2014 Feb 10
0
BestPower Ferrups driver glitch with f commands
The problem will only affect newer firmwares on the BestPower FerrUPS 2.1kva units. Additional white-space was the issue. I added a if clause to the bestfcom driver to account for this without breaking what was there. Here is the patch:
diff -rupN release-orig/nut-2.7.1/drivers/bestfcom.c release-patched/nut-2.7.1/drivers/bestfcom.c
--- release-orig/nut-2.7.1/drivers/bestfcom.c 2013-07-31
2014 Feb 10
0
Patch for bestfcom driver
To deal with small model string differences that are present on the BestPower FerrUPS 2.1Kva ups, I have the patch below. The change in formatting seams to exist in firmware 9.28 and I think even older firmware.
The patch is against the 2.7.1 bestfcom driver. Please pardon any errors in my patch submission has I have only submitted a patch once or twice before. This patch should fix a situation
2014 Feb 10
2
BestPower Ferrups driver glitch with f commands
I did the testing you suggested, and it was indeed the whitespace. I added another if clause test to the function and everything seems to work. I have working driver that I will email a patch for this list. My coworker says the model ID is configurable though, so we will try that first, which would negate the need to patch the driver.
________________________________________
From: Charles Lepple
2014 Feb 07
2
BestPower Ferrups driver glitch with f commands
Greetings to you all,
We are attempting to use NUT to interface with a BestPower FerrUPS FE2.1KVA. We are using the bestfcom driver because the driver listed our UPS as supported. The driver fails, however, because "fc" commands do not exist on the unit.
We are running NUT v2.7.1 on CentOS 6.5 with the bestfcom driver. We setup a serial tap and see the UPS error out on the fc command
2013 May 11
1
Best Ferrups (bestfcom patch)
Hello,
I have a Best Ferrups 3.1KVA and I noticed that the percent battery voltage reported from upsc never gets above 69.9%. I believe there is a mistake in the driver. The battery percentage is calculated based on the High Battery Alarm Setpoint (59.6V) instead of the Ideal Voltage which is about 54V (4 batteries x 13.6V). I examined the source code and found that the variable fc.fullvolts is
2014 Feb 08
0
BestPower Ferrups driver glitch with f commands
On Feb 7, 2014, at 3:44 PM, Ritter, Nicholas wrote:
> Greetings to you all,
>
> We are attempting to use NUT to interface with a BestPower FerrUPS FE2.1KVA. We are using the bestfcom driver because the driver listed our UPS as supported. The driver fails, however, because "fc" commands do not exist on the unit.
There is a upsdrv_init_nofc() function, but it seems to be
2007 Dec 02
1
Driver bestfcom - Timing problem with Fortress LI1420
Hi,
my UPS is a Best Fortress LI1420 with the monitoring master running fedora 7.
I have to replace the manufacturer's software "Checkups II" because it's not
working with releases after fc4.
My choice is the nut package.
But it isn't just installing rpm's and configure the parameter files.
?
The first hurdle to take was realising the UPS doesn't send a prompt.
2008 Feb 06
2
Problem with bestfcom and old Ferrups
I have an old (1997) Best Ferrups (model FE18KVA) that I am trying to
monitor for the first time, but all the Best drivers fail to communicate
with it.
In ups_sync() in bestuferrups.c and bestfcom.c, the "time" command is
sent and a one-line response is read. However, on my UPS, that command
returns the current time and then prompts for a new time setting. I
worked around that by just
2008 Jun 13
2
Best Ferrups reporting uptime in minutes, not seconds
I had a power hiccup yesterday and a server connected to a Best Ferrups
18KVA shutdown. The problem is that the UPS is reporting remaining
runtime in minutes but nut treats it as seconds (so nut thought it only
had 46 seconds left).
Simple patch:
diff -urN nut-2.2.1-dist/drivers/bestfcom.c nut-2.2.1/drivers/bestfcom.c
--- nut-2.2.1-dist/drivers/bestfcom.c 2008-06-13 14:04:07.000000000 -0500
2018 Mar 19
2
Best Power FE700VA?
On 02/20/2018 06:16 PM, Charles Lepple wrote:
> Do you have a pinout for that cable?
Unsure, but after recent suggestions, it may be working.? Already had
NUT from SlackBuilds.org (SBo) installed, but reinstalled to add the
group:user.
> I forget if it is the default, but you might need to turn off the hardware and software flow control (minicom: Ctrl-A then letter O, "Serial port
2018 Mar 19
0
Best Power FE700VA?
On Mar 19, 2018, at 4:00 AM, David Melik wrote:
>
>> Then you can launch the driver with at least one "-D" flag:
>>
>> /usr/libexec/nut/bestfcom -a ups -D
>
> I thought there was a lot more to it than that, but after I ran that stuff, the driver outputs. However, /etc/rc.d/rc.ups initialization script might not do anything yet (only the command you gave,
2005 Aug 25
0
Is anyone working on the bestfcom driver ?
I've just started using nut , and one of my UPSes is a Best Ferrups 1.8kva
bestfcom seems to be the driver that would support it, but as currently in
2.0.2 it doesn't work on the FE1.8kv. I've done some hacking this afternoon
and have it basically working.
This is the only Best I have, so if anyone else is working on this, I was
hoping to co-ordinate so I don't break any
2018 Jan 21
0
Best Power FE700VA?
On Jan 21, 2018, at 1:12 AM, David Melik <dchmelik at gmail.com> wrote:
>
> I have an excellent old Best Power FE700VA but am suprised it's unlisted. I thought Best Power ones were for critical applications, mostly for POSIX-based (Unix, etc.) servers, so I want to run it on 64-bit Slackware GNU/Linux. I'm wondering why, or if it may be added in the future, or if there are
2005 Aug 30
1
Best Fortress LI660VA-Question(s)
Hi,
I recently got a Best Fortress LI660VA which was until then used on an
AS/400 System. It's quite old and even with minimal Load only keeps the
Line for a few seconds -- however, two new (Panasonic) Batteries cost
less than half of what a new UPS will cost and so I decided to keep it.
However, I'd like to run some Monitoring SW for the UPS. No Problem, I
found NUT and was impressed by
2018 Feb 19
2
Best Power FE700VA?
On 02/13/2018 03:49 AM, Charles Lepple wrote:
> On Feb 12, 2018, at 11:53 PM, David Melik wrote:
>
> On 01/21/2018 05:53 AM, Charles Lepple wrote:
>>> If you hook up a terminal emulator to the comms port (1200 baud, 8/N/1 unless stickers and/or configuration DIP switches indicate otherwise), and type "f" <return>, do you get a status line like one of the
2018 Feb 13
3
Best Power FE700VA?
On 01/21/2018 05:53 AM, Charles Lepple wrote:
> My understanding was that many of the older Best Power units were downstream of generators, and as such, full-blown power outages of both mains and generator power were not expected.
>
> That said, it might be that the "bestfcom" driver predates when we were actively collecting specific model names for the Hardware Compatibility
2018 Dec 25
3
APC Back UPS and Best Power FERRUPS?
Lately I got (used) an APC Back UPS Pro 1000 and Back UPS NS 1080. I got
an ethernet-to-USB cable from another UPS, but the Pro isn't detected
(with usbhid-ups.) I haven't tried the NS yet but it seems to not be on
the list though looks just like the Pro.
Some months ago I was discussing setup of a Ferrups 700VA. I got it to
work only with a command in rc.local, but not automatically
2018 Mar 20
2
Best Power FE700VA?
On 03/19/2018 04:49 AM, Charles Lepple wrote:
> The rc-style init systems typically want programs like the drivers to
> go into the background on their own (as the driver does without "-D",
> or when launched by "upsdrvctl start"). Other init systems like
> launchd or systemd will monitor the PID of the program to restart it
> if necessary, so they work best
2007 May 25
0
Patch -- SVN revision in the version string
This is the patch to include SVN revision level in version number displays.
There should be two enclosures; the patch itself and a new source file.
common/upsversion.c.
upversion.c defines a single function. upsversion(), that returns a version
string for display. Some Makefile trickery ensures that this file will
be recompiled whenever the project's SVN revision level has changed since
it
2018 Dec 26
0
APC Back UPS and Best Power FERRUPS?
On Dec 25, 2018, at 4:07 AM, David Melik wrote:
>
> Lately I got (used) an APC Back UPS Pro 1000 and Back UPS NS 1080. I got an [8P8C]-to-USB cable from another UPS, but the Pro isn't detected (with usbhid-ups.) I haven't tried the NS yet but it seems to not be on the list though looks just like the Pro.
>
There are a few different angles we can approach this one from. What