2013 Dec 06
0
Delayed UPS start up after shutdown?
Hi,
I own one a MGE Protection Center 675. You can change the
parameter ups.delay.start into your UPS to set the "Interval to wait
before (re)starting the load (seconds)"
use upsset to change the
value.
Regards,
Ren?
Le 2013-12-06 15:14, Angel Tsankov a ?crit :
> Hello.
>
> I am faced with a configuration where the OS (Debian
6.0.8) and the PC
> shut down before
2013 Dec 06
2
Delayed UPS start up after shutdown?
Hello, Ren?.
> You can change the parameter
> ups.delay.start into your UPS to set the "Interval to wait before
> (re)starting the load (seconds)"
>
> use upsset to change the value.
So far, the ups.delay.start parameter in my MGE Protection Center 675
has always been equal to the driver.parameter.ondelay parameter (which
equals the ondelay argument in ups.conf).
2013 Dec 06
1
Delayed UPS start up after shutdown?
> Le 2013-12-06 15:14, Angel Tsankov a ?crit?:
> ...if main power comes back within 10 seconds after the UPS has been
> shut down, the UPS will power up the PC but the latter will not start.
On Fri, 6 Dec 2013, Rene Garcia wrote:
> .... You can change the parameter ups.delay.start into your UPS to set
> the "Interval to wait before (re)starting the load (seconds)"
>
2013 Dec 24
0
Delayed UPS start up after shutdown?
Angel Tsankov wrote, On 12/24/2013 1:22 AM:
> On 12/06/2013 10:57 PM, Kris Jordan wrote:
> > [...]
>> (*) Some UPS's do provide extra options to determine when they will
>> restore power to load.
>
> That would be a nice feature.
>
> Anyway, it is a strange thing that I can set the waiting time for
> power to be restored if main power comes back before
2013 Dec 24
3
Delayed UPS start up after shutdown?
On 12/06/2013 10:57 PM, Kris Jordan wrote:
> [...]
> (*) Some UPS's do provide extra options to determine when they will
> restore power to load.
That would be a nice feature.
Anyway, it is a strange thing that I can set the waiting time for power
to be restored if main power comes back before offdelay has elapsed, but
the UPS ignores this setting if main power comes back after
2013 Dec 06
0
Delayed UPS start up after shutdown?
Angel Tsankov wrote, On 12/6/2013 12:31 PM:
> Hello, Ren?.
>
>> You can change the parameter
>> ups.delay.start into your UPS to set the "Interval to wait before
>> (re)starting the load (seconds)"
>>
>> use upsset to change the value.
>
> So far, the ups.delay.start parameter in my MGE Protection Center 675
> has always been equal to the
2013 Dec 25
2
Delayed UPS start up after shutdown?
On 12/25/2013 12:16 AM, Kris Jordan wrote:
> Angel Tsankov wrote, On 12/24/2013 1:22 AM:
[...]
>> I can see that my UPS (MGE Protection Center 675) has a parameter
>> ups.timer.start (currently holding the strange value of -10). Any idea
>> if this could help and how this parameter can be changed?
>
> in upsrw?
In upsc only. Here's the complete output:
2013 Dec 26
1
Delayed UPS start up after shutdown?
On 12/25/2013 11:42 PM, Kris Jordan wrote:
> Angel Tsankov wrote, On 12/25/2013 12:16 AM:
>>
>> What did you mean by "load.on.delay"?
>
> upscmd -l <ups>
>
> load.on.delay - Turn on the load with a delay (seconds)
Alright, but... how does this command work? Once it has been executed,
will the UPS wait the specified period before turning the load on
2013 Dec 25
0
Delayed UPS start up after shutdown?
Angel Tsankov wrote, On 12/25/2013 12:16 AM:
>
> What did you mean by "load.on.delay"?
>
upscmd -l <ups>
load.on.delay - Turn on the load with a delay (seconds)
----
ups.timer.shutdown: 0
ups.timer.start: 0
are my upsc values. I'll have to pay more attention to those next time I
test.
2010 Jan 22
1
Eaton / MGE Ellipse MAX 600 USBS and nut
Hi there,
I've replaced yesterday my old UPS with a brand new "Eaton Ellipse MAX 600
USBS".
I've choosed the Eaton (previously MGE) both because I've always been
extremely satisfied with MGE UPSes of all kinds at work, and because of the
involvement of MGE (with Arnaud) in nut development, which made me quite sure
that I would have no trouble with an Eaton (MGE) UPS and
2018 Oct 04
2
after power outage and proper shutdown, UPS turns on before power returns
On Tue, Oct 2, 2018 at 3:59 PM Charles Lepple <clepple at gmail.com> wrote:
>
> On Sep 27, 2018, at 6:59 PM, Gabriel <jarod125 at gmail.com> wrote:
> >
> > Hi,
> >
> > I'm struggling with a peculiar issue with my UPS. After a power
> > outage, the devices powered by it properly shut down via nut.
> > Eventually, the UPS also goes down.
2018 Mar 02
1
Work around for power recycling after shutdown.return - TSSHARA UPS - nutdrv_qx driver - megatec protocol
2018-02-28 21:11 GMT+01:00 Jairo Rotava <jairo.rotava at gmail.com>:
> Hello,
>
> I think that on this file nutdrv_qx_megatec.c the definition for
> shutdown.stayoff may be wrong. In the file the definition is "S%sR0000\r"m
> while on the megatec protocol description (
> http://networkupstools.org/protocols/megatec.html) the command is just
> "S%s\r".
2018 Sep 27
2
after power outage and proper shutdown, UPS turns on before power returns
Hi,
I'm struggling with a peculiar issue with my UPS. After a power
outage, the devices powered by it properly shut down via nut.
Eventually, the UPS also goes down. Power is still out, however,
roughly 40 seconds after the UPS shut down, it turns back on and it
starts supplying power to the load, thus turning back on the devices
attached to it. This is obviously not something I want. In
2014 Apr 15
3
CyberPower CP1500PFCLCD and NUT upsset.cgi
Since there is apparently no immediate solution to upsstats.cgi not
reading the output voltage correctly, I have moved on to trying to use
upsset.cgi. To recap the UPS is a CyberPower CyberPower CP1500PFCLCD
UPS running on a headless server running Slackware 14.1 with the
3.10.7 kernel. The version of NUT is 2.71 and I am using usbhid-ups
for communication with the UPS
The problem is that when
2006 Aug 12
4
Will MGE-UPS Ellipse USBS auto shutdown?
I have an Ellipse USBS connected via serial cable to a CentOS 3 box.
Do I need to turn off the UPS as the final stage of shutdown, or will
the UPS power itself off, before the battery reaches a level to low to
safely recharge from?
I notice there is the option for the UPS to turn itself off (and on
again) unattended if power is restored during shutdown, but there
doesn't seem to be an option
2013 Jul 31
0
nut package with Riello UPS support
On Jul 31, 2013, at 3:36 AM, Pavel Potcheptsov (EKTOS) wrote:
> Does it looks good?
I think so - 40.8 volts with a nominal of 36 volts is 13.6 V/cell, which agrees with the 100% charge value. Hopefully the line voltages and frequency make sense for your region.
> Another question what does riello experimental driver warning mean?
We add that to all new drivers. This driver was written by
2013 Jul 31
2
nut package with Riello UPS support
Thank you very much!!
I have tried configure downloaded source with
# ./configure --with-user=_ups --with-group=_ups
--with-statepath=/var/db/nut/
and then build driver and copy again. but this doesn't help (driver pid
still in the /var/state/ups).
Maybe I must add more arguments to change driver's pid location, but I did
next, I changed this argument in openbsd ports:
# pkg_delete nut
#
2018 Feb 28
2
Work around for power recycling after shutdown.return - TSSHARA UPS - nutdrv_qx driver - megatec protocol
Answers bellow.
2018-02-28 1:41 GMT-03:00 Daniele Pezzini <hyouko at gmail.com>:
> 2018-02-27 14:51 GMT+01:00 Jairo Rotava <jairo.rotava at gmail.com>:
> > Hi,
> >
> > I had an issue where after returning the power from a shutdown.return the
> > ups would do another shutdown.return during the boot, and kept this
> forever.
> > After some
2007 Jun 02
1
CGI-BIN for Nut
I'm access nut online via localhost. But I have the following problems.
When I click on Statistics I get cannot open /etc/hosts.conf. When I click
on settings I get: Error: Can't open upsset.conf to verify security
settings.
Refusing to start until this is fixed.
I have .htaccess in cgi-bin with the following:
<Files upsset.cgi>
deny from all
allow from 127.0.0.1
</Files>
2006 Jul 13
2
MGE Pulsar Extreme - restart problem
Hello,
looking for replacements for some older Powerware equipment I found the MGE
Pulsar Extreme 1000C and I'm currently testing one with nut-2.0.3 on a
self-brewn i386-linux.
Upto now everything seems to work fine - except I can't get the power outlets
switching on again after mains returns. As this works with Personal
Solution-Pac 2 on W2k I thought that there might be a way to