup a small mobile server rack with key switch to power on/off the whole system. Used USP is an APC Smart-UPS 1500 SMT1500RMI2U with extra AP9613 IO card [1] to get the key switch "connected" to the UPS. The IO card has several inputs which can trigger actions like power on and "gracefully" shutdown. On key switch OFF this SMT ups model changes ups
2020 Jun 21
2
Server did not shut down
2013 Sep 11
1
Issue with slave FSD notification on Windows port of NUT
I have the latest version of the Windows port of NUT installed on my Windows?7?machine. The UPS is connected via serial cable to the Windows machine. I also have my Synology NAS (which uses NUT) connected over the local network as a slave to the Windows NUT master. The Synology slave is configured to immediately go into "safe mode" whenever an FSD or OB+LB indication is received from the