2014 Aug 20
0
win7 x64 victron driver exiting with error
...S Victron NetPro connected via serial port
When I run driver when UPS cable is connected to computer's serial port it
exits with following output
victronups - -DDDD -a victron
Network UPS Tools -GE/IMU/Victron UPS driver 0.20 (2.6.5.-3723:3731M)
0.000000 debug level is "4"
0.000000 w32_serial_open (COM1)
0.000000 setting initial state on COM1
0.015600 0000000050 = w32_serial_open (COM1)
0.015600 Warning: no locking method is available: No error
0.015600 tcgetattr(COM1): Input/output error
But... when I run the driver and few seconds later connect the cable to
serial port it works correctly....
2015 May 13
0
Problem connecting to APC Smart UPS SC1000 on Windows
...oblem with connecting to APC SC1000 using NUT port for windows
2.6.5-6.
Last working version is NUT 2.6.1-1. With the same config files it works
well.
c:\NUT\bin>apcsmart.exe -a SC1000
Network UPS Tools - APC Smart protocol driver 3.1
(Windows-v2.6.5-5-7-g72f380c)
APC command table version 3.1
w32_serial_open (COM3)
setting initial state on COM3
0000007C = w32_serial_open (COM3)
Warning: no locking method is available: No error [+?????? ???????
?????????. ]
vmin_ 0, vtime_ 0
action 0
vtime 0, vmin 1
ReadTotalTimeoutConstant -2, ReadIntervalTimeout -1,
ReadTotalTimeoutMultiplier
-1
vmin_ 1, vtime_ 0
a...
2016 Jul 20
0
port for powercom
...'powercom' driver instead.
So I switched to the powercom driver, but I have tried a whole bunch of likely suspects for the port setting, none of which have worked
Tried so far:-
com1 with these results:-
Network UPS Tools - PowerCom protocol UPS driver 0.13 (Windows-v2.6.5-5-7-g72f38
0c)
w32_serial_open (com1)
setting initial state on com1
0000005C = w32_serial_open (com1)
Warning: no locking method is available: No error [The operation completed succe
ssfully. ]
vmin_ 0, vtime_ 0
action 0
vtime 0, vmin 1
ReadTotalTimeoutConstant -2, ReadIntervalTimeout -1, ReadTotalTimeoutMultiplier
-1
data rece...
2018 Nov 29
0
Problem to connect to APC SC1500
...PS: APC SC 1500VA
Driver: apcsmart
upsdrvctl.exe start outputs this errors:
----------------------------------------------------------------------------------------------------------------
Network UPS Tools - APC Smart protocol driver 3.1 (Windows-v2.6.5-5-7-g72f380c)
APC command table version 3.1
w32_serial_open (COM4)
setting initial state on COM4
000000A8 = w32_serial_open (COM4)
Warning: no locking method is available: No error [Der Vorgang wurde erfolgreich beendet. ]
vmin_ 0, vtime_ 0
action 0
vtime 0, vmin 1
ReadTotalTimeoutConstant -2, ReadIntervalTimeout -1, ReadTotalTimeoutMultiplier -1
vmin_ 1,...
2011 Jul 19
2
KIN-1500AP RM + Windows 2008 64-bit Standard R2 SP1 (nut 2.6.1)
I have only RS-232 on the box (meanwhile, it was manufactured on march of
2011)
Here is my configs:
nut.conf:
*
*
MODE = netserver
ups.conf:
*
*
[KIN1500]
driver = powercom
port = notUsed
desc = "Powercom KING PRO KIN-1500AP RM"
upsd.conf:
*
*
LISTEN 192.168.1.2 3493
upsd.users:
*
*
[monuser]
password = xxxxxxxx
upsmon master
2013 May 11
1
blazer_ser problem on windows NUT 2.6.5-3780M
...zer_ser
port = com6
desc = "Proline UPS"
Here is the output from blazer_ser not working:
C:\Program Files (x86)\NUT\bin>blazer_ser -ups *-DDD* -a myups
Network UPS Tools - Megatec/Q1 protocol serial driver 1.55 (2.6.5-3780M)
0.000000 debug level is '3'
0.002000 w32_serial_open (com6)
0.177010 setting initial state on com6
0.231013 00000050 = w32_serial_open (com6)
0.236014 Warning: no locking method is available: No error [The
operation completed successfully. ]
0.244014 vmin_ 0, vtime_ 0
0.346020 action 0
0.398023 vtime 0, vmin...
2012 May 10
3
battery.charge and other fixes needed for X-Power Tigra 1kVA
...ll: SETINFO driver.parameter.id
"610,1000,230,230,10.0,36.0"
0.000000 send_to_all: SETINFO driver.parameter.nombattvolt "41.1"
0.015625 send_to_all: SETINFO driver.parameter.battvoltmult "18"
0.015625 debug level is '7'
0.015625 w32_serial_open (com1)
0.015625 setting initial state on com1
0.015625 000007AC = w32_serial_open (com1)
0.015625 Warning: no locking method is available: No error [The
operation completed successfully. ]
0.015625 vmin_ 0, vtime_ 0
0.109376 action 0
0.109376 vtime 0...
2013 Jan 30
3
bug report: apcsmart (WIN) 940-0024C connect fail, problem with command 'E'
...hout
command 'E'. However, command 'T' reports the UPS power on hours in decimal
format xxx.x
Thank you in advance,
Markus Pruehs
ups.conf:
[600LS]
driver=apcsmart
port=COM1
C:\Programme\NUT\bin>apcsmart -a 600LS -DDDDD
0.000000 debug level is '5'
0.000000 w32_serial_open (COM1)
0.010014 setting initial state on COM1
0.010014 000007D0 = w32_serial_open (COM1)
0.010014 Warning: no locking method is available: No error [Der
Vorgang wurde erfolgreich beendet. ]
0.020029 vmin_ 0, vtime_ 0
0.120173 action 0
0.120173 vtime 0, vmin...
2013 Apr 02
3
blazer driver: Possible bugs with battery packs
...pecified, battery.charge drops to zero.
I have not investigated (2), but I did do some digging regarding one above.
When running with -DDDDD, I get the following:
Network UPS Tools - Megatec/Q1 protocol serial driver 1.55 (2.6.5-3780M)
0.000000 debug level is '5'
0.000000 w32_serial_open (com1)
0.000000 setting initial state on com1
0.000000 000007D0 = w32_serial_open (com1)
0.000000 Warning: no locking method is available: No error [?
????????-?
???????????? ?? ??????-?. ]
0.000000 vmin_ 0, vtime_ 0
0.109369 action 0
0.109369 vtime...