Displaying 2 results from an estimated 2 matches for "vdkss_vk98wt0adz".
2020 Apr 29
0
[EXTERNAL] SNMP shutdown timing out
...0
battery.voltage.nominal: -1.00
device.mfr: APC
device.model: SMART-UPS 1400
device.serial: WS9831004667
device.type: ups
driver.name<https://urldefense.proofpoint.com/v2/url?u=http-3A__driver.name&d=DwMFaQ&c=f9s1WCuF-N6cmD_YaZ7gBg&r=lhr3k4au5dVQgHY_iS-v_t9g8PHVkn8Px_wyaupZGfQ&m=VdKSS_Vk98WT0ADZ-mQe_3zCfrLacAAuMS7JSj5wn1w&s=hM67G_Mcn7oW5yo4o44Na9wyw26mxM8hKXFExeGyhJQ&e=>: snmp-ups
driver.parameter.authProtocol: MD5
driver.parameter.mibs: apcc
driver.parameter.pollinterval: 2
driver.parameter.port: 192.5.37.191
driver.parameter.privProtocol: DES
driver.parameter.secLevel: authPri...
2020 Apr 29
2
SNMP shutdown timing out
I'm in the process of trying to get NUT to manage an APC SmartUPS.
Monitoring of the UPS is working fine:
$ upsc nutdev1 at localhost
Init SSL without certificate database
ambient.1.humidity.alarm.high: 60.00
ambient.1.humidity.alarm.low: 30.00
ambient.1.temperature.alarm.high: 40.00
ambient.1.temperature.alarm.low: 10.00
battery.charge: 94.00
battery.charge.restart: 0
battery.current: 0.00