Displaying 20 results from an estimated 5000 matches similar to: "APC Smart 700 UK and frequency setting at cold start"
2006 Jun 01
0
"Battery constant" value for APC UPS
Hi all,
Thought I'd forward this on, as the apcsmart driver doesn't appear to
have any support for this (admittedly obscure) setting and it doesn't
seem to be listed at http://www.networkupstools.org/protocols/apcsmart.html.
Hope someone finds it useful.
Later,
Russ
--
Russell Odom
http://www.gloomytrousers.co.uk/
Fast, cheap, good: pick two.
-------- Original Message --------
2009 Feb 27
0
support for APC Matrix 5000, vintage 12/00 (was: NUT apcsmart driver - firmware addition)
Hey Jarett,
2009/2/24 <jarett.stevens at usermail.com>
> After upgrading to the 2.4.1 version, I wasn't able to read as many
> variables from my UPS. After a bit of experimentation, I determined that
> the firmware on my UPS was different than what is currently in the
> apcsmart driver, though it had worked before. I located my firmware
> version (5ZM), and added in
2014 Jan 14
2
Unable to detect an APC Smart protocol UPS. Windows. APC Smart protocol driver 3.04 (2.6.5-3723:3731M)
Hello.
Trouble to communicate with APC SmartUPS via serial port.
UPS connected to the com1 port on windows host.
Communication witch hyperterm works well.
There is a log:
YSM
^ASmart-UPS SC1000
n5S0713T63247
m03/29/07
L240.0
B27.10
apcupsd also can communicate with the UPS and works well.
running apcsmart -a ups gives the following:
com1: device reports different attributes than what were set
2014 Jan 14
0
Unable to detect an APC Smart protocol UPS. Windows. APC Smart protocol driver 3.04 (2.6.5-3723:3731M)
On 2014-01-14 10:12, dstrr wrote:
> Hello.
> Trouble to communicate with APC SmartUPS via serial port.
> UPS connected to the com1 port on windows host.
> Communication witch hyperterm works well.
> There is a log:
>
> YSM
> ^ASmart-UPS SC1000
> n5S0713T63247
> m03/29/07
> L240.0
> B27.10
>
> apcupsd also can communicate with the UPS and works well.
>
2009 Mar 19
0
plz add support of APC sc1500i by NUT
thanks for these info.
2009/3/19 Artyom Mikhailov <artyom.mikhailov at gmail.com>
> Hi there,
>
> Great project you have - NUT, thx for the development!
> I just thought it might be usefull to let you know that APC SC1500I ups can
> be found supported by NUT.
> I used the following settings:
> [sc1500i]
> driver = apcsmart
> port = /dev/ttyUSB0
2013 Jul 10
0
Hope for APC Smart UPS 1500
On Jul 9, 2013, at 9:04 AM, Gregor Burck wrote:
> we bought two Smart-UPS X 1500 FW:UPS 09.1 / ID=20
[...]
> I see there should be problems to get it work with a free daemon like nut, but are there some hints using it?
> In my ups.conf I tried:
>
> [apc001]
> driver = apcsmart
> port = auto
> desc = "Smart APC"
Only the USB drivers should
2009 May 04
1
Patches for NUT 2.2.2: APC SmartUPS-900
2009/5/3 Thomas Juerges
> -----BEGIN PGP SIGNED MESSAGE-----
> Hash: SHA1
>
> Hi Arnaud,
>
Hi Thomas,
> I just checked the 2.4.1 version of nut and found that you forgot to add
> my old UPS model (APC Smart-UPS 900). I guess it is because you were
> busy at the time when I sent you the patch. So here it goes again. :)
>
uh, right sorry.
I was pretty sure I applied
2006 Nov 25
2
patch for old APC Smart-UPS 600
Hi there,
I am using an old (really old) APC Smart-UPS 600. It worked fine
under apcupsd but when I tried NUT it did not work.
The error I was getting was:
sudo /lib/nut/apcsmart -DDD /dev/ttyS1
Network UPS Tools (version 2.0.4) - APC Smart protocol driver
Driver version 1.99.8, command table version 2.0
debug level is '3'
Attempting firmware lookup
Firmware: [D4]
Not found in
2013 Sep 17
0
Support for APC Smart-UPS X 3000
Just my experiences speaking, look at another brand. I use MGE/Eaton and
have had much better life and the quality has been much better. APC does
not release the protocol for comunicating with the UPS and so to get NUT to
work you have to sniff the traffic and then figure out what the commands
and responses mean.(thus reverse engineered) APC also will change the
protocol between models. (Thus why
2013 Sep 10
0
'^' character in APC Smart protocol
Dear All ...
I Want to build something like http://tandem.ck.ua/ups_mtm-eng.php , but
based on arduino.
I'm reading http://www.networkupstools.org/ups-protocols/apcsmart.html now.
My question is : what is the ascii code of '^' i.e ^A from that page ?
Is it ^ + A ?
Or is it ctrl + A ?
Background : Mikrotik have ups monitor feature.
Based on
2007 Jan 21
1
APC Smartups protocol - Hidden Programming Mode
Hej!
Hope nut-upsuser is an appropriate place to post additional info about
the smartups protocol, please tell me if not.
I got an APC Smartups 2200 (5U Rack Mount, European/230V version, 48V
batteries) a couple of days ago, was very happy to find the protocol
description at http://www.networkupstools.org/protocols/apcsmart.html,
and started to play. At the point when everything was working
2007 Jan 12
1
Trouble connecting to apc smart 1500 via serial cable
Hello.
I've been running a two machine setup with a mge-shut for some time
without problems, and now I'm configuring a three machine setup with an
APC Smart 1500.
The UPS has three machines connected to it, in a peculiar way: one
windows machine is connected via USB. The second windows machine is
using an agent to monitor messages from the first windows machine. Then,
I have a GNU/Linux
2014 May 03
2
NUT + OpenBSD + dc2500cc + APC Smart-UPS SC620 = problem
On May 3, 2014, at 5:20 AM, Charles Lepple wrote:
> On May 2, 2014, at 3:26 AM, Kastus Shchuka wrote:
>
>> Hi,
>>
>> I am trying to set up NUT on a mini-ITX system running OpenBSD 5.5.
>>
>> I have an APC Smart-UPS SC620 which runs perfectly well on Ubuntu,
>> with nut-2.2.1. Ubuntu system uses ASUS motherboard.
>>
>> On mini-ITX system, I
2014 May 03
0
NUT + OpenBSD + dc2500cc + APC Smart-UPS SC620 = problem
On May 2, 2014, at 3:26 AM, Kastus Shchuka wrote:
> Hi,
>
> I am trying to set up NUT on a mini-ITX system running OpenBSD 5.5.
>
> I have an APC Smart-UPS SC620 which runs perfectly well on Ubuntu,
> with nut-2.2.1. Ubuntu system uses ASUS motherboard.
>
> On mini-ITX system, I have Intel d2500cc motherboard with 4 serial ports.
> I've tested ports by connecting
2009 May 25
1
APC Smart UPS 900i
Hi,
I'm running an old APC Smart UPS 900i. As there isn't any software from APC which supports this
UPS anymore, I've installed NUT (Gentoo Ebuilds), but version 2.0.5 and version 2.2.2 loose
connection to the UPS while version 2.4.1 and SVN version don't show any settings and there are no
instant commands.
The only information I can get are:
driver.name: apcsmart
2006 Feb 05
1
APC Smart-UPS v/s 650 variables.
Hi all,
when I try to get infos from this ups, the only variables that upsc
print is:
# upsc Smart-UPS@localhost
driver.name: apcsmart
driver.version: 2.0.0
driver.version.internal: 1.99.6
ups.mfr: APC
ups.status: OL
Is it not possible to get voltage and other infos from that model of
UPS? Thanks.
Regards,
Dio.
2008 Jun 18
1
APC Smart-UPS RT 5000
Hello all
I've a brand-new APC box, model Smart-UPS RT 5000, which comes with a black
cable RJ48 in one side (10P4C) and RS232-DB9 in the other. The cable
reads "940-1525A" in the DB9 side.
Which is the best setting (driver and options) to connect this UPS to my
computer? It seems not to be recognized by a typical apcsmart driver setting.
Many thanks
Noel Torres
er Envite
2013 Jul 09
0
Hope for APC Smart UPS 1500
Hi,
we bought two Smart-UPS X 1500 FW:UPS 09.1 / ID=20
lsusb -v:
Bus 002 Device 002: ID 051d:0003 American Power Conversion UPS
Device Descriptor:
bLength 18
bDescriptorType 1
bcdUSB 2.00
bDeviceClass 0 (Defined at Interface level)
bDeviceSubClass 0
bDeviceProtocol 0
bMaxPacketSize0 64
idVendor
2015 May 13
0
Problem connecting to APC Smart UPS SC1000 on Windows
Hello.
I have problem with connecting to APC SC1000 using NUT port for windows
2.6.5-6.
Last working version is NUT 2.6.1-1. With the same config files it works
well.
c:\NUT\bin>apcsmart.exe -a SC1000
Network UPS Tools - APC Smart protocol driver 3.1
(Windows-v2.6.5-5-7-g72f380c)
APC command table version 3.1
w32_serial_open (COM3)
setting initial state on COM3
0000007C = w32_serial_open
2014 Oct 19
1
Smart-UPS RT 3000 XL: very old or unknown APC model, support will be limited
I have a Smart-UPS RT 3000 XL connected via serial cable to TrueNAS TrueNAS-9.2.1.2-RELEASE-x64 (002022c) which runs on FreeBSD 9.2-RELEASE-p3.
When I start the NUT service, I get the message:
Oct 20 01:53:50 truenas notifier: very old or unknown APC model, support will be limited
Which I interpret as an indicator of less than optimal operating mode. I suspect that the model identifier is not