2014 Jan 14
2
Unable to detect an APC Smart protocol UPS. Windows. APC Smart protocol driver 3.04 (2.6.5-3723:3731M)
Hello.
Trouble to communicate with APC SmartUPS via serial port.
UPS connected to the com1 port on windows host.
Communication witch hyperterm works well.
There is a log:
YSM
^ASmart-UPS SC1000
n5S0713T63247
m03/29/07
L240.0
B27.10
apcupsd also can communicate with the UPS and works well.
running apcsmart -a ups gives the following:
com1: device reports different attributes than what were set
2014 Jan 14
0
Unable to detect an APC Smart protocol UPS. Windows. APC Smart protocol driver 3.04 (2.6.5-3723:3731M)
On 2014-01-14 10:12, dstrr wrote:
> Hello.
> Trouble to communicate with APC SmartUPS via serial port.
> UPS connected to the com1 port on windows host.
> Communication witch hyperterm works well.
> There is a log:
>
> YSM
> ^ASmart-UPS SC1000
> n5S0713T63247
> m03/29/07
> L240.0
> B27.10
>
> apcupsd also can communicate with the UPS and works well.
>
2006 Nov 25
2
patch for old APC Smart-UPS 600
Hi there,
I am using an old (really old) APC Smart-UPS 600. It worked fine
under apcupsd but when I tried NUT it did not work.
The error I was getting was:
sudo /lib/nut/apcsmart -DDD /dev/ttyS1
Network UPS Tools (version 2.0.4) - APC Smart protocol driver
Driver version 1.99.8, command table version 2.0
debug level is '3'
Attempting firmware lookup
Firmware: [D4]
Not found in
2013 Jul 09
2
Hope for APC Smart UPS 1500
Hi,
we bought two Smart-UPS X 1500 FW:UPS 09.1 / ID=20
lsusb -v:
Bus 002 Device 002: ID 051d:0003 American Power Conversion UPS
Device Descriptor:
bLength 18
bDescriptorType 1
bcdUSB 2.00
bDeviceClass 0 (Defined at Interface level)
bDeviceSubClass 0
bDeviceProtocol 0
bMaxPacketSize0 64
idVendor
2009 May 25
1
APC Smart UPS 900i
Hi,
I'm running an old APC Smart UPS 900i. As there isn't any software from APC which supports this
UPS anymore, I've installed NUT (Gentoo Ebuilds), but version 2.0.5 and version 2.2.2 loose
connection to the UPS while version 2.4.1 and SVN version don't show any settings and there are no
instant commands.
The only information I can get are:
driver.name: apcsmart
2013 Jul 10
0
Hope for APC Smart UPS 1500
On Jul 9, 2013, at 9:04 AM, Gregor Burck wrote:
> we bought two Smart-UPS X 1500 FW:UPS 09.1 / ID=20
[...]
> I see there should be problems to get it work with a free daemon like nut, but are there some hints using it?
> In my ups.conf I tried:
>
> [apc001]
> driver = apcsmart
> port = auto
> desc = "Smart APC"
Only the USB drivers should
2008 Dec 12
1
APC Backups-Pro 650 - Any way to use apcsmart?
Listmates,
After wrangling with the voltage value on the CyberPower 1000AVRLCD and now
having 2 of them working, I though it would be a simple matter to move my APC
BP650 from apcupsd to nut so that all 3 servers would be monitored on the same
web interface. The APC is attached to an older box running openSuSE 11.0 with
nut-2.2.2-66.1. (nut-classic).
The APC BP650 uses a serial connection
2014 May 03
0
NUT + OpenBSD + dc2500cc + APC Smart-UPS SC620 = problem
On May 2, 2014, at 3:26 AM, Kastus Shchuka wrote:
> Hi,
>
> I am trying to set up NUT on a mini-ITX system running OpenBSD 5.5.
>
> I have an APC Smart-UPS SC620 which runs perfectly well on Ubuntu,
> with nut-2.2.1. Ubuntu system uses ASUS motherboard.
>
> On mini-ITX system, I have Intel d2500cc motherboard with 4 serial ports.
> I've tested ports by connecting
2014 May 02
2
NUT + OpenBSD + dc2500cc + APC Smart-UPS SC620 = problem
Hi,
I am trying to set up NUT on a mini-ITX system running OpenBSD 5.5.
I have an APC Smart-UPS SC620 which runs perfectly well on Ubuntu,
with nut-2.2.1. Ubuntu system uses ASUS motherboard.
On mini-ITX system, I have Intel d2500cc motherboard with 4 serial ports.
I've tested ports by connecting them with a null-modem cable and running cu
in 2 terminals. Type in one terminal, output shows
2007 Jan 12
1
Trouble connecting to apc smart 1500 via serial cable
Hello.
I've been running a two machine setup with a mge-shut for some time
without problems, and now I'm configuring a three machine setup with an
APC Smart 1500.
The UPS has three machines connected to it, in a peculiar way: one
windows machine is connected via USB. The second windows machine is
using an agent to monitor messages from the first windows machine. Then,
I have a GNU/Linux
2008 Jun 18
1
APC Smart-UPS RT 5000
Hello all
I've a brand-new APC box, model Smart-UPS RT 5000, which comes with a black
cable RJ48 in one side (10P4C) and RS232-DB9 in the other. The cable
reads "940-1525A" in the DB9 side.
Which is the best setting (driver and options) to connect this UPS to my
computer? It seems not to be recognized by a typical apcsmart driver setting.
Many thanks
Noel Torres
er Envite
2010 Jan 29
4
APC Smart-ups "status codes" (slightly OT)
We got replacement battery "kits" for some of our APC UPS' (Smart-UPS,
rackmount). I put them into one tray (it's for an RBC 43, which takes 8,
and weighs a ton), and put it in, and let it charge. Idiot "change
battery" led stays on. So I hit the test button, it discharges very
rapidly (a good number of servers on this), and the led stays on.
For some reason,
2009 May 07
1
Findings of dual APC UPS sensor attachments
Hi,
We have several APC Smart UPSes (serial port/apcsmart) with the APC
Temp/Humidity sensor cards (AP9612TH). The sensor cards have 2 plugs for
2 separate sensors. So far, we have only used one of the sensors in
conjunction with the apcsmart module from nut. This has been working
great. Example output:
[nut at nut]# upsc APC11
ambient.humidity: 037.2
ambient.humidity.alarm.maximum: NO,NO
2008 Jul 03
4
Old APC SmartUPS 1250, Nut 2.2.2 Fedora 9
Hi All,
I've got two APC SmartUPS's that behave differently with nut, I have a
SmartUPS1400 & a SmartUPS1250.
I'm fairly sure this isn't a nut problem but more likely a problem with
the age of the SmartUPS1250 and the apcsmart driver not being able to
identify it. Under the APC Powerchute software the same monitoring &
command parameters are available for both
2015 Jul 20
1
apcsmart: doesn't detect missing battery on Smart-UPS 2200 RM
Michal,
I ran across this Debian bug today:
https://bugs.debian.org/cgi-bin/bugreport.cgi?bug=707223
It's a bit of a corner case, and it's for NUT 2.6.4 (apcsmart driver v3.04), but I was wondering if it was still applicable for the latest code?
"nut reports 100% battery charge after unplugging the battery on a Smart-UPS 2200 RM (SUA2200RMI2U) using apcsmart.
Powerchute correctly
2005 Nov 18
1
APC Matrix 5000 UPS
Hello,
I can get nut to work with this UPS using the apcsmart driver, but only
with limited functionality. It is only reporting the OL/OB status and
that's about it. None of the other useful variables such as run time,
load etc are reported and initiating battery tests does not work either.
Has anyone managed to get nut to report more than these variables with a
Matrix type UPS?
I see
2009 May 04
1
Patches for NUT 2.2.2: APC SmartUPS-900
2009/5/3 Thomas Juerges
> -----BEGIN PGP SIGNED MESSAGE-----
> Hash: SHA1
>
> Hi Arnaud,
>
Hi Thomas,
> I just checked the 2.4.1 version of nut and found that you forgot to add
> my old UPS model (APC Smart-UPS 900). I guess it is because you were
> busy at the time when I sent you the patch. So here it goes again. :)
>
uh, right sorry.
I was pretty sure I applied
2009 Sep 02
6
Selftest intervall, APC Smart-UPS 750 RM
Hello
I recently switched from apcupsd to NUT2.2.2 without
any troubles.
I tried to figure out how I can configure the self-test
intervall. The command upsrw lists only the variables
battery.charge.low
battery.runtime.low
ups.delay.shutdown
ups.delay.start
The command usbhid-ups -D and the listing under
http://obsvermes.org/cgi-bin/nut/upsstats.cgi?host=apcsmart at localhost&treemode
2013 Sep 10
0
'^' character in APC Smart protocol
Dear All ...
I Want to build something like http://tandem.ck.ua/ups_mtm-eng.php , but
based on arduino.
I'm reading http://www.networkupstools.org/ups-protocols/apcsmart.html now.
My question is : what is the ascii code of '^' i.e ^A from that page ?
Is it ^ + A ?
Or is it ctrl + A ?
Background : Mikrotik have ups monitor feature.
Based on
2010 Jul 28
1
APC SmartUPS 2200XL + UDEV + USB = tcgetattr : Invalid argument
I need direction. I don't know what to google for anymore. I am unable
to get my SmartUPS 2200XL to be recognized. My suspicions are that it's
UDEV or Kernel related. I've updated the kernel to the highest version
I feel comfortable with due to other things that run on the server, and
I've updated UDEV a bit too.
When I plug in the USB cable from the UPS into the server, I