2016 Oct 06
0
UPS Shutdown
On Wed, 5 Oct 2016, Jeff Bowman wrote:
> I?m trying to better understand OffDelay and OnDelay:
> http://networkupstools.org/docs/man/usbhid-ups.html#_extra_arguments
>
> My server requires ~3? minutes to shut itself down. Considering this I?m
> comfortable setting OffDelay to 300 (five minutes).
>
> How does this work in conjunction with the UPS hardware? Does NUT
>
2016 Oct 06
5
UPS Shutdown
> > How does this work in conjunction with the UPS hardware? Does NUT
> > immediately send a command to the UPS to wait for 300 seconds and then
> > shut itself down, thereby allowing the server enough time to safely
> > shut itself down as well?
>
> Yes.
Very good, thank you.
> The command is "upsdrvctl shutdown".
That's what I thought, but I
2017 May 11
2
Good Day NUT
Good Day nut
Many thanks for your reading
==> AA. I confront an issue that can't shutdown the ups
With the nut, I can get the ups status(upsc) and shutdown the linux-ubuntu when power failure occurs(upsmon)
But don't know which configuration I ignore to setup for ups shutdown
==> BB. I want to check that with the command "upsdrvctl shutdown" and
2017 Jul 03
2
Help with Elite 800VA usb UPS
Ok, I am running NUT in dummy mode.
I have added a new ups in ups.conf
[dummy]
driver = dummy-ups
port = upsc.dev
desc = "dummy ups for testing purposes"
upsc.dev has been generated by exporting the Elit configuration.
I have added the monitor line in upsmon.conf and the "exec" flags (all the
events)
MONITOR dummy at artu 1 user pass master
SHUTDOWNCMD
2019 Dec 16
3
Shutdown time configuration
On 2019-12-16 05:34, Roger Price wrote:
> On Sun, 15 Dec 2019, Phil Stracchino wrote:
>
>> I switched a while back to a Cyberpower PR3000LCDRTXL2U UPS with an
>> external battery chassis. We've lost power twice since I installed it,
>> and both times, the UPS has killed power to everything while still
>> indicating 80% capacity before NUT has even initiated
2017 Jun 09
2
Apple Mac slave
On Thu, 8 Jun 2017, Robbie van der Walle wrote:
> After the first test and the NAS is restarted I had to change the
> setting battery.charge.low again to 80?
Does the NAS DSM reset battery.charge.low to 10 or is it internal to the
UPS? You will have to experiment by disconnecting the UPS control lead
from the NAS and connecting it (if possible) to the Mac. After setting to
80 and a
2016 Sep 08
3
How to get started (Windows)
I've been able to get the latest Windows port installed on my Hyper-V 2012 R2 instance and start the service.
But as I'm an absolute beginner I'm not sure how to proceed further. I've browsed the archives, but discussions here tend to assume at least an intermediate level of understanding; thus it's still quite a bit over my head. Your patience and slow explanations are
2017 May 15
1
Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
On Mon, 15 May 2017, Dinow Hsieh wrote:
> ==> I have tried this command "upsdrvctl shutdown" as below results (However the UPS still sustain the power)
>
> ??? Network UPS Tools - UPS driver controller 2.7.1
> ??? Network UPS Tools - Generic HID driver 0.38 (2.7.1)
> ??? USB communication driver 0.32
> ??? Using subdriver : PowerCOM HID 0.4
> ??? Initiating UPS
2017 Jun 10
1
Apple Mac slave
On Fri, 9 Jun 2017, Robbie van der Walle wrote:
> ... and also still open is the notification on the Mac.
If notify-send is available on the Mac, then perhaps this will work:
In upsmon.conf on the Mac you need
NOTIFYCMD /usr/sbin/upssched (or wherever this goes on a Mac)
NOTIFYFLAG ONBATT SYSLOG+EXEC
In upssched.conf you need
CMDSCRIPT /usr/sbin/upssched-cmd (or wherever this
2020 Mar 10
2
Fwd: Windows upssched does not work
Hi,
I have problem with upssched on windows. Upssched is not executed. I
have 2 scripts, 1 for notification in upsmon and second for scheduling
in upssched. Monitoring is working fine, script write to log. I'm
using binary windows installer 2.6.5-6 from NUT.
Here are my configs:
--- nut.conf
MODE=netclient
--- upsmon.conf
MONITOR ups_1000 at 192.168.3.95 1 <user> <password> slave
2022 Dec 22
3
NUT & UPS, how to shut down client after 2 min on battery?
Hi!
Some systems I have take some time to shut down, so I would like them to shut down if the UPS have been on battery for 2 minutes.
Internet has told me that SHUTDOWNCMD ?/sbin/shutdown -h +0? in /etc/nut/upsmon.conf will execute when the UPS is both OB (on battery) and LB (Low battery). Like in wiki.ipfire.org - Detailed NUT Configuration<https://wiki.ipfire.org/addons/nut/detailed>
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 03
3
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On Mon, 3 Apr 2017, Gene Heskett wrote:
>>
> Nut, IIRC, can do a periodic battery test by putting it offline, using
> the battery, for a predetermined length of time, weekly, monthly etc,
We definitely don't want that in this instance either! (Unless it is a
dual PS server.) We want the ALARM that the nut driver is generating,
and upsd is passing on - to be acted on in some
2015 Oct 27
2
The system doesn't shutdown
Yes, that was the power off test. However the upssched-cmd script gave
absolutely no signs of activity. Even it's logger lines don't show up in
journalctl. No any permission error messages - nothing. Only the 2 messages
from upsmon - on battery and then on line power.
Here is the nut-report:
http://www.filehosting.org/file/details/518300/NUT.report
---
George Anchev
On Tue, Oct 27,
2010 Jan 09
2
problem with mailing (nut 2.4.1 and a powermust650 -> megatec_usb)
Hello guys
Yesterday i started do configure my Mustek Powermust650 with nut using
the megatec_usb driver. Everything works fine except for the mailing
when something happens. My upsmon looks like this:
MONITOR powermust650 at localhost 1 local controller master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
NOTIFYCMD /root/upsmailer
POLLFREQ 10
POLLFREQALERT 5
HOSTSYNC 15
2024 Feb 21
1
System keeps going into FSD mode after power on
Hello,
I am a new user of NUT and trying to wrap my ahead around a couple of
things. I installed NUT 2.7.4-13 from package on RasPi 4, running Raspbian
Linux 11 (bullseye). I have Cyberpower SL700U connected to it. For testing
I set battery.charge.low to 90, so I wouldn't have to wait a long time. See
all relevant config below.
First of all, what seems to happen is that UPS gets to the low
2011 Jun 08
2
Misconfiguration of Windows MSI installer 2.6.0-1 with my Powerware 5115 connected via USB port
Hello.
I've tried to configure Windows (complete port, Beta): Windows MSI installer
2.6.0-1 with my Powerware 5115 connected via USB port but have no luck.
Here is my config files:
*nut.conf:*
MODE = netserver
*ups.conf:*
[PW5115]
driver = bcmxcp_usb
port = notUsed
desc = "PowerWare 5115"
*upsd.conf:*
LISTEN 192.168.1.12 3493
*upsd.users:*
[monuser]
2014 Jan 21
3
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 3:16 AM, Rafa? Oleszek wrote:
> I would like to mention that MINSUPPLIES manipulation doesn't work. My nut version is : 2.2.2-4 (RHEL 5)
What do your configuration files look like? Setting MINSUPPLIES to 2 should work. You can run upsmon with a debug level of 3 or greater, and it will print the current and minimum "power value", which is what determines
2012 Apr 11
1
NOTIFYCMD doesn't work from Windows service
Hello dear all,
I try to use NUT for windows (not WinNUT), and stuck with launching NOTIFYCMD.
On any event marked as SYSLOG+WALL+EXEC syslog entry appears, popup
window appears, but NOTIFYCMD script doesn't run.
If I run upsmon.exe in cmd (i. e. not as a service) everything works fine.
Here is my upsmon.conf:
MONITOR central at 10.35.0.180 1 user password slave
MINSUPPLIES 1
SHUTDOWNCMD
2020 Jan 01
2
Belkin USB UPS Not Turning Off
Well it is the season for storms and power outages here in the US PNW. I
noticed that today when the power went out, NUT mostly did what I
hoped/wanted. But it did not actually turn off the UPS at all. The UPS
kept beeping and I had to turn it off manually.
I thought that NUT would handle this. But perhaps it cannot for my unit?
Or perhaps I have things improperly configured? Any suggestions?
2009 Dec 28
4
Megatec driver floods logs #2 & mail notifications
Hi there!
I'm a n00b NUT user trying to get it running on RHEL5 and actually do
something useful for me. Few questions:
1) I want it to notify me by email on power loss and power back events.
I can't find any sample scripts for this purpose... Where shall I look
for them?
2) So far, I've backported the package from Fedora and got my Ablerex
running (previously used with Upsilon /