NUT on openSUSE 12.3 requires additional systemd service unit
OpenSUSE 12.3 has fully embraced systemd, but to get NUT working correctly now requires some further systemd engineering in addition to the usual NUT configuration files. A new systemd service unit is needed to power off the UPS. The service unit consists of a new file /etc/systemd/system/ups-delayed-shutdown.service [Unit] Description=Initiate delayed UPS shutdown
2013 Aug 14
0
NUT on openSUSE 12.3 requires additional systemd service unit
On 08/10/2013 11:43 PM, Roger Price wrote: > OpenSUSE 12.3 has fully embraced systemd, but to get NUT working > correctly now requires some further systemd engineering in addition to > the usual NUT configuration files. A new systemd service unit is needed > to power off the UPS. > > The service unit consists of a new file > /etc/systemd/system/ups-delayed-shutdown.service
2009 Nov 15
3
two MGE Ellipse 1500 ups via usb
Hi, I've got two MGE Ellipse 1500 UPS connected via usb to an ubuntu jaunty system with nut and libupsclient1 2.4.1-2ubuntu4. As soon as I start the driver for the second one, they start fighting each other and I get no data. I found an older post to this list that said: If you want to monitor multiple UPSes through usbhid-ups, you *must* make sure that each one can be uniquely identified
2015 Jan 07
2
NUT configuration with APC CS650 and ESXi host
Hello, I have decided to upgrade my home server by turning it into an ESXi host and have also added an APC CS650 UPS. My plan was to have NUT version 2.6.4 running in a Debian 7.7.0 virtual machine, NUT installed using apt. I configured NUT to run as a netserver, installed the ESXi nut .vib, configured the shutdowncmd in the VM to do nothing, so that the ESXi host would close that virtual machine
2015 Jan 09
0
NUT configuration with APC CS650 and ESXi host
On Jan 7, 2015, at 6:11 PM, DatGingerCat <dat.ginger.cat at gmail.com> wrote: > Hello, > > I have decided to upgrade my home server by turning it into an ESXi host and have also added an APC CS650 UPS. > My plan was to have NUT version 2.6.4 running in a Debian 7.7.0 virtual machine, NUT installed using apt. > I configured NUT to run as a netserver, installed the ESXi nut
2015 Jan 11
1
NUT configuration with APC CS650 and ESXi host
The serial number looks completely different, but the firmware seems to be the same. Pasting upsc output: battery.charge: 80 battery.charge.low: 10 battery.charge.warning: 50 battery.date: 2013/12/04 battery.mfr.date: 2013/12/04 battery.runtime: 1781 battery.runtime.low: 120 battery.temperature: 29.2 battery.type: PbAc battery.voltage: 13.5 battery.voltage.nominal: 12.0 device.mfr: American Power
2015 Jan 27
0
CyberPower BR850ELCD ignores offdelay and turns itself back on while still on battery
On Jan 22, 2015, at 9:53 AM, Sebastian Hosche <sebastian.hosche at web.de> wrote: > Hi Charles, > > Thanks so much for your quick and detailed reply! I've added my answers and details inline. Sorry this reply wasn't as quick. > On 22.1.2015 04:46, Charles Lepple wrote: >> On Jan 21, 2015, at 9:15 AM, Sebastian Hosche <sebastian.hosche at web.de> wrote:
2013 Aug 10
0
NUT on openSUSE 12.3 requires additional systemd service unit
On Aug 10, 2013, at 5:43 PM, Roger Price wrote: > OpenSUSE 12.3 has fully embraced systemd, but to get NUT working correctly now requires some further systemd engineering in addition to the usual NUT configuration files. A new systemd service unit is needed to power off the UPS. > > The service unit consists of a new file /etc/systemd/system/ups-delayed-shutdown.service > >
2010 Aug 20
2
APC Smart-UPS X 1500 Restart Issue.
APC Smart-UPS X 1500 Restart Issue. Hi All, I have installed nut-2.4.3. I have manually modified the files apc-hid.c and udev-rules to support 5G APC UPS. I took sample code from the 2.5 development tree. Shutdown process is working very well -- upsmon creates the file /etc/killpower - shutdown script checks for the file and issues /sbin/upsdrvctl shutdown - UPS cuts the power off. All
2010 Aug 20
2
APC Smart-UPS X 1500 Restart Issue.
APC Smart-UPS X 1500 Restart Issue. Hi All, I have installed nut-2.4.3. I have manually modified the files apc-hid.c and udev-rules to support 5G APC UPS. I took sample code from the 2.5 development tree. Shutdown process is working very well -- upsmon creates the file /etc/killpower - shutdown script checks for the file and issues /sbin/upsdrvctl shutdown - UPS cuts the power off. All
2015 Mar 13
0
Problems with NUT 2.7.2 on CentOS 7 and using the Mini-Box OpenUPS
On Mar 13, 2015, at 10:14 AM, Rob Groner <rgroner at RTD.com> wrote: >> >> The documentation isn't explicit about this, but 'upsdrvctl shutdown' is >> meant to be run after all of the other processes on the system have been >> killed, real filesystems have been unmounted, and the kernel shutdown >> syscall is about to be called. Usually the init
2008 Feb 20
3
Important regression in usbhid-ups (r1113)
while finishing some work on the HAL integration (I'm now mapping DBus method with NUT commands, to allow at least the final UPS poweroff), I was horrified to realize (and so late) the changes in usbhid-ups->upsdrv_shutdown(). We've lost a lot there, but making a generic code, instead of keeping the subdrivers delegation. For example, the shutdown.return command (which is or should be
2020 Feb 18
2
UPS shuts down after restart
Hi Roger, Hi all,   > Does upsmon.conf specify a shutdown on LB? I think so. You mean SHUTDOWNCMD? The relevant parts of my upsmon.conf (notifications removed): MONITOR ups at localhost 1 upsmaster secret master MINSUPPLIES 1 SHUTDOWNCMD "/sbin/shutdown -h +0" POLLFREQ 5 POLLFREQALERT 2 HOSTSYNC 15 DEADTIME 40 POWERDOWNFLAG /etc/killpower RBWARNTIME 43200 NOCOMMWARNTIME 1800
2015 Jan 22
2
CyberPower BR850ELCD ignores offdelay and turns itself back on while still on battery
Hi Charles, Thanks so much for your quick and detailed reply! I've added my answers and details inline. On 22.1.2015 04:46, Charles Lepple wrote: > On Jan 21, 2015, at 9:15 AM, Sebastian Hosche <sebastian.hosche at web.de> > wrote: > >> First issue: whatever I set as the offdelay, seems to be ignored and >> the UPS just cuts the power about 2sec after receiving
2016 Oct 05
2
UPS Shutdown
I'm trying to better understand OffDelay and OnDelay: http://networkupstools.org/docs/man/usbhid-ups.html#_extra_arguments My server requires ~3? minutes to shut itself down. Considering this I'm comfortable setting OffDelay to 300 (five minutes). How does this work in conjunction with the UPS hardware? Does NUT immediately send a command to the UPS to wait for 300 seconds and then shut
2018 Aug 21
2
APC Back-UPS CS 650 offdelay and startdelay
Welcome, Acctualy, I'm try to poweroff my ESXi (6.7). Virtual machine with Ubuntu and redirected USB port with APC Back UPS CS 650, have nut-server and send info to ESXi. When battery is low, ESXi poweroff gracefully all VM and same ESX go down. This work fine and don't have any problem. But important to me, is set to more offdelay on UPS than the default 60 sec. (cut off power socket
2006 Sep 13
2
POWERDOWNFLAG (/etc/killpower) does not contain the upsmon magic string!!!
Hi to all, i install nut and it's work perfectly but when i start upsmon i recive the message: POWERDOWNFLAG (/etc/killpower) does not contain the upsmon magic string My upmon.conf contain: MONITOR myups@theseo 1 orion91 carlos81 master SHUTDOWNCMD "/sbin/shutdown -h +0" HOSTSYNC 15 POWERDOWNFLAG /etc/killpower FINALDELAY 5 My killpower scrit in /etc/killpower
2007 Feb 06
9
Shutdown problem with Geek Squad GS1285U
Nut will monitor the ups and shutdown Linux when the ups goes to low battery as it should. But the UPS is not shut down so the system will restart when the power is restored. If I switch the UPS off , restore power and switch the UPS on the system will restart. I have not been able to get nut to switch the UPS off after it brings the system down. I can get the UPS to switch off with upscmd
2009 May 25
0
FreeBSD installation procedure (updated)
The purpose of this posting is to summarize the FreeBSD installation procedure from the beginning till the very end. 1. Follow the instructions provided in the How-To prepared by Thierry Thomas (http://people.freebsd.org/~thierry/nut_FreeBSD_HowTo.txt). Please note the following: a) if you are using an USB device, as of NUT 2.2 usbhid-ups completely replaces the legacy hidups driver and provides
2016 Oct 06
5
UPS Shutdown
> > How does this work in conjunction with the UPS hardware? Does NUT > > immediately send a command to the UPS to wait for 300 seconds and then > > shut itself down, thereby allowing the server enough time to safely > > shut itself down as well? > > Yes. Very good, thank you. > The command is "upsdrvctl shutdown". That's what I thought, but I