Steffen Plotner
2008-Sep-05 02:44 UTC
[Nut-upsdev] Re: apcsmart and ambient data (was: NUT and MonAMI
Hi Paul, Aha - we have both found the same. I am referring to your post from: http://lists.alioth.debian.org/pipermail/nut-upsdev/2006-November/001344.html Looking at the source code the temp value is obtained by querying the following OID: #define APCC_OID_IEM_TEMP ".1.3.6.1.4.1.318.1.1.10.2.3.2.1.4.0" notice that the OID ends with .0 (index zero). Well, looking at the snmpwalk below: PowerNet-MIB::iemStatusProbeNumber.1 = INTEGER: 1 PowerNet-MIB::iemStatusProbeName.1 = STRING: "Int Sensor" PowerNet-MIB::iemStatusProbeStatus.1 = INTEGER: connected(2) PowerNet-MIB::iemStatusProbeCurrentTemp.1 = INTEGER: 32 I see that the index is 1 and not 0, which is why we don't see the temperature probe's values. Fixing the underlying problem is much harder. It seems to me that we need to 'walk' the mib structure to find the data. Have you resolved the issue? Steffen ________________________________ Steffen Plotner Systems Administrator/Programmer Systems & Networking Amherst College PO BOX 5000 Amherst, MA 01002-5000 Tel (413) 542-2348 Fax (413) 542-2626 Email: swplotner at amherst.edu ________________________________ -------------- next part -------------- An HTML attachment was scrubbed... URL: http://lists.alioth.debian.org/pipermail/nut-upsdev/attachments/20080904/6270bb60/attachment.htm