battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 04
4
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...at localhost ONBATT SYSLOG+EXEC
>>
>> 3. A <notify type> "ALARM" as you propose.
>>
>
> good ideas
>
there is a Github issue: https://github.com/networkupstools/nut/issues/415
+ a branch with the implementation:
https://github.com/networkupstools/nut/tree/upsmon_alarm
For now:
- upsmon can react on the ALARM notify type, as with other events, and
WALL+SYSLOG+EXEC...
- I've also fixed the CGI to expose the ALARM flag, which was not done.
A possible improvement would be to send the content of ups.alarm, but that
requires more thinking and time.
And the curre...
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 04
0
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On 04/04/17 15.19, Arnaud Quette wrote:
>
[cuuut]
> there is a Github issue: https://github.com/networkupstools/nut/issues/415
> + a branch with the implementation:
> https://github.com/networkupstools/nut/tree/upsmon_alarm
>
> For now:
> - upsmon can react on the ALARM notify type, as with other events, and
> WALL+SYSLOG+EXEC...
> - I've also fixed the CGI to expose the ALARM flag, which was not done.
>
> A possible improvement would be to send the content of ups.alarm, but that
> requires...
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 10
0
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...-04 14:18 GMT+02:00 Jon Bendtsen <jon.bendtsen at jonix.dk
> <mailto:jon.bendtsen at jonix.dk>>:
[cuuuuut]
>
> there is a Github issue: https://github.com/networkupstools/nut/issues/415
> + a branch with the implementation:
> https://github.com/networkupstools/nut/tree/upsmon_alarm
>
> For now:
> - upsmon can react on the ALARM notify type, as with other events, and
> WALL+SYSLOG+EXEC...
> - I've also fixed the CGI to expose the ALARM flag, which was not done.
>
> A possible improvement would be to send the content of ups.alarm, but that
> requires...
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 04
2
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On Tue, 4 Apr 2017, Arnaud Quette wrote:
> Hi Jon, Stuart and the list
>
> 2017-04-04 1:09 GMT+02:00 Stuart Gathman <stuart at gathman.org>:
> Which NOTIFYCMD is run when there is an ALARM?
> Have you specified that in your upsmon.conf?
>
> And that is the question of the hour.? How do you specify that?? Note
> that this is not the REPLBATT