search for: value1200

Displaying 5 results from an estimated 5 matches for "value1200".

Did you mean: value120
2014 Aug 08
2
Cyberpower Value1200E might not need 0.667 battery scaling
...ry scale is applied that goes down to 17.7V. upsc output: battery.charge: 100 battery.charge.low: 10 battery.charge.warning: 20 battery.mfr.date: CPS battery.runtime: 3012 battery.runtime.low: 300 battery.type: PbAcid battery.voltage: 17.7 battery.voltage.nominal: 24 device.mfr: CPS device.model: Value1200E device.type: ups driver.name: usbhid-ups driver.parameter.offdelay: 20 driver.parameter.ondelay: 1 driver.parameter.pollfreq: 30 driver.parameter.pollinterval: 2 driver.parameter.port: auto driver.version: 2.7.2 driver.version.data: CyberPower HID 0.3 driver.version.internal: 0.38 input.transfer.h...
2014 Aug 08
0
Cyberpower Value1200E might not need 0.667 battery scaling
On Aug 7, 2014, at 10:18 PM, Matthew Stapleton <matthew4196 at gmail.com> wrote: > I just got a Cyberpower SOHO Value 1200 ELCD UPS and even with nut 2.7.2, it appears to report battery voltage too low due to the battery scaling function (In drivers/cps-hid.c). Even though the ups has usb id: 0764:0501, UPS.PowerSummary.Voltage reports 26.6 for the 24V batteries so when the 0.667
2014 Aug 11
1
Cyberpower Value1200E might not need 0.667 battery scaling
Attached is the first 32 seconds of the driver output after applying the patch which fixes the battery scaling problem for this UPS. Matthew Stapleton Email: matthew4196 at gmail.com On 10/08/14 01:27, Charles Lepple wrote: > On Aug 8, 2014, at 9:15 AM, Charles Lepple <clepple at gmail.com> wrote: > >> On Aug 7, 2014, at 10:52 PM, Charles Lepple <clepple at gmail.com>
2014 Aug 09
0
Cyberpower Value1200E might not need 0.667 battery scaling
On Aug 8, 2014, at 9:15 AM, Charles Lepple <clepple at gmail.com> wrote: > On Aug 7, 2014, at 10:52 PM, Charles Lepple <clepple at gmail.com> wrote: > >> On Aug 7, 2014, at 10:18 PM, Matthew Stapleton <matthew4196 at gmail.com> wrote: >> >>> I just got a Cyberpower SOHO Value 1200 ELCD UPS and even with nut 2.7.2, it appears to report battery voltage
2014 Aug 08
2
Cyberpower Value1200E might not need 0.667 battery scaling
On Aug 7, 2014, at 10:52 PM, Charles Lepple <clepple at gmail.com> wrote: > On Aug 7, 2014, at 10:18 PM, Matthew Stapleton <matthew4196 at gmail.com> wrote: > >> I just got a Cyberpower SOHO Value 1200 ELCD UPS and even with nut 2.7.2, it appears to report battery voltage too low due to the battery scaling function (In drivers/cps-hid.c). Even though the ups has usb id: