Displaying 1 result from an estimated 1 matches for "vfh_".
Did you mean:
vf_
2009 Mar 07
0
New variables for Victron/GE UPS
...xt (1,2)
RETURNS: vZ1f_
------------------------------------------------------------------------------------------------
GET: vFh? "audible status (i.e. beeper status)" may be a RAM
value, exists until UPS restarts
1 - disabled
2 - enabled
3 - muted (for current alarm only)
SET: vFh_! where _ is the value in text (1,2,3)
RETURNS: vFh_
------------------------------------------------------------------------------------------------
Investigated via port monitoring tool and then tested with my GE Match
700 with terminal.
Best regards,
Ilja