Email Alerts for Multiple UPSs with upssched
Ah! So I can detect the source UPS in the upssched.conf and pass it as a distinct event to the shell script. That sounds like an excellent approach.
Thanks!
GMH
From: O'Shaughnessy, Mike [mailto:Mike.OShaughnessy at gd-ms.com]
Sent: Tuesday, October 31, 2017 12:46 PM
To: Garrett Michael Hayes <Garrett at VerbalImaging.com>; nut-upsuser at lists.alioth.debian.org
Subject: RE: Email
2017 Oct 31
0
Email Alerts for Multiple UPSs with upssched
There's supposedly another way with a custom upsmon.conf:
NOTIFYMSG type message
upsmon comes with a set of stock messages for various events. You can change them if you like.
NOTIFYMSG ONLINE "UPS %s is getting line power"
NOTIFYMSG ONBATT "Someone pulled the plug on %s"
Note that %s is replaced with the identifier of the UPS in question.
The message must be one
2017 Oct 31
0
Email Alerts for Multiple UPSs with upssched
I'm running a single "nut-server" that monitors seven ups units.
In upsmon.conf:
MONITOR ups-1 0 <User> <Pw> master
MONITOR ups-2 0 <User> <Pw> master
MONITOR ups-3 0 <User> <Pw> master
MONITOR ups-4 0 <User> <Pw> master
MONITOR ups-5 1 <User> <Pw> master
MONITOR ups-6 1 <User> <Pw> master
MONITOR
2017 Mar 02
6
NUT - General Concept Question
I've been looking over the documentation and several installation guides for NUT, and I'm starting to get a little bit of a feel for what it is. But I'm still not clear whether what I'd *like* to accomplish is actually practical using NUT. Perhaps someone here can tell me if they've done something similar, or if I'm way off base.
I would like to set up a Linux host as a
2017 Nov 01
1
Email Alerts for Multiple UPSs with upssched
This was the secret sauce! I first modified my BASH script to stuff the output of the 'set' command into a variable, then passed that variable in to my email command. Then I triggered an event and saw what variables were there in the body of the message.
Voila!
$UPSNAME and $NOTIFYTYPE were there and available. I modified the script to pump THOSE into the mail command, and the problem
2005 Sep 13
3
timers and their usage
Hi everyone,
new to the list but a long time nut user.
I've tried a couple of times to set up a timer to avoid getting annoying
messages when the system goes on battery for only a few seconds.
in uppsched.conf I added this at the bottom:
AT ONBATT * START-TIMER onbattwarn 60
AT ONLINE * CANCEL-TIMER onbattwarn
What am I missing? it still doesn't wait before alerting me.
2017 Oct 31
0
Email Alerts for Multiple UPSs with upssched
On October 31, 2017 4:09:46 PM GMT+01:00, Garrett Michael Hayes <Garrett at VerbalImaging.com> wrote:
>Greetings Gentlebeings,
>
>I have started deploying a number of NUT instances on Raspberry Pi
>machines (Raspbian Jessie) across my network. The purpose of these
>"nutcases" as we refer to them is to monitor the status of the UPSs
>supporting our network
2014 Jan 21
3
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 3:16 AM, Rafa? Oleszek wrote:
> I would like to mention that MINSUPPLIES manipulation doesn't work. My nut version is : 2.2.2-4 (RHEL 5)
What do your configuration files look like? Setting MINSUPPLIES to 2 should work. You can run upsmon with a debug level of 3 or greater, and it will print the current and minimum "power value", which is what determines
2017 Jun 09
2
Apple Mac slave
On Thu, 8 Jun 2017, Robbie van der Walle wrote:
> After the first test and the NAS is restarted I had to change the
> setting battery.charge.low again to 80?
Does the NAS DSM reset battery.charge.low to 10 or is it internal to the
UPS? You will have to experiment by disconnecting the UPS control lead
from the NAS and connecting it (if possible) to the Mac. After setting to
80 and a
2022 Dec 22
3
NUT & UPS, how to shut down client after 2 min on battery?
Hi!
Some systems I have take some time to shut down, so I would like them to shut down if the UPS have been on battery for 2 minutes.
Internet has told me that SHUTDOWNCMD ?/sbin/shutdown -h +0? in /etc/nut/upsmon.conf will execute when the UPS is both OB (on battery) and LB (Low battery). Like in wiki.ipfire.org - Detailed NUT Configuration<https://wiki.ipfire.org/addons/nut/detailed>
2023 May 27
2
unable to connect to APC UPS Connection Refused
I've not been able to connect to my ups using NUT 2.7.4 or NUT 2.8.0.
2.7.4 was installed as a package, 2.8.O was compiled from source.
I've messed with permissons, everything is root:root and has the approprate read/execute permissons. I've tried two differnt UPS(es) APC & CyperPower. I'm running PI OS (Raspbian) on a Raspberry Pi3 model B. The port 3493 is open (UFW). I can
2019 Mar 30
2
upssched Not Running
2011 Jul 19
2
KIN-1500AP RM + Windows 2008 64-bit Standard R2 SP1 (nut 2.6.1)
I have only RS-232 on the box (meanwhile, it was manufactured on march of
2011)
Here is my configs:
nut.conf:
*
*
MODE = netserver
ups.conf:
*
*
[KIN1500]
driver = powercom
port = notUsed
desc = "Powercom KING PRO KIN-1500AP RM"
upsd.conf:
*
*
LISTEN 192.168.1.2 3493
upsd.users:
*
*
[monuser]
password = xxxxxxxx
upsmon master
2017 Jun 29
2
Help with Elite 800VA usb UPS
On Jun 29, 2017, at 6:52 AM, Andrea de Lutti wrote:
>>> Anyway I still not receive any email on any test (power cord disconnected and/or reconnected for example)
>>
>> Oh, I misinterpreted "working script" as a script that was sending email, rather than work-in-progress. Does that same command work from the command line? Can you add something like "logger"
2007 Nov 09
2
UPSSched UPSNAME env variable
Hi everybody,
i'm trying to use the UPSNAME environment variable within the script
launched by upssched, and although it is correctly written and thus read by
my script, it doesn't get updated when multiple UPSes are configured.
To be more precise i'm monitoring 2 UPSes and using AT *EVENT* * *OPERATION*
*handle *to manage events in upssched.conf.
Am i wrong somewhere?
I'm
2023 Jun 11
1
Upssched 100% CPU after updating Debian 12
Hi,
I have been running nut successfully for a long time with my Debian 11 server. I upgraded my server to Debian 12 today, which upgraded nut also from 2.7.4-13 to 2.8.0-7. I noticed that after upgrade there was a upssched process running and taking 100% cpu time.
I checked if there were any changes to configuration file formats with nut upgrade and only differences I noticed were a terminology
2011 Jun 08
2
Misconfiguration of Windows MSI installer 2.6.0-1 with my Powerware 5115 connected via USB port
Hello.
I've tried to configure Windows (complete port, Beta): Windows MSI installer
2.6.0-1 with my Powerware 5115 connected via USB port but have no luck.
Here is my config files:
*nut.conf:*
MODE = netserver
*ups.conf:*
[PW5115]
driver = bcmxcp_usb
port = notUsed
desc = "PowerWare 5115"
*upsd.conf:*
LISTEN 192.168.1.12 3493
*upsd.users:*
[monuser]
2015 Oct 27
2
The system doesn't shutdown
Yes, that was the power off test. However the upssched-cmd script gave
absolutely no signs of activity. Even it's logger lines don't show up in
journalctl. No any permission error messages - nothing. Only the 2 messages
from upsmon - on battery and then on line power.
Here is the nut-report:
http://www.filehosting.org/file/details/518300/NUT.report
---
George Anchev
On Tue, Oct 27,
2019 Jun 08
2
How to shutdown macOS / mac OSX from Network UPS Tools client - NUT
Hi,
I’ve posted my question on Superuser.com but not had any replies in 2 weeks, so I guess no-one there knows anything about NUT.
https://superuser.com/questions/1441153/how-to-shutdown-macos-mac-osx-from-network-ups-tools-client-nut <https://superuser.com/questions/1441153/how-to-shutdown-macos-mac-osx-from-network-ups-tools-client-nut>
I’m looking for help in shutting down my iMac on
2023 Jan 12
1
NUT & UPS, how to shut down client after 2 min on battery?
Now I have this in /etc/nut/upsmon.conf (my QNAP NAS wants admin and 123456 or not working)
RUN_AS_USER root
MONITOR qnapups at localhost 1 admin 123456 master
MONITOR qnapups at 192.168.222.252 3493 admin 123456 slave
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/killpower
NOTIFYFLAG ONLINE SYSLOG+EXEC