2014 Jan 14
0
Unable to detect an APC Smart protocol UPS. Windows. APC Smart protocol driver 3.04 (2.6.5-3723:3731M)
On 2014-01-14 10:12, dstrr wrote: > Hello. > Trouble to communicate with APC SmartUPS via serial port. > UPS connected to the com1 port on windows host. > Communication witch hyperterm works well. > There is a log: > > YSM > ^ASmart-UPS SC1000 > n5S0713T63247 > m03/29/07 > L240.0 > B27.10 > > apcupsd also can communicate with the UPS and works well. >
2009 Jul 09
1
apcsmart and dual environmental sensors
Hi, We have a several AP9612TH environmental cards (they have 2 probe connectors) inserted into our APC UPS devices which monitor temperature and humidity. The apcsmart nut module knows how to query the ambient.temperature and ambient.humidity using the 't' and 'h' commands of the UPS (refer to apcsmart.h). The results of the 't' and 'h' commands are from probe 1.
2011 Mar 05
19
[RFC apcsmart V3 00/18] apcsmart driver updates
Sorry for a bit longer delay than I anticipated, I was stuffed with the work. This is the next iteration of the patch adding some functionality to apcsmart driver, and relying on 'ignorelb' recently added. Follow up from previous thread: http://www.mail-archive.com/nut-upsdev at lists.alioth.debian.org/msg02331.html Main differences is that V3 is split into many small patches, so the
2013 Jan 30
3
bug report: apcsmart (WIN) 940-0024C connect fail, problem with command 'E'
Dear Ladies and Gentlemen, I have several old, yet functioning APC Smart-UPS (Model 600LS, Part AP600I, Firmware 6JI, no EEPROM, from 1991). They are not supported by Powerchute any more. I run NUT 2.6.5-4 on Windows XP SP3. I use COM1 port with cable 940-0024C. The connection fails with APC Smart protocol driver 3.0 (2.6.3-3534:3540M), APC command table version 3.0 or higher - it works with APC
2011 Mar 12
2
[RFC/PREVIEW] Move apcsmart driver to canonical processing + minor stuff
Inital tests with two apc units (2005 and pre-2000) seem to go well. See commit message for details. I'll add more detailed rationale after getting some sleep :) Michal Soltys (1): apcsmart: switch processing to ICANON + minor fixes drivers/apcsmart.c | 270 +++++++++++++++++++++++++++++++++++----------------- drivers/apcsmart.h | 127 ++++++++++++++++--------- 2 files changed, 267
2011 Mar 21
2
apcsmart question
Before I start any commits. In patch 2/18 - http://lists.alioth.debian.org/pipermail/nut-upsdev/2011-March/005299.html Two "custom" commands slipped in: ups.firmware.old and shutdown.return.grace. In 18/18 I tried to rename them and add remainig commands for "hackish" shutdown methods, to make them easily callable through e.g. upscmd (for example for testing). Is it
2014 Jan 14
2
Unable to detect an APC Smart protocol UPS. Windows. APC Smart protocol driver 3.04 (2.6.5-3723:3731M)
Hello. Trouble to communicate with APC SmartUPS via serial port. UPS connected to the com1 port on windows host. Communication witch hyperterm works well. There is a log: YSM ^ASmart-UPS SC1000 n5S0713T63247 m03/29/07 L240.0 B27.10 apcupsd also can communicate with the UPS and works well. running apcsmart -a ups gives the following: com1: device reports different attributes than what were set
2008 Sep 05
0
Re: apcsmart and ambient data (was: NUT and MonAMI
Hi Paul, Aha - we have both found the same. I am referring to your post from: http://lists.alioth.debian.org/pipermail/nut-upsdev/2006-November/001344.html Looking at the source code the temp value is obtained by querying the following OID: #define APCC_OID_IEM_TEMP ".1.3.6.1.4.1.318.1.1.10.2.3.2.1.4.0" notice that the OID ends with .0 (index zero). Well, looking at the
2008 Sep 08
1
apcsmart and ambient data
Perhaps someone else could confirm this, I have an APC UPS with a built-in network management card with environmental sensor for temp/humidity. The OID index for the sensors appears to be .1 (the last component for each of the OIDs listed below). The original source code has them at .0 drivers/apccmib.h #define APCC_OID_IEM_TEMP ".1.3.6.1.4.1.318.1.1.10.2.3.2.1.4.1" #define
2009 May 07
1
Findings of dual APC UPS sensor attachments
Hi, We have several APC Smart UPSes (serial port/apcsmart) with the APC Temp/Humidity sensor cards (AP9612TH). The sensor cards have 2 plugs for 2 separate sensors. So far, we have only used one of the sensors in conjunction with the apcsmart module from nut. This has been working great. Example output: [nut at nut]# upsc APC11 ambient.humidity: 037.2 ambient.humidity.alarm.maximum: NO,NO
2011 May 27
0
quick update
Hi Michal, I've cc'ed -upsdev, since some info could be interesting for everybody. 2011/5/27 Michal Soltys <soltys at ziu.info> > On 11-05-25 09:35, Arnaud Quette wrote: > > Hi Michal, > > > > 2011/5/25 Michal Soltys <soltys at ziu.info <mailto:soltys at ziu.info>> > >(...) > > > > I'm preparing larger patchset with
2007 Jun 04
2
APCsmart serial port problem
I have a new APC Smart-UPS SUA2200RM2U. I've had no success with the manufacturer's PowerChute software and smart signaling, so I have decided to try NUT. The smartups driver can't make contact through the serial port. Since this is rack-mounted, it comes with a 940-1524 serial cable. As far as I can tell, this is supposed to work with smart signaling. Here's my ups.conf:
2013 Aug 10
0
apcsmart dev branch
On Aug 9, 2013, at 7:18 AM, Michal Soltys wrote: > I'm still a bit reluctant to merge it without a bit wider exposure, so if anyone has a possiblity to test it with some apc units - any feedback would be most welcome. Apparently, a lot of people are using NUT via packages, so: * users might not want to build from source if things are working * the packagers might not pick up a 2.7.x
2011 Jun 28
1
[nut-commits] svn commit r3071 - branches/apcsmart-dev/drivers
Citeren Michal Soltys <msoltyspl-guest at alioth.debian.org>: > Log: > apcsmart: allow tearing down/setting up serial connection during > normal activity; If this is needed at all (why?), I don't think this should be handled at driver level, but this would need to be in the serial.c library. Opening/closing a serial port is independent from the protocol used (no data
2011 Jan 18
1
apcsmart.c question
Hi, I started updating smart driver with a few things I've been missing. While going through the source: - in upsdrv_shutdown(), there're loads of printfs - they kinda look like a leftover from older debug times. Shouldn't they be changed into upsdebugx() or upslogx() ?
2012 Oct 23
1
apcsmart and #311678 feature request thoughts
https://alioth.debian.org/tracker/?func=detail&atid=411544&aid=311678&group_id=30602 I wanted to do it somewhat more flexibly/elegantly, so this is what I've been thinking about (or rather sitting on mostly implemented piece, still needing some testing though): - any variable that may include multiple data, would be (during runtime) split into appropriate *.N.* sets; for
2010 Oct 28
0
[nut] question regarding potential new smart driver or patches for existing apcsmart driver
Hi Michal, I'm cc'ing the NUT development mailing list. you should also subscribe to it. 2010/10/28 Michal Soltys > Greetings > > I have loads of relatively old smart upses that I currently control using a > bit patched version of apcupsd - the reason for those patches is the age of > the upses - roughly 10 years old+, which are can be a bit tricky to control. > From
2009 Feb 27
0
support for APC Matrix 5000, vintage 12/00 (was: NUT apcsmart driver - firmware addition)
Hey Jarett, 2009/2/24 <jarett.stevens at usermail.com> > After upgrading to the 2.4.1 version, I wasn't able to read as many > variables from my UPS. After a bit of experimentation, I determined that > the firmware on my UPS was different than what is currently in the > apcsmart driver, though it had worked before. I located my firmware > version (5ZM), and added in
2009 Jun 25
1
Runaway apcsmart process
On several occasions I have seen the apcsmart process runaway using 100% CPU while filling my syslog partition by logging the following syslog entries at an incredible rate. I have seen up to 21,800 log entries PER SECOND of the following nature: --[snip]-- Jun 25 10:06:38 servername apcsmart[4012]: Communications with UPS lost: Communications with UPS lost - check cabling Jun 25 10:06:38
2007 Jul 31
1
Proposed apcsmart driver patch
G'day y'all, Here's a tiny patch set for drivers/apcsmart.c and drivers/apcsmart.h. Adds APC SmartUPS 1250 ("8QD" case) + 940-0024C recognition to apcsmart. (Unpatched apcsmart.c v1.99.8 misidentifies the SmartUPS 1250 as a "dumb" UPS.) For NUT 2.0.5+. NUT 2.0.5: Patches apply successfully. Builds successfully. Works as expected under Ubuntu 7.04. NUT 2.2: