2006 Aug 18
0
(no subject)
Dear Mr Claesson, prepare for quite a long letter from me. I hope you will have time to read it. I bestowed a whole morning on trying to identify the correct upstype. Here are the results: root@marto:/home/marto# /usr/local/ups/bin/powercom -DD -u root -a Inform -x type=KP625AP Network UPS Tools - PowerCom and similars protocol UPS driver $ Revision: 0.5 $ (2.0.4) debug level is '2'
2006 Aug 17
2
powercom UPS shoutdown discussion
Thank you for your response. The point is that I have configured my system to shut down at the event "upsc Inform@localhost ups.status"!="OL", not at "LB". So there will be no /etc/killpower file created. At an ups.status != "OL" event, the following script named "notifyme" is run: echo `date` >> /root/upsLog echo " No power, shutting
2007 Dec 24
3
Driver for Powercom BNT/KIN/IMP/IMD series
Hello all. Try this driver (for nut 2.2.0). See attach. - Trust, KP625AP, Egys models stay as it was - add Powercom's Black Knight Pro model support ( BNT-400/500/600/800/801/1000/1200/1500/2000AP 220-240V ) - add Powercom's King Pro model support ( KIN-425/525/625/800/1000/1200/1500/1600/2200/3000/5000AP[-RM] 100-120,200-240 V) - add Powercom's Imperial model support ( IMP-xxxAP,
2011 May 17
3
Powercom issues in NUT (was: PowerCom BNT2000AT ups on nut 2.6.0 - second try)
Dino, Alexey, there are a number of users suffering issues with your Powercom devices. Could you (Dino, and Keven if possible) please have a look at the below one, from Angela, and check for a fix? I've scheduled to release 2.6.1 next week, and having that fixed is part of the list. 2011/5/16 Angela Williams <angierfw at gmail.com> > Hi All > > On Friday 13 May 2011 at
2005 Dec 30
2
BNT600AP
Hi, I have a little problem with PowerCom BNT600AP after running driver I see: root@rask> powercom -D /dev/ttyS1 Network UPS Tools - PowerCom and similars protocol UPS driver $ Revision: 0.5 $ (2.0.2) debug level is '1' Values of arguments: manufacturer : 'PowerCom' model name : 'Unknown' serial number : 'Unknown' line
2005 Aug 19
1
Sustainer S-1000C (Powercom protocol)
Hi, I've sent the following message 3 weeks ago, yet have recieved no reply at all. I don't want to nag, but could anyone please help me? Thanks, Dror ------------------ Hi, I have a UPS of the Israeli company Sustainer, model S-1000C (http://www.sustainer.co.il/data/files/specifications%20smart%20en.pdf - don't worry, it's in english...). I've been trying to connect to
2006 Aug 16
5
Master privileges unavailable on UPS, no access :(
Hello! After I type "upsmon", in syslog the following message appears: Aug 16 14:11:09 marto upsmon[7731]: Master privileges unavailable on UPS [Inform@localhost] Aug 16 14:11:09 marto upsmon[7731]: Reason: Access denied Can you tell me where my error is, my configuration files are: ups.conf: [Inform] driver = powercom port = /dev/ttyS0 desc = "inform guard" linevoltage = 220
2006 Dec 11
2
howto setup BNT-1500AP on gentoo
Good afternoon. I try to put nut on gentoo. Has executed installation by a standard command emerge nut. All has passed successfully. I use UPS POWERCOM BNT-1500AP. It is connected to serial port 1, i.e. for my system it/dev/tts/0. In/etc/nut/ups.conf [powercom] driver = powercom port = /dev/tts/0 desc = "PowerCom BNT-1500AP on IP-PBX" modelname = "BNT-1500AP" linevoltage = 230
2006 Aug 17
0
(no subject)
So, this is the result of upsc Inform@localhost with the UPS connected to the mains: battery.charge: 97.7 driver.name: powercom driver.parameter.linevoltage: 220 driver.parameter.port: /dev/ttyS0 driver.parameter.type: KIN1500AP driver.version: 2.0.4 driver.version.internal: $ Revision: 0.5 $ input.frequency: 49.61 input.voltage: 236.3 input.voltage.nominal: 220 output.frequency: 49.10
2006 Apr 21
1
Powercom BNT-1200AP
Hello I have UPS Powercom Black Knight Pro 1200 (BNT-1200AP) I try to use nut, but powercom driver not understand my model Ok, i try to use type KIN1500AP and it's work But powercom driver can't set UPS's shutdown delay time Also i have powercom's original program (upsmon), and this program can do it What can i do for help to add this function to nut's powercom driver? For
2007 Nov 06
1
BNT-1000AP
Hi guys, We've got a BNT-1000AP (powercom) BlackKnight UPS that works with the KIN1500AP model in the powercom driver. Well, almost. It seems the input frequency and the battery charge is swapped around: # upsc blackknight at localhost battery.charge: 46.5 driver.name: powercom driver.parameter.manufacturer: BlackKnight driver.parameter.modelname: BNT-1000AP driver.parameter.port:
2009 Dec 27
4
XPCC XVRT-1000 driver
-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA1 Has anyone used nut with a XPCC UPS, in particular one of the XVRT units? Their supplied monitoring tool "works", but I'd really prefer to use nut if possible. I've systematically gone through each of the drivers in /lib/nut and none seem to talk with the unit properly. I'll be talking with a XPCC support person tomorrow, though
2005 Jul 06
0
Powercom BNT-1500AP
Hey all, Does anybody know there is a full working setup for the PowerCom BNT-1500AP. I got some stuff working with the Powercom driver and the type set to "KIN1500AP". But it seems that there is still missing usablity. I was wondering if anybody found any better configs? ---- excerpt of ups.conf [AVR1500] driver = powercom port = /dev/ttyS0 desc =
2011 May 13
1
PowerCom BNT2000AT ups on nut 2.6.0 - second try
Hi! Normally nut was just worked and worked for me! Not this time though! Distro is Gentoo withe latest nut-2.6.0 emerged today. Linux kernel version is 2.6.36 UPS is PowerCom BNT2000AT "Driver" is powercom ups.conf looks like this! Okay so APC1 is not and APC! [APC1] driver = powercom type = BNT port = /dev/ttyS1 numOfBytesFromUPS = 16
2007 Oct 04
0
Powercom black knight 800AP (serial)
Hi, Nut versions: 2.2.0 and 2.0.2 (powercom -x type=KIN1500AP -x linevoltage=220) I've got the above mentioned serial UPS and have found some problems using it. 1) under linux 2.6.12 select() timed out on reading the serial port in NONBLOCK mode. Not sure about this one, seems most likely a kernel problem, since it's working OK in 2.6.20. But on the other hand it was a nasty one. For
2011 Jul 08
2
Ubuntu 10.04 Ultra 700VA UPS Setup Nut
I just bought an Ultra UPS system for my linux server, and I need help getting it set up. It's an Ultra 700VA UPS. NUT INFORMATION: Package (apt-get install nut) NUT VERSION: Latest Driver: I don't have one? Here's the device information from my syslog: Code: Jul 7 23:25:27 eric-desktop kernel: [ 3045.609066] usb 2-1: USB disconnect, address 3 Jul 7 23:25:30 eric-desktop
2007 Dec 29
1
Odd Values For Powercoms
All, I'm using the Powercom driver from 2.2 (not the one recently mailed to thelist). Since it's a KIN2200AP, I'm using the driver settings right from the manpage. All the values look "sane" when I'm on-line, but note some of the odd values (<-- Here) when on battery: Also, does anyone know if this UPS supports logging of the "boost" or
2006 Dec 21
2
Specs for Powercom Kingpro UPSes!
Hey all, I found a pinout of powercom's Kingpro UPSes in their manual. http://www.powercom-ups.com/manuals/kingpro.pdf Page 11. Unfortunately, this doesn't give PROTOCOL details. Does anyone have a "first step" at how to decode that? (for example, how to gauge line speed, how to "snoop" the serial port under windows? (for which the only software exists right
2006 Jul 08
0
Powercom BNT-600AP and NUT (powercom driver)
Hello, I'm new there. I bought an UPS Powercom BNT-600AP. It's compatible in NUT with driver powercom and protocol type KIN1500AP. But I have a simple problem: the 'upsc' shows wrong values in battery.charge (maybe in other rows also /ups.load, voltages?/) - if battery is 100% charged it shows only 92.6% or 93.0%. I thing I have wrong values in driver parameters: batteryPercentage,
2005 Jul 07
2
PowerCom Smart King SMK-1000
Hi! I've tried the Fenton Driver for my UPS. The Powercom driver doesn't work. Here is the results: Network UPS Tools - UPS driver controller 2.0.0 Network UPS Tools - Fenton UPS driver 1.21 (2.0.0) Unknown ups - please report this ID string: #PCM SMK-1000 2001 V9.0 Detected Unknown MK-1000 on /dev/ttyS0 Have you any ideas to make it compartible with NUT. Thanks! With