2016 May 14
2
Low Battery event not occurring
> > battery.charge: 3 > battery.charge.low: 10 > battery.charge.warning: 30 > battery.runtime: 93 > battery.temperature: 32.9 > battery.type: PbAC > battery.voltage: 46.4 > battery.voltage.nominal: 48.0 Is it possible that battery.charge is really 30% rather than 3%? The 3016 protocol models have issues with scaling on some of the voltages and frequencies. You can see
2016 May 16
1
Low Battery event not occurring
Hi Charles, I made the change, and it still won't incite a poweroff: ========================================================================== [root at localhost ~]# upsc myups at localhost battery.charge: 76 battery.charge.low: 90 battery.charge.warning: 30 battery.runtime: 1811 battery.temperature: 31.9 battery.type: PbAC battery.voltage: 49.2 battery.voltage.nominal: 48.0 device.mfr:
2016 May 13
0
Low Battery event not occurring
I here is some information I could have provided previously. Here is what I am seeing: ==================================================================== Broadcast message from nut at localhost.localdomain (Fri May 13 22:31:35 2016): UPS myups at localhost on battery upsc myups at localhost battery.charge: 3 battery.charge.low: 10 battery.charge.warning: 30 battery.runtime: 93
2016 May 16
0
Low Battery event not occurring
Hi Charles, Thanks for the response! I don't believe the battery.charge is actually 30%. I watched the "battery.charge" go down from "100" to "3", so I can only assume this field to be "%". Here is what it currently looks like after charging over the weekend: ==================================================== [root at localhost ~]# upsc myups at
2020 Jul 22
1
AVRX750/500 issues
I wouldn't be surprised if they both use the same driver. I think they are essentially the same model, but with one having a slightly larger battery. My issue is primarily with the UPS turning back on after having shut off like it should. @Scott Colby if you take a look at the config files I posted in the github issue I created, perhaps that will give you some hints on your issue. Maybe
2020 Feb 18
2
UPS shuts down after restart
Hi Roger, Hi all,   > Does upsmon.conf specify a shutdown on LB? I think so. You mean SHUTDOWNCMD? The relevant parts of my upsmon.conf (notifications removed): MONITOR ups at localhost 1 upsmaster secret master MINSUPPLIES 1 SHUTDOWNCMD "/sbin/shutdown -h +0" POLLFREQ 5 POLLFREQALERT 2 HOSTSYNC 15 DEADTIME 40 POWERDOWNFLAG /etc/killpower RBWARNTIME 43200 NOCOMMWARNTIME 1800
2020 Feb 17
2
UPS shuts down after restart
An HTML attachment was scrubbed... URL: <http://alioth-lists.debian.net/pipermail/nut-upsuser/attachments/20200217/b486de30/attachment.html> -------------- next part -------------- A non-text attachment was scrubbed... Name: usbhid.zip Type: application/zip Size: 4031 bytes Desc: not available URL:
2020 Jun 28
2
AVR750U Low Power not Triggering Shutdown
On Sat, Jun 27, 2020, at 23:11, Manuel Wolfshant wrote: > On 6/28/20 5:54 AM, Scott Colby wrote: >> >> I'm not convinced this is the problem; I think that pfSense has an alternative way of running the NUT components: # ps aux | grep ups root 45456 0.0 0.1 6796 884 - Is 02:22 0:00.01 /usr/local/sbin/upsmon uucp 45751 0.0 0.1 6796 772 - S 02:22
2020 Feb 18
2
UPS shuts down after restart
>> But I noticed two other details: >> 1. I was a bit wrong with step 7 and 8 - Looks like the UPS is "OL CHRG" (according to display) at first but goes to battery ("OL DISCHRG" according to nut) right when the RasPi (and nut) is booting. >> 2. When I pull the plug of the RasPi after UPS went down before main power comes back (so between step 5 and 6), the UPS
2020 Jun 18
3
Low Battery Problems
Hello, I am having a heck of a time with false low battery alarms right now.  It has been going on for the last couple of months.  I originally started getting them with a UPS that was 1-2 years old so I thought it was time to change it out and buy a new one.  I'm still getting the false alarms with the brand new one.  The status is "OL LB" which is strange to me. I have a
2005 Oct 09
1
apc-hid tests with the new ups_status updates
Peter, Here are the transitions that I have tested with your latest changes (on the APC/Back-UPS ES 650): 1) OL ==> OB DISCHRG followed by OB DISCHRG ==> OL (no CHRG inbetween) 2) OL CHRG ==> OL 3) OL CHRG ==> OL CHRG LB (by manipulating battery.charge.low) 4) OL CHRG LB ==> OL CHRG (i.e. transition from below) 5) OB DISCHRG ==> FSD OB DISCHRG LB followed by proper shutdown In
2019 Jun 09
2
How to shutdown macOS / mac OSX from Network UPS Tools client - NUT
On Sun, 9 Jun 2019, Joe Gervasio wrote: > This question undermines my reading of the documentation.  I had thought that > these were separate things:  > >     SHUTDOWNCMD "/sbin/shutdown -u -h +1"  >     NOTIFYCMD /opt/local/sbin/upssched > > I had assumed that the SHUTDOWNCMD would be used by the Nut client (upsmon) to > shutdown the slave system,  and that
2023 Nov 27
1
APC Modbus support is finally here!
Jim Klimov <jimklimov+nut at gmail.com> > > I believe some fixes were applied to the branch since your report (most visibly, about battery time settings), are you in position to test how it behaves now? :) Hi: I got another ups for testing. so I test the new commit for both APC SRT3000XL and SMT2200RM2U. the results below: 1. I get the new attribute "ups.test.result" for
2023 Nov 27
1
APC Modbus support is finally here!
Jim Klimov <jimklimov+nut at gmail.com> > > I believe some fixes were applied to the branch since your report (most visibly, about battery time settings), are you in position to test how it behaves now? :) Hi: I got another ups for testing. so I test the new commit for both APC SRT3000XL and SMT2200RM2U. the results below: 1. I get the new attribute "ups.test.result" for
2020 Jul 22
3
AVRX750/500 issues
Thanks for chiming in @David Zomaya. Tripp Lite replaced my AVRX550U once thinking that the powering back on was a defective unit, but the replacement does the same thing. The SN on the first one is 2935AVHOM87BB00152. NUT has my model listed as protocol 2010, so that needs to be corrected to 2012, but I'm not sure if anyone is doing active development on it right now. I also have a
2014 Jan 21
3
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 3:16 AM, Rafa? Oleszek wrote: > I would like to mention that MINSUPPLIES manipulation doesn't work. My nut version is : 2.2.2-4 (RHEL 5) What do your configuration files look like? Setting MINSUPPLIES to 2 should work. You can run upsmon with a debug level of 3 or greater, and it will print the current and minimum "power value", which is what determines
2005 Oct 09
2
Re: apc-hid tests, ups_status updates
Arnaud, > first, even if your battery is full, and your ups is online, there is a > small amount of power drawn. So having always is CHRG status is normal. > In fact, these complementary status are more interesting for higher end > UPSs. > > second, these status need not to be handled like LB, as each one clears the > other. While LB had no pending event (!LB) before... >
2006 Sep 13
2
POWERDOWNFLAG (/etc/killpower) does not contain the upsmon magic string!!!
Hi to all, i install nut and it's work perfectly but when i start upsmon i recive the message: POWERDOWNFLAG (/etc/killpower) does not contain the upsmon magic string My upmon.conf contain: MONITOR myups@theseo 1 orion91 carlos81 master SHUTDOWNCMD "/sbin/shutdown -h +0" HOSTSYNC 15 POWERDOWNFLAG /etc/killpower FINALDELAY 5 My killpower scrit in /etc/killpower
2015 Mar 19
2
Brand new EATON 3S700DIN (mfr.date 09/28/14) doesn't wait for LB flag
Linux-2.4.28 libusb-0.1.8 nut-2.6.5 [+most recent drivers from GIT] - from tarball EATON 3S700DIN [mfr.date 09/28/14] ---------------------------------- ISSUES: I) Too many kernel logs: --- In /var/log/kernel.log usbdevfs: usb_submit_urb returned -28 In /var/log/daemon.log: usbhid-ups[744]: libusb_get_interrupt: No error usbhid-ups[744]: libusb_get_interrupt: error submitting URB: No space left
2006 Nov 15
1
Tripp Lite OMNI900LCD
I am having an issue running NUT and using an TrippLite OMNI900LCD. When I run ./upsdrvctl start I get : [player@V0002-S002 bin]$./upsdrvctl start Network UPS Tools - UPS driver controller 2.1.0 Network UPS Tools: 0.28 USB communication driver 0.28 - core 0.30 (2.1.0) Detected a UPS: Tripp Lite /TRIPP LITE UPS Using subdriver: TrippLite HID 0.1 (experimental) dstate_setflags: base variable