[EXTERNAL] SNMP shutdown timing out
...0 battery.voltage.nominal: -1.00 device.mfr: APC device.model: SMART-UPS 1400 device.serial: WS9831004667 device.type: ups driver.name<https://urldefense.proofpoint.com/v2/url?u=http-3A__driver.name&d=DwMFaQ&c=f9s1WCuF-N6cmD_YaZ7gBg&r=lhr3k4au5dVQgHY_iS-v_t9g8PHVkn8Px_wyaupZGfQ&m=VdKSS_Vk98WT0ADZ-mQe_3zCfrLacAAuMS7JSj5wn1w&s=hM67G_Mcn7oW5yo4o44Na9wyw26mxM8hKXFExeGyhJQ&e=>: snmp-ups driver.parameter.authProtocol: MD5 driver.parameter.mibs: apcc driver.parameter.pollinterval: 2 driver.parameter.port: 192.5.37.191 driver.parameter.privProtocol: DES driver.parameter.secLevel: authPri...
2020 Apr 29
2
SNMP shutdown timing out
I'm in the process of trying to get NUT to manage an APC SmartUPS. Monitoring of the UPS is working fine: $ upsc nutdev1 at localhost Init SSL without certificate database ambient.1.humidity.alarm.high: 60.00 ambient.1.humidity.alarm.low: 30.00 ambient.1.temperature.alarm.high: 40.00 ambient.1.temperature.alarm.low: 10.00 battery.charge: 94.00 battery.charge.restart: 0 battery.current: 0.00