Displaying 20 results from an estimated 600 matches similar to: "several problems with Powercom BNT-500AP"
2013 Jun 10
2
several problems with Powercom BNT-500AP
I took the log. Here's what happened.
Broadcast Message from nut at rasp
(somewhere) at 16:18 ...
UPS BNT500AP at localhost battery needs to be replaced
occurred when for the first time value "1" was read as "UPS.PowerSummary.PresentStatus.NeedReplacement", on this line:
6409.240690 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x0a,
2013 Jun 11
0
several problems with Powercom BNT-500AP
[I am CC'ing Alexey from Powercom in case he has seen any of these issues with the Raspberry Pi hardware.]
On Jun 10, 2013, at 1:05 PM, M?rti?? Pu??tis wrote:
> I took the log. Here's what happened.
> Broadcast Message from nut at rasp
> (somewhere) at 16:18 ...
> UPS BNT500AP at localhost battery needs to be replaced
>
> occurred when for the first time value
2013 Nov 27
0
several problems with Powercom BNT-500AP
Hello.
It's been a while since I started this topic. I've finally tested it on Linux desktop PC.
Nut version 2.6.4-2.3
Basically the behavior is the same as on raspberry pi. It reports "battery needs to be replaced" regularly and I got "on battery" message
114107.780504 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Input, ReportID: 0x0a, Offset: 2, Size: 1,
2013 Jun 08
0
several problems with Powercom BNT-500AP
On Jun 8, 2013, at 12:57 PM, M?rti?? Pu??tis wrote:
> I'll take a longer driver log. This page (http://www.networkupstools.org/support.html) says that to take a driver log NUT should be stopped, so I won't be able to tell when these events occurred within a driver log.
Hmm, I didn't realize it said that, but I think that's to prevent having two copies of the same driver
2013 Jun 08
2
several problems with Powercom BNT-500AP
Thanks for the support.
Here's list of when transition to battery with return to utility power within a few seconds occurred in last few days:
Wednesday
1:41
11:48
11:54
12:59
13:42
14:42
18:13
18:14
Thursday
5:23
Friday
5:12
7:39
7:43
Saturday
7:34
Here's list of when messages that battery needs replacement occurred:
Wednesday
20:34
Thursday
9:07
23:09
Friday
18:25
Saturday
7:32
19:47
2013 Jun 08
0
several problems with Powercom BNT-500AP
On Jun 5, 2013, at 11:49 AM, M?rti?? Pu??tis wrote:
> Driver debug output attached.
The debug output looks normal (many devices do not implement the interrupt pipe; hence, the timeouts). Unfortunately, we might need the log over a longer period of time, including your observations as to when various events occurred (such as transitions to battery).
--
Charles Lepple
clepple at gmail
2011 Jan 13
0
[NUT]updated powercom driver for powercom BNT-500AP
Hi,
2010/12/27 ??? <pointbre at naver.com>
> First of all, thanks for your effort to NUT Project,
> I'm developing remote monitoring solution for many devices based on linux
> server.
> In field test, we reached the power shutdown problem which may cause the
> crack of linux file system.
> I search the solution and find NUT project and i'm very glad that NUT
>
2010 Feb 04
0
Powercom BNT-800AP
While fundamentally working, I'm having a few issues with the driver...
The default voltage quads (for every model) are way off... Showing
~95v when it should be ~117V. I've changed the 4th/final coefficient
to +5.0, but haven't tested extensively (with fluctuating voltages).
The input/output voltage appears to be swapped _most of the time_.
When doing a battery test, or when
2017 May 17
2
Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
Good Day Roger
AA. notice that during the test, you have little or no load, since despite
being in state OB
DISCHRG the battery.charge is still 100. It's best to perform such tests
with a dummy load
such as a table lamp and an old fashioned incandescent 100 watt bulb.
==> Yes. I got it and try to ascend load as below results
dinow-All-Series:~# upsc pcmups
Init SSL without
2017 May 17
1
Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
Good Day Roger
AA. notice that during the test, you have little or no load, since despite
being in state OB
DISCHRG the battery.charge is still 100. It's best to perform such tests
with a dummy load
such as a table lamp and an old fashioned incandescent 100 watt bulb.
==> Yes. I got it and try to ascend load as below results
dinow-All-Series:~# upsc pcmups
Init SSL without
2017 May 16
2
Fw: [Nut-upsdev] POWERCOM-UPS-USB : UPS Shutdown
Good Day Roger Price
AA. Hi, Normally one would expect the UPS to disconnect it's power outlets
after the default ups.delay.shutdown = 20 seconds.
==> I got it. I tried to command "upsdrvctl shutdown" on both line-mode and
battery-mode
==> But ups do not disconnect its outlets power
-----------------------------------------------------------------------------------
BB.
2006 Jul 08
0
Powercom BNT-600AP and NUT (powercom driver)
Hello,
I'm new there. I bought an UPS Powercom BNT-600AP. It's compatible
in NUT with driver powercom and protocol type KIN1500AP.
But I have a simple problem: the 'upsc' shows wrong values in
battery.charge (maybe in other rows also /ups.load, voltages?/) - if
battery is 100% charged it shows only 92.6% or 93.0%.
I thing I have wrong values in driver parameters: batteryPercentage,
2005 Jul 06
0
Powercom BNT-1500AP
Hey all,
Does anybody know there is a full working setup for the PowerCom
BNT-1500AP. I got some stuff working with the Powercom driver and the
type set to "KIN1500AP". But it seems that there is still missing
usablity. I was wondering if anybody found any better configs?
---- excerpt of ups.conf
[AVR1500]
driver = powercom
port = /dev/ttyS0
desc =
2006 Apr 21
1
Powercom BNT-1200AP
Hello
I have UPS Powercom Black Knight Pro 1200 (BNT-1200AP)
I try to use nut, but powercom driver not understand my model
Ok, i try to use type KIN1500AP and it's work
But powercom driver can't set UPS's shutdown delay time
Also i have powercom's original program (upsmon), and this program can do it
What can i do for help to add this function to nut's powercom driver?
For
2012 Nov 13
1
PowerCom BNT-600AP on ubuntu 12.04.1 AMD64
Hello people,
I use a BNT-600AP from PowerCom, and on driver loading (nut service
start) the UPS goes off so I cannot use nut as service as the computer
goes off with the UPS.
When the computer is not using the UPS, but still connected, I see that
the UPS goes off for a very short time, does battery check and goes on
again.
I don't know how to deal with this issue as I cannot use my UPS
2009 Jul 27
1
Powercom BNT-1000CS
Hello. I have recently purchased a Powercom BNT-1000CS(Black Knight CS).
I am new to NUT(and am not a programmer), but I have noticed that this
model does not work with NUT. I am willing to provide details about this
UPS for anyone who would like to add support for it(i dont know how to
get much info though, so you'll have to tell me how). For starters, this
is what happens when I do
2017 Apr 26
0
Powercom BNT-2000AP(USB)
Hello all!
Some days ago we received new UPS?Powercom BNT-2000AP with USB interface to replace an old staff and I've spent three last days trying to connect it with NUT. I have a FreeBSD 8.4 box with NUT 2.7.2.
# dmesg|grep -i powercom
ugen0.3: <POWERCOM Co.,LTD> at usbus0
uhid0: <POWERCOM Co.,LTD HID UPS Battery, class 0/0, rev 1.10/0.01, addr 3> on usbus0
uhid0: <POWERCOM
2010 Mar 24
2
Powercom RS232 driver improvement/rewrite
Hello all,
Last week I rescued and UPS from the trash (it's really amazing the
kind of things you can find in the trash of the university research
labs). No manual, no cd, no cables, just the unit. It's name is
"Blizzo 500", and blizzo was just the rebranding of a spanish reseller
which has been out of the scene for nearly two years now, at least
according to the wayback
2007 Jan 18
1
Nut with Powercom iCute ICT-530U (USB)
Hi!
Is there any user of nut having this type of UPS? (
http://www.pcmups.com.tw/product/iCute.html)
It works nice under windows and also is detected under Linux and installed
as USB HID device. There is problem however, as the software provided by its
manufacturer (http://www.pcmups.com.tw/download/Download/UPSMON_USBV091.zip)
doesn't seem to comunicate with the UPS at all. It shows messages
2013 Apr 28
0
PowerCOM BNT-1000AP HID instant commands patch
Hello,
Got PowerCOM BNT-1000AP, usb id 0d9f:00a6, firmware FW4.A6
nut 2.4.3 on debian stable shows only two instant commands:
beeper.toggle - Toggle the UPS beeper -- not working
test.battery.start.quick - Start a quick battery test -- works ok.
No load and shutdown commands.
Trying svn trunk version, with the same results.
Debug output shows the problem:
0.035558