Displaying 20 results from an estimated 1200 matches similar to: "APC Easy UPS"
2023 Sep 16
1
Nut-upsdev Digest, Vol 206, Issue 5
It seems the `libmodbus` library or headers were not found, or something
similar - so the driver against it was not built. Did you install
`libmodbus-dev` before the build? What does `config.log` in the build root
say (and.or the summary shown after you run the `configure` script)?
On Sat, Sep 16, 2023 at 7:46?PM FatGear <fatgear1 at free.fr> wrote:
> Hi,
>
> I don't know what
2023 Sep 19
1
Nut-upsdev Digest, Vol 206, Issue 5
Hello there,
I don't think that's working,?
I have done all your repo but i don't know how it's supposed to work.
I have a idea, change vendor id and product id? to make the driver try
to connect to the ups, what do you think of that ? With this driver
maybe : usbhid-ups
FatGear
Le 16/09/2023 ? 20:40, Jim Klimov a ?crit?:
> It seems the `libmodbus` library or headers were
2023 Sep 19
1
Nut-upsdev Digest, Vol 206, Issue 5
Well, now that the `subdriver` option got added to `usbhid-ups` too, you
can at least try that (by building again the current master). See
command-line help for the subdrivers it would currently recognize, and copy
e.g. the first word as the matching option, e.g.:
./drivers/usbhid-ups -DDDDDD -d1 -s test -x port=auto -x vendorid=...
-x productid=... -x subdriver=...
and try to lockpick your
2023 Sep 23
1
Nut-upsdev Digest, Vol 206, Issue 5
Hello There,
I tried your advice and i don't think it works either,
See the logs,
"
/tmp/nut# ./drivers/usbhid-ups -DDDDDD -d1 -s test -x port=auto -x
vendorid=... -x productid=... -x subdriver=...
Network UPS Tools - Generic HID driver 0.52 (2.8.0-2557-g81fca30b2)
USB communication driver (libusb 1.0) 0.46
?? 0.000000??? [D3] main_arg: var='port' val='auto'
??
2023 Sep 23
1
Nut-upsdev Digest, Vol 206, Issue 5
<facepalm ;)> the ellispis "something=..." were supposed to be replaced by
your device ID numbers, etc.
On Sat, Sep 23, 2023, 18:26 FatGear <fatgear1 at free.fr> wrote:
> Hello There,
>
> I tried your advice and i don't think it works either,
>
> See the logs,
>
> "
>
> /tmp/nut# ./drivers/usbhid-ups -DDDDDD -d1 -s test -x port=auto -x
2003 Apr 04
2
Bug in %in% (match)
Hi,
Am I hitting some limit in match? Consider the following example:
> tst<-seq(100,125,by=.2)%in%seq(0,800,by=.1)
> sum(tst)
[1] 76
> seq(100,125,by=.2)
[1] 100.0 100.2 100.4 100.6 100.8 101.0 101.2 101.4 101.6 101.8 102.0
102.2
[13] 102.4 102.6 102.8 103.0 103.2 103.4 103.6 103.8 104.0 104.2 104.4
104.6
[25] 104.8 105.0 105.2 105.4 105.6 105.8 106.0 106.2 106.4 106.6 106.8
2003 Apr 04
2
Bug in %in% (match)
Hi,
Am I hitting some limit in match? Consider the following example:
> tst<-seq(100,125,by=.2)%in%seq(0,800,by=.1)
> sum(tst)
[1] 76
> seq(100,125,by=.2)
[1] 100.0 100.2 100.4 100.6 100.8 101.0 101.2 101.4 101.6 101.8 102.0
102.2
[13] 102.4 102.6 102.8 103.0 103.2 103.4 103.6 103.8 104.0 104.2 104.4
104.6
[25] 104.8 105.0 105.2 105.4 105.6 105.8 106.0 106.2 106.4 106.6 106.8
2005 Jul 09
1
apcsmart varibles
Hello,
I am working on getting NUT working with my Smart-UPS 900 UPS (with the C c=
able)
For several years, I have used the apcupsd product, but because of the
nagios support for nut, I am working on switching over.
Under apcupsd, I get tons of information from my UPS:
# /usr/local/sbin/apcaccess status
DATE : Sat Jul 09 12:56:41 CDT 2005
HOSTNAME : homer
RELEASE : 3.8.6
UPSNAME :
2007 Dec 12
1
[PATCH]Support full capabilities on older Smart-UPS 600
Hi,
The patch below adds support for a pair of old (circa 1993) APC
Smart-UPS 600 devices that I have. They don't support the query
mechanism of newer APC devices but do respond to the full Smart-UPS
command set:
battery.alarm.threshold: 0
battery.charge: 100.0
battery.charge.restart: 00
battery.date: 02/22/93
battery.runtime: 2040
battery.runtime.low: 120
battery.voltage: 27.67
2007 Jul 31
1
Proposed apcsmart driver patch
G'day y'all,
Here's a tiny patch set for drivers/apcsmart.c and drivers/apcsmart.h.
Adds APC SmartUPS 1250 ("8QD" case) + 940-0024C recognition to
apcsmart. (Unpatched apcsmart.c v1.99.8 misidentifies the SmartUPS
1250 as a "dumb" UPS.) For NUT 2.0.5+.
NUT 2.0.5: Patches apply successfully. Builds successfully. Works as
expected under Ubuntu 7.04.
NUT 2.2:
2013 Jun 14
1
Battery runtime not displaying
Thanks for the help, with the apcsmart-old driver it works again! Didn't notice my UPS is now so "old" ;-)
Here is the output of upsc with apcsmart-old driver:
battery.alarm.threshold: 0
battery.charge: 100.0
battery.charge.restart: 00
battery.date: 11/22/06
battery.packs: 001
battery.packs.bad: 000
battery.runtime: 540
battery.runtime.low: 120
battery.voltage: 53.73
2007 Dec 10
1
Driver: apcsmart, SMART-UPS 2200, battery.runtime status information?
Hello,
We have a APC SMART-UPS 2200 which gives the following status
information:
battery.alarm.threshold: 0
battery.charge: 089.0
battery.charge.restart: 00
battery.date: 01/10/04
battery.packs: 000
battery.runtime: 21180
battery.runtime.low: 120
battery.voltage: 52.95
battery.voltage.nominal: 048
driver.name: apcsmart
driver.parameter.pollinterval: 2
driver.parameter.port: /dev/ttyS0
2006 Jun 01
0
"Battery constant" value for APC UPS
Hi all,
Thought I'd forward this on, as the apcsmart driver doesn't appear to
have any support for this (admittedly obscure) setting and it doesn't
seem to be listed at http://www.networkupstools.org/protocols/apcsmart.html.
Hope someone finds it useful.
Later,
Russ
--
Russell Odom
http://www.gloomytrousers.co.uk/
Fast, cheap, good: pick two.
-------- Original Message --------
2006 Nov 23
2
apcsmart and ambient data (was: NUT and MonAMI plugin)
Hi Paul,
> I have another NUT client for your client-projects[1] page: MonAMI[2].
>
> MonAMI aims to be a "universal sensor framework". The data gathered
from
> MonAMI's NUT plugin can be sent to any of the output plugins. Currently,
> these include Ganglia, Nagios, KSysguard and a file-logger (amongst
others).
interesting though I've not had time to
2013 Jun 07
1
cannot update battery.date value of APC ups battery
Hi,
I'm running this command:
# upsrw -s "battery.date=2013Jun7" -u ups-mon-IT "IT-APC-BOTTOMRIGHT at 127.0.0.1"
Password:
OK
but I'm getting this listing:
# upsc IT-APC-BOTTOMRIGHT at 127.0.0.1
battery.alarm.threshold: 0
battery.charge: 100.0
battery.charge.restart: 15
battery.date: 01/10/06
battery.packs: 000
battery.runtime: 1440
battery.runtime.low: 120
2013 Mar 07
1
unacceptable utility voltage rate of change
Hi,
One of my APC devices reports: "unacceptable utility voltage rate of change".
I believe it has something to do with input voltage fluctuating too fast maybe even beneath or over the input voltage thresholds.
Should I worry about this?
should I measure input voltage? (I suppose I'd need more than multimeter readings. Maybe an oscilloscope or a multimeter that can record
2008 Apr 18
2
My APC ups shutdown but doesn't start again
Hello,
My APC Ups uses nut to manage all systems connected to it. But if online power failed until it shutdown, it not restart automatically after the power returned. It stay down until i restart it.
When i execute the command: # upsc siUps1
it output me this:
battery.alarm.threshold: L
battery.charge: 018.0
battery.charge.restart: 15
battery.date: 03/31/07
battery.runtime: 120
2013 Feb 28
8
false low battery alarm
Hi,
I have two types of UPS devices and one of them (APC) gave me a false "low battery" alert. I can't reproduce the problem... Also, there was nothing apparently wrong with the UPS at the time of the false alert. All I could do was grab the driver values within a minute after the "low battery" notification.
These are the values:
battery.runtime.low : 120
2013 Jan 30
3
bug report: apcsmart (WIN) 940-0024C connect fail, problem with command 'E'
Dear Ladies and Gentlemen,
I have several old, yet functioning APC Smart-UPS (Model 600LS, Part AP600I,
Firmware 6JI, no EEPROM, from 1991). They are not supported by Powerchute
any more. I run NUT 2.6.5-4 on Windows XP SP3. I use COM1 port with cable
940-0024C. The connection fails with APC Smart protocol driver 3.0
(2.6.3-3534:3540M), APC command table version 3.0 or higher - it works with
APC
2009 Feb 28
2
APC SMART-UPS 1500 always reporting LB
Using nut v2.2.2, and the APC serial cable.
I have a client who's APC SMART-UPS 1500 (circa 2000) is always reporting LB. The batteries were old so they were replaced two weeks ago with brand new batteries. UPS still reported low batteries...
I ran a calibration and a test on the unit (using the nut upscmd utility)
During those tests, the battery charge on the unit goes to zero and slowly