similar to: ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS

Displaying 20 results from an estimated 3000 matches similar to: "ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS"

2019 Apr 10
2
ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS
Hi, that's a good point, thanks. I don't see ups.delay.start anywhere. Here is the output of upsrw: upsrw Eaton at localhost [outlet.desc] Outlet description Type: STRING Maximum length: 20 Value: Main Outlet [output.voltage.nominal] Nominal output voltage (V) Type: ENUM Option: "200" Option: "208" Option: "220" Option: "230" SELECTED Option:
2019 Apr 10
2
ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS
Thanks for help! Are you happy with your Eaton Elipse ECO 1600? Does it work well with ondelay? I will need some UPS that supports the ondelay parameter. Bartosz śr., 10 kwi 2019 o 13:06 Roger Price <roger at rogerprice.org> napisał(a): > On Wed, 10 Apr 2019, Bartosz wrote: > > > I don't see ups.delay.start anywhere. Here is the output of upsrw: > > > > upsrw
2019 Apr 11
1
ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS
On Wed, 10 Apr 2019, Bartosz wrote: > BTW,does it have passive cooling? In the sense that there is no fan, The Eaton Ellipse ECO 1600 has passive cooling. It gets warm but not hot. > Are you happy with your Eaton Elipse ECO 1600? Does it work well with ondelay? "ECO" means that it does not have "buck and boost" or a fancy control panel. I replace my batteries
2019 Dec 22
0
ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS
On Sat, 21 Dec 2019, Bartosz wrote: > Hi Roger, > have you ever tested the > ups.delay.start: 40  > parameter in action? > Does it actually work in your UPS? Yes, thoroughly tested, and it works as described in my Configuration Examples. (Including correct operation during this morning's storm :-) > Could you send me a link to your UPS on the Internet? I see that there
2019 Apr 10
0
ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS
BTW, does it have passive cooling? Bartosz śr., 10 kwi 2019 o 16:53 Bartosz <bartoszmail at gmail.com> napisał(a): > Thanks for help! > Are you happy with your Eaton Elipse ECO 1600? > Does it work well with ondelay? > I will need some UPS that supports the ondelay parameter. > Bartosz > > śr., 10 kwi 2019 o 13:06 Roger Price <roger at rogerprice.org> napisał(a):
2019 Apr 06
0
ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS
In the upsc output for my Eaton Elipse ECO 1600 I see ups.delay.shutdown: 30 ups.delay.start: 40 but in the uspc output for your Eaton 5E850iUSBDIN I see only ups.delay.shutdown: 60 Where is ups.delay.start ? Does the command upsrw <UPS> display this variable ? Roger
2019 Apr 10
0
ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS
On Wed, 10 Apr 2019, Bartosz wrote: > I don't see ups.delay.start anywhere. Here is the output of upsrw: > > upsrw Eaton at localhost > [outlet.desc] > [output.voltage.nominal] > [ups.delay.shutdown] > [ups.start.battery] > Might it be that the UPS does not support it or maybe the driver does not > support it? Since the usbhid-ups driver supports
2020 Sep 12
1
UPS recommendation for NUT and power-on-delay support
On Fri, 11 Sep 2020, Bartosz wrote: > Could you please recommend me a UPS with 100% support of the ondelay parameter > and NUT compatibility? 850 or 1000 VA I have the EATON 5E850iUSBDIN UPS and it > does not support this parameter so I would like to buy another UPS that for > sure will support it. I have an Eaton Ellipse Eco 1600 bought in 2016 which has a delayed start feature.
2015 Jan 21
2
CyberPower BR850ELCD ignores offdelay and turns itself back on while still on battery
Hi there, I just purchased a CyberPower BR850ELCD and while setting NUT up with the install instructions from the homepage was pretty straightforward, and the UPS was detected by the usbhid-ups driver, I'm having problems getting the UPS to work properly. First issue: whatever I set as the offdelay, seems to be ignored and the UPS just cuts the power about 2sec after receiving the
2020 Sep 11
1
UPS recommendation for NUT and power-on-delay support
On Fri, Sep 11, 2020, at 4:05 PM, Bartosz wrote: > Dear All, > > Could you please recommend me a UPS with 100% support of the ondelay parameter and NUT compatibility? > > 850 or 1000 VA > > I have the EATON 5E850iUSBDIN UPS and it does not support this parameter so I would like to buy another UPS that for sure will support it. > > Thank you, > Bart Can you tell
2015 Jan 22
0
CyberPower BR850ELCD ignores offdelay and turns itself back on while still on battery
On Jan 21, 2015, at 9:15 AM, Sebastian Hosche <sebastian.hosche at web.de> wrote: > Hi there, > > I just purchased a CyberPower BR850ELCD and while setting NUT up with the install instructions from the homepage was pretty straightforward, and the UPS was detected by the usbhid-ups driver, I'm having problems getting the UPS to work properly. > > First issue: whatever I
2020 Jan 08
0
Hardware compatability report: Eaton Ellipse ECO 1600
Here is a Compatibility Report for the Eaton Ellipse ECO 1600 UPS. Roger battery.charge: 100 battery.charge.low: 20 battery.runtime: 1575 battery.type: PbAc device.mfr: EATON device.model: Ellipse ECO 1600 device.serial: 000000000 device.type: ups driver.name: usbhid-ups driver.parameter.lowbatt: 37 driver.parameter.offdelay: 30 driver.parameter.ondelay: 40 driver.parameter.pollfreq: 30
2010 Nov 11
1
Setting offdelay and ondelay in Smart-UPS 1500 RM units
Hello there. Have been experimenting with an APC Smart-UPS 1500 RM and would like to share the results of my research. I hope this could be of help to people having this kind of units. I would also like to give something back to the NUT community. :) Here are the details of the unit in question (a 1500 VA rack mountable one): Model: Smart-UPS 1500 RM Firmware revision: 617.3.I USB firmware
2007 Mar 12
3
upsmon keeps broadcasting on battery / on power (driver is newhidups)
Hi, I try to install the newhidups driver for a MGE Pulsar M2200 connected to a USB port under Linux Red Hat 4 Upd 4. I have compiled and installed the usb driver (make usb && make install-usb). I followed the instructions in /nut-2.0.5/scripts/hotplug-ng/README abour the /etc/udev/rules.d/025_nut-usbups.rules. The ups is recognized by the kernel: Mar 12 14:52:03 serveur1 kernel: usb
2007 Mar 12
3
upsmon keeps broadcasting on battery / on power (driver is newhidups)
Hi, I try to install the newhidups driver for a MGE Pulsar M2200 connected to a USB port under Linux Red Hat 4 Upd 4. I have compiled and installed the usb driver (make usb && make install-usb). I followed the instructions in /nut-2.0.5/scripts/hotplug-ng/README abour the /etc/udev/rules.d/025_nut-usbups.rules. The ups is recognized by the kernel: Mar 12 14:52:03 serveur1 kernel: usb
2020 Sep 05
9
ups not being started sat reboot
But runs normally if started. On a rpi4 running an uptodate raspbian buster, how do I set it to auto start at boot time? Thanks. Cheers, Gene Heskett -- "There are four boxes to be used in defense of liberty: soap, ballot, jury, and ammo. Please use in that order." -Ed Howdershelt (Author) If we desire respect for the law, we must first make the law respectable. - Louis D.
2013 Mar 08
0
Windows: offdelay/ondelay
Are there plans to change the default offdelay/ondelay for the Windows versions of NUT since it can't be invoked at the end of shutdown? E.g. I have a Win2k3 server that takes just over 4min to shut down, so I set my offdelay to 600 (ondelay is +15 that) to be extra safe. Maybe a 2 min by default would be good? Most (all?) APC non-smart UPS's are hard-coded at an annoying 1min delay,
2018 Feb 02
0
Default value for ondelay
On Fri, 2 Feb 2018, nut.user.u830 at neverbox.com wrote: > I have an older box set up this way for continuous integration, and it needs to see more than a few seconds of power loss for the "always turn > on" BIOS setting to work. I forget how many different intervals I tried, but 30 seconds of off time is reliable for that particular box. > > Thanks. This
2005 Aug 30
0
mge-shut doesn't use lowbatt parameter
Hello nuters, FreeBSD, Ellipse USBS 800, serial line, nut 2.02 everything works fine. But I'm only able to get an automatic shutdown when reaching the built-in 30% level. I the "lowbatt parameter" is set to anything, it's simply ignored. This is a problem as I want to shutdown around 90% to avoid the battery to drain out when multiple shutdowns occur. Any idea ?
2015 Jun 30
1
nut UPS kill inverter: offdelay ignored
Dear All, I am running Slackware64-14.1(Linux marto 3.10.17 #1 SMP Fri Feb 14 16:39:21 CST 2014 x86_64 Intel(R) Pentium(R) CPU G3250 @ 3.20GHz GenuineIntel GNU/Linux) with kernel 3.10.17 and nut package nut-2.6.5-x86_64-1_SBo, buit from source using the build script http://slackbuilds.org/repository/14.1/system/nut/ In the README.Slackware it is suggested that the commands for killing the