Displaying 20 results from an estimated 1000 matches similar to: "Old Contact UPS Info"
2015 Nov 16
2
Contact-closure UPS
Hello,
I have one UPS Infosec XP Pro 2500 RM and it works with windows sw RUPS2000.
Now I want to install this UPS as virtual server on vmware ESXi vMA - (SUSE SLES 11SP2 linux).
On this linux I have NUT 2.6.0 and I stopped now with configuration of genericups driver.
Working cable (direct cable pin1-pin1 ... pin9-pin9) connection on Windows:
PIN | PC | UPS
2008 Dec 23
2
Exide NetUPS SE (aka Powerware 5119 etc)
My UPS is an Exide NetUPS SE PRC1500i (1500 VA), also known as
Powerware 5119, according to Karl Schmidt
(http://lists.alioth.debian.org/pipermail/nut-upsuser/2005-July/000026.html)
also Deltec PowerRite Pro II, and according to
http://www.usedups.de/compaq_ups.html also Compaq R3000h. I am not
sure if the information in http://www.bps.hu/powerware/model_en.html
is to be interpreted as that it was
2008 Dec 23
2
Exide NetUPS SE (aka Powerware 5119 etc)
My UPS is an Exide NetUPS SE PRC1500i (1500 VA), also known as
Powerware 5119, according to Karl Schmidt
(http://lists.alioth.debian.org/pipermail/nut-upsuser/2005-July/000026.html)
also Deltec PowerRite Pro II, and according to
http://www.usedups.de/compaq_ups.html also Compaq R3000h. I am not
sure if the information in http://www.bps.hu/powerware/model_en.html
is to be interpreted as that it was
2005 Nov 30
4
ups.conf configure
Hello, I got this information from the manufacturer of my ups Kobian/Mercury
and were tested wtih powstatd on Linux (Works OK). Now i want to configure
it with NUT and i didn't have any luck (it always says OB)
Initiliasation for monitoring: RTS = 1 (High)
Main power fail: CTS = 0 (Low)
Batter low: DCD = 0 (Low)
Kill UPS: DTR = 0 (Low)
How would the ups.conf look like?
Reagards,
Lep
2005 Jul 04
1
Powerware 5119 = Exide NETUPS SE = Deltec name was PowerRite Pro II
Someone might want to add this to the docs - cable list and compatibility list
- took me way to long to find.
I was trying to find information on my UPS and came up with the following names
for the same UPS series.
Powerware 5119
Exide name was NetUPS SE
Deltec name was PowerRite Pro II
(1000VA-3000VA)
What I have:
The Exide NETUPS SE
model PRC2400a
p/n 05144038-3904
OUTPUT 2400VA 1600 WATTS
2015 Nov 21
2
Contact-closure UPS
>> On Nov 21, 2015, at 2:43 AM, R?bert SZAKSZ <robert at szaksz.eu> wrote:
>>
>> I mesured it and on DC and it shows 0 V (zero V).
>> May be the information (pls. see attachment) that UPS PIN1 should bee keept HI is mandatory. Should I connect it to PC PIN4 DTR?
>
>Certainly possible. blazer_ser and nutdrv_qx should set DTR high and RTS low by default, but
2006 Jul 11
1
Re: [nut-commits] svn commit r446 - in branches/Testing: . drivers man
> +22 = Gamatronic UPSs with alarm interface
> + [CP=RTS] [OL=CTS] [LB=\-DCD] [SD=DTR]
> +
> +22 = CyberPower SL seriess
> + [CP=RTS] [OL=CTS] [LB=\-CAR] [SD=DTR]
> +
> +
This part of the patch is no good. While TIOCM_CAR is equivalent to
TIOCM_CD (at least in some implementations) CAR certainly isn't handled
the same as DCD by genericups. It won't be
2015 Nov 16
0
Contact-closure UPS
[please use reply-all when responding - the list does not modify the reply-to header.]
> On Nov 16, 2015, at 8:24 AM, R?bert SZAKSZ <robert at szaksz.eu> wrote:
>
> Hello,
>
> I have one UPS Infosec XP Pro 2500 RM and it works with windows sw RUPS2000.
> Now I want to install this UPS as virtual server on vmware ESXi vMA - (SUSE SLES 11SP2 linux).
> On this linux I
2015 Nov 21
2
Contact-closure UPS
>On Nov 20, 2015, at 12:17 PM, R?bert SZAKSZ <robert at szaksz.eu> wrote:
>>
>> No progress has been made:
>>
>> cable is UPS - PC
>> 6 - 3
>> 7 - 5
>> 9 - 2
>>
>
>Maybe pins 4 and 7 (ground) both need to be connected on the UPS side?
I connected both to pin 5
>Unfortunately, I don't think there is a safe way (in software)
2015 Nov 16
2
Contact-closure UPS
Hi Charles,
>----- Original Message -----
>From: "Charles Lepple" <clepple at gmail.com>
>To: "R?bert SZAKSZ" <robert at szaksz.eu>
>Cc: nut-upsuser at lists.alioth.debian.org
>Sent: Monday, November 16, 2015 3:20:17 PM
>Subject: Re: [Nut-upsuser] Contact-closure UPS
>
>[please use reply-all when responding - the list does not modify the
2008 Mar 14
0
Sola 305 with INT-0051 cable
Hello again,
I have a Sola 305 (aka Powerware 3110) here connected via a serial
INT-0051 cable which I am trying to get working with nut. The
driver.list file indicates that nut supports the Sola 305 when connected
via the INT-0025C cable using the genericups driver with upstype set to
7 but it does not mention the INT-0051.
I was able to use the "Basic CheckUPS II" utility provided
2012 Feb 26
1
Server Does Not Shut Down
Hello,
I have a UPS connected to my server with the following:
Server is Suse 10.1
Nut version is?Network UPS Tools - Generic UPS driver 1.32 (2.0.4)
I installed this around 2005 and cannot remember how I installed the software.
ups.conf:
[sdrups]
driver = genericups
port = /dev/ttyS0
desc = "For Server & Backup"
upstype = 9
upsd.conf:
ACL all 0.0.0.0/0
ACL localhost
2015 Apr 27
1
Contact closure UPS?
Hello again! I'm yet again the guy from the blazer_usb problem and the
ATCL one too. This time I have a third UPS (the last one In my collection)
that i'm trying to make work instead of the ATCL one since there's no
driver for it on windows.
This UPS is another no-brand box (actually it is a "kozumi", but that's
just a rebrand), and apparently it's much more basic
2005 Aug 08
1
Here are CORRECT APC cable diagrams
+-----------------------------------------------------------------+
| |
| Black APC 940-0024C Smart Signalling UPS Cable Wiring Diagram |
| This information is verified and tested to be 100% correct. |
| |
2018 Jun 26
2
Instruction boundaries
There should be a line-table entry for the end of the function, which appears to be missing from the dump you provided. llvm-dwarfdump should report this address with 'end_sequence' in the Flags. Are you using a different dumper?
I am not sure but my guess would be that inline data is not represented in the line table. The line table's primary purpose is to inform the debugger
2007 Apr 04
3
Compaq T2400H UPS model 242688-006
Hi,
I have a Comapq T2400H model 242688-003 and do not have the special
cable to connect it to my serial port.
I have tried all sorts of cable wirings that I found on the net,
including ones for the powerware 5119 which appears to be the same
model.
I have read the documentation that comes with NUT, tried to read
the source code and looked at the genericups code too.? I have
2007 Oct 23
2
Data calls through TDM2400E
Hello. Has anyone been able to successfully make data (dialup modem) calls
through a TDM2400E? We're able to make fax and credit card calls fine, but
cannot successfully make modem calls using a 56K modem connected to a patch
panel connected to an FXS port which then gets bridged to an FXO port
connected directly to a phone line. We have 'echocancelwhenbridged=no' set
in
2010 Jun 15
0
mercury smart1200 pro serial powerdown problem
Hello *
Trying to get above serial UPS to work gives my some troubles.
With upstype=21 [CP=RTS] [OL=CTS] [LB=-DCD] [SD=RTS+DTR]
and/or upstype=4 [CP=RTS] [OL=CTS] [LB=-DCD] [SD=-RTS]
I do get OL OB LB ok, but shutting down the UPS does not work.
Direct call w/ command genericups ... -k and from lowbatt/
initscripts doesnt do. The UPS claims to be capable of and
the software shipped (RUPS2000)
2018 Jun 26
2
Instruction boundaries
I'm not familiar with the target instruction set, but if "MOV PC, R0" is not a return instruction, I'm guessing that the sequence starting at A39C is a dispatch through a jump table. The jump table would be considered part of the instruction stream and included in the scope of the line table. This is not a case where you would see end_sequence; my mistake.
The line table does
2009 Dec 21
1
Config serial/contact on Cyberpower UPS PR1500LCDRTXL2U
Hi,
Could somebody please help me get this one to work using the close
contact information.
I can not get it to detect off line
Config:
OpenSuse 11.0 NUT 2.2.2
[cyberpower]
driver = genericups
port = /dev/ttyS1
mfr = "Cyberpower"
model = "PR1500LCDRTXL2U"
desc = "Cyberpower PR1500LCDRTXL2U - Serial/contact"